Danfoss DH Standard Welded Stations Type DSP 1 MAXI CEE

Data sheet
Danfoss DH Standard Welded Stations
Type DSP 1 MAXI CEE
General description and
application
District heating transfer stations provide the link
between district heating suppliers and customers’
systems. They incorporate the necessary equipment
to tailor the supplied heat to the needs of the object
premises as specified in the heating supply contract.
In this they need to comply with all applicable
standards and with the supplier’s technical
connection conditions.Indirect connections (in
which district heating and in-house systems are
hydraulically isolated)incorporate components to
separate the systems (heat exchanger), to limit the
flow volume to that specified in the contract,
regulate the secondary supply temperature and
measure the energy consumption. The system
described here is a standard type in which one of
3 types of pump modules and different options
can be connected on the secondary. Thus, this
system is especially suitable for District Heating
applications.
Primary
Maximum operating
parameters
Maximum permissible supply temperature, primary
Maximum permissible operating pressure, primary
Rated pressure, primary
Maximum permissible pressure differential, primary
Maximum permissible flow volume, primary
TVP
PZP
PN
DPP
VPP
130°C / (150 °C for material design components)
16 bar (g)
16
12 bar (PN16)
10,0 m3/h for w <= 1,2 m/s
TVS
100 °C
PZS
PN
VPS
3 bar(g)
10
19,5 m3/h for w <= 1,4 m/s
Secondary
Maximum permissible supply temperature,
secondary
Maximum permissible operating pressure, secondary
Rated pressure, secondary
Maximum permissible flow volume, secondary
Technical
data
PZP
VPP
type max. max.
no. [bar(g)] [m3/h]
DN
pri.
AVQM XB59M VPS
QP*
KVS
no.
max. DN
[m3/h] [m3/h] plates [m3/h] sec.
max. max. max.
dpp* dpp** dps
[kPa] [kPa] [kPa]
Pump
Head
max Width Depth Height
[m]
[mm] [mm] [mm]
mass
**
[kg]
exp.
vessel
***
[l]
01
16,0
3,5
32
3,5
8,0
30
5,5
50
51
55
25
7,50
1367
774
1772
131
150
02
16,0
3,5
32
3,5
8,0
40
6,6
50
54
60
21
7,50
1367
774
1772
136
200
11
25,0
6,0
32
6,0
12,5
50
8,8
50
55
58
25
7,50
1367
774
1772
144
300
12
25,0
6,0
32
6,0
12,5
80
11,0
50
52
57
23
7,00
1367
774
1772
153
500
21
25,0
8,2
40
10,0
16,0
80
15,4
65
51
58
19
7,50
1367
774
1772
166
500
22
25,0
8,2
40
10,0
16,0
110
19,7
65
55
60
24
7,50
1367
774
1772
175
750
31
25,0
10,0
50
10,0
20,0
110
19,7
65
55
62
33
7,50
1367
774
1772
184
750
32
25,0
10,0
50
10,0
20,0
140
24,1
65
57
66
31
6,50
1367
774
1772
195
750
* without heatmeter (HM) / include insert
** include heatmeter (HM) SONOMETER 1100
*** is not included. The intent is only recommended. Please check your conditions
DEN-SMT/PL
VD.IQ.N1.02
© Danfoss 04/2014
1
Data sheet
Materials
Danfoss DH Standard Welded Stations
Type DSP 1 MAXI CEE
Pipes and pipe fittings, flanges, threaded nuts
Heat exchanger
Fittings
P235GH-TC1, C22.8, CuSn5Pb5Zn5-C (RG-5)
1.4404 with CU brazing compound
CuSn5Pb5Zn5-C (RG-5), ST37.0,
EN-GJS-400-18-LT (GGG40.3)
PU-Hardfoam, black, λ = 0,027 W/mK
Insulation
Function
Hot water drawn from the pipeline of the local or
district heating supply company is fed into the
station at an appropriate temperature and pressure,
which may be higher in winter than in summer.
In the primary supply line this hot water will flow
through a shut-off valve and a dirt trap / strainer.
The supply and return lines will incorporate
a thermometer and a manometer to register the
temperature and pressure.
There will also be regulatory equipment in the
return lines of the primary as specified by the circuit
design.
The cooled heating water then flows back to the
local or district heating supply company via the
primary return pipe.
On secondary side 3 types of pump modules and
different options can be connected.
Circuit diagram
DSL
210
440
HPU
200
230
220
S1
500
410
100
STW
400
410
430
10
S3
M1
120
40
200
MAG
20 S5
440
270
EXP
280
290
DSP 1 MAXI
200
Shut-off device for primary (left/right conn.)
220
Dirt trap / strainer
430
Manometer
400
Thermometer
40
Insert / optional Heatmeter
20
Motorized Combi (Control) valve
M1
Electrical actuator
S5
Return temperature limiter primary
270
High-pressure drain valve
10
Heat exchanger
Optional sheet metal harcover (accessory)
2
DSL
HPU
210
Heating Pump
Shut-off device secondary
290
Refilling line (accessories)
VD.IQ.N1.02
© Danfoss 04/2014
100
S3
EXP
MAG
280
230
440
500
S1
Safety valve
Supply temperature sensor secondary
Expansion Vessel (delivered by costumer)
Pressure retention connector
Drain valve
Dirt trap / strainer
Manometer
Electronic controller
Outdoor sensor
410
440
Thermometer
Manometer
DEN-SMT/PL
Data sheet
Type designation
Danfoss DH Standard Welded Stations
DSP 1 MAXI
-
Base type
Type designation
for Pump Module
PD
P=Electrical box
Controller Danfoss
D = ECL310
DSL
-
Base type
-
Type DSP 1 MAXI CEE
11
LT
Type No.
see Page 1
LT:
PN16/140°C
S100
Lenght of insert for HM or
HM SONOMETER 1100 QP ..
S035 = Sonometer 1100 QP 3,5
S060 = Sonometer 1100 QP 6,0
S100 = Sonometer 1100 QP 10,0
I260 = Insert 260 mm / G1 ¼”
I300 = Insert 300 mm / G2”
40 –120 F
type of pump
1772
482
Dimensions
1367
750
139
345
285
591
774
217
1150
DEN-SMT/PL
VD.IQ.N1.02
© Danfoss 04/2014
3
Data sheet
Capacity range
Temperature programs
Danfoss DH Standard Welded Stations
Capacities
100
125
150
Type DSP 1 MAXI CEE
175
200
Temperatures
primary/secondary
250
300
350
400
450
500
550
Type
130 -> 75 / 90 < 70 °C
01
01
02
11
11
12
21
21
22
31
32
32
120 -> 65 / 80 < 60 °C
01
01
02
11
11
12
21
21
22
31
32
32
110 -> 60 / 75 < 55 °C
01
01
02
11
11
12
21
22
31
32
32
32
110 -> 55 / 70 < 50 °C
01
02
02
11
12
12
21
22
31
32
32
32
90 -> 60 /75 < 55 °C
01
02
11
11
12
21
21
31
Please be aware, that in case of high differential temperature primary heatmeters or inserts for
can be oversized!
use impossible
Ordering codes
Standard substation
Code
004F4936
Example for ordering:
4
Type
DSP 1 MAXI-PD-01 LT I260
Pump Module
Type
no.
Code
Code
accessories
01
087H3802
Application Key A230
004F4940
DSP 1 MAXI-PD-01 LT S035
01
004F4937
DSP 1 MAXI-PD-02 LT I260
02
004F4941
DSP 1 MAXI-PD-02 LT S035
02
004F4819
DSP 1 MAXI-PD-11 LT I260
11
004F4842
DSP 1 MAXI-PD-11 LT S060
11
004F4830
DSP 1 MAXI-PD-12 LT I260
12
004F5907
DSL 40-120F
DSL40-120F Pump Module:
High Efficiency Pump Magna3
40 -120F
+Thermometer/Manometer/
ball valves DN50
004F4843
DSP 1 MAXI-PD-12 LT S060
12
004F4831
DSP 1 MAXI-PD-21 LT I300
21
004F5908
004F4844
DSP 1 MAXI-PD-21 LT S100
21
004F4832
DSP 1 MAXI-PD-22 LT I300
22
004F4845
DSP 1 MAXI-PD-22 LT S100
22
DSL50 -120F Pump Module:
High Efficiency Pump Magna3
50 -120F
+Thermometer/Manometer/
ball valves DN65
004F4833
DSP 1 MAXI-PD-31 LT I300
31
004F4846
DSP 1 MAXI-PD-31 LT S100
31
004F4834
DSP 1 MAXI-PD-32 LT I300
32
004F4847
DSP 1 MAXI-PD-32 LT S100
32
DSL 50-120F
004F5909
DSL 50-150F
substation 210 kW, type 12 with heatmeter
DSL50-150F - Pump Module:
High Efficiency Pump Magna3
50 -150F
+Thermometer/Manometer/
ball valves DN65
DSP 1 MAXI
DSP 1 MAXI-PD-12 LT I260
Type 12
Application Key
Pump Module
DSL 40-120F
Optional
Refilling line
004F4843
087H3802
Sheet hardcover
004F5907
Refilling line:
- 2 pcs. Ball valves valves DN25
+ Pressure reducer
+ flowmeter
+connection port for
expansion vessel
VD.IQ.N1.02
004F5910
004F4931
004F5910