Carisma Coanda CCN Carisma Coanda CCN-ECM

NE
rd
l
oa
co
l b s to
ro bu ro
nt d p
co r Mo ion
t
MB fo ica
n
mu
m
co
W
Air Conditioning
One Way Cassette Fan Coils
Carisma Coanda CCN
Carisma Coanda CCN-ECM
QUALITY MANAGEMENT SYSTEMS
ISO 9001 - Cert. n° 0545/5
www.eurovent-certification.com
www.certiflash.com
ENVIRONMENTAL COMFORT
CONTENTS
Introduction
CCN Version
• Main components
• Dimensions, Weight, Water content
• EUROVENT certifications
• Working conditions and Air throw
• Emissions
• Water side pressure drop
• Accessories
• Control operations
• Wall electronic controls
• Speed switches
• Electronic control accessories
• Wireless control system
• Controls and units MB version
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
3
4
6
7
8
12
13
15
16
18
19
20
22
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
23
24
26
27
28
32
33
35
36
37
CCN-ECM Version
• Main components
• Dimensions, Weight, Water content
• EUROVENT certifications
• Working conditions and Air throw
• Emissions
• Water side pressure drop
• Accessories
• CCN–ECM configuration
• CR-T-ECM Wall electronic control
• CR-T-ECM Accessories
CCN / CCN-ECM Version
• Controls and units MB version
• Management system for a network of units
Page 38
Page 44
Thanks to the particular air handling section, Carisma Coanda
cassette units generate an airflow with a “coanda” effect. The
unit is suitable for installation in a suspended ceiling. Air intake
is from the bottom while the air supply is parallel to the ceiling,
through practical and functional intake and outlet grids.
The “coanda” effect creates excellent circulation of the air
inside the room.
In addition to the traditional AC asynchronous motors are
available a innovative electronic motors with extremely low
energy consumption, controlled by an inverter board and
identified by ECM.
The EC motors allow to decrease electric consumption by
more than 50% compared to traditional AC asynchronous
motors. They enable to control the air flow continuously and
the ambient temperature with precision, with further benefits
in terms of very low noise levels thanks to the reduced average
working speed.
Every unit can be supplied with 1 coil (2 pipe system) and
possibly an electric heating element, or with 2 coils (4 pipe
system) with one or two rows, for water supply at a low
temperature.
Fresh air may be mixed with room air.
A condensate pump may also be supplied as an accessory.
In addition to the conventional temperature and speed control
systems, there is also the possibility to control operation
of each unit through a single remote control with central
supervisor software installed on a PC (Sabianet).
With AC asynchronous motor units it is also possible to use the completely wireless electronic control
system based on radio communication, Free Sabiana, with great advantages in terms of installation
flexibility and maximum precision in measuring room temperature.
Sabiana take part to the Eurovent program of fan coil performance certification.
The official figures are published in the Eurovent web sites www.eurovent-certification.com and
www.certiflash.com. The tested performances are:
• Cooling total emission at the following conditions:
- water temperature
+7°C E.W.T.
+12°C L.W.T.
- air temperature
+27°C dry bulb
+19°C wet bulb
• Cooling sensible emission at the following conditions:
- water temperature
+7°C E.W.T.
+12°C L.W.T.
- air temperature
+27°C dry bulb
+19°C wet bulb
• Heating emission (2-pipe units) at the following conditions:
- water temperature
+50°C E.W.T.
- air temperature
+20°C
- water flow rate as for the cooling conditions
• Heating emission (4-pipe units) at the following conditions:
- water temperature
+70°C E.W.T.
+60°C L.W.T.
- air temperature
+20°C
• Fan absorption
• Water pressure drop
• Sound power
Main components
Carisma
Coanda
CCN Version
Constructional features of the main components
Casing
Made from 1 mm galvanized steel insulated with polyolefin (PO) foam (class M1).
Diffuser with intake grille
In prepainted metal sheet in RAL 9003 colour with intake grille that can be opened for inspection and maintenance of the air filter.
Air Filter
Polypropylene cellular fabric regenerating filter.
Fan Assembly
The fans have aluminium or plastic blades directly keyed on the motor with double aspiration and they are dynamically and
statically balanced during manufacture in order to have an extremely quiet operation.
Electric motor
The motor is wired for single phase and has six speeds, three of which are connected, with capacitor. The motor is fitted on
sealed for life bearings and is secured on anti-vibration and self-lubricating mountings. Internal thermal protection with automatic
reset, protection IP 20, class B.
The speeds connected in the factory are indicated by “MIN, MED and MAX” in the following tables.
Heat exchange coil
It is manufactured from drawn copper tube and the aluminium fins are mechanically bonded onto the tube by an expansion
process. The coil has two 1/2 inch BSP internal connections and 1/8 inch BSP air vent and drain.
The heat exchanger is not suitable for use in corrosive atmosphere or in environments where aluminium may be subject to
corrosion.
The connection side cannot be changed on site.
Condensate Collection Tray
Made from plastic (ABS UL94 HB), with an “L”-shape fitted on the inner casing; the try is insulated with polyolefin (PO) foam
(class M1). The outside diameter of the condensate discharge pipe is 15mm.
Round diffuser
The Carisma Coanda one-way cassette units are supplied
with round diffusers suitably designed to generate an airflow
with “coanda” effect. The direction of diffuser air flow can be
adjusted on site.
3
Dimensions, Weight,
Water content
Carisma Coanda Gr 1 - 3 diffusers
CCN Version
Carisma
Coanda
Carisma Coanda Gr 2 - 5 diffusers
A
592
592
A
Carisma Coanda Gr 3 - 6 diffusers
592
A
Water
inlet
Water
outlet
Coil connections
on the left
4
Dimensions, Weight,
Water content
CCN Version
Carisma
Coanda
W
730
370
DIMENSIONS (mm)
Model
A
E
F
W
1
2
3
592
454
78
750
970
884
43
1130
1192
1099
46,5
1350
weight (kg)
Model
Rows
3
3+1
3+2
4
4+1
1
Weight packed unit
2
3
Weight unpacked unit
1
2
3
18
20
23
20
23
34
40
46
37
42
44
51
58
48
54
16
19
22
18
21
33
38
43
35
40
42
48
54
45
51
Water content (l)
Rows
Model
3
4
+1
+2
1
2
3
0,6
0,8
0,2
0,4
1,3
1,7
0,4
0,8
1,7
2,4
0,5
1,0
5
CCN Version
Carisma
Coanda
EUROVENT certifications
www.eurovent-certification.com
www.certiflash.com
Technical features
2-pipe units
The following standard rating conditions are used:
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
Model
CCN 13
1 (E) 2 (E)
3
Speed
MIN MED
Air flow
m3/h 140 180 220
Cooling total emission (E)
kW 0,88 1,06 1,26
Cooling sensible emission (E) kW 0,66 0,81 0,98
Heating (E)
kW 1,08 1,33 1,59
∆P Cooling (E)
kPa
2,4
3,3
4,5
∆P Heating (E)
kPa
1,8
2,6
3,5
Fan (E)
W
16
22
32
Sound power (E)
Lw dB(A) 35
41
46
Sound pressure (*)
Lp dB(A) 26
32
37
Model
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 50°C E.W.T.
Water flow rate as for the cooling conditions
CCN 23
4
5 (E)
6
MAX
245 280 305
1,35 1,50 1,60
1,06 1,18 1,27
1,73 1,93 2,08
5,1
6,1
6,8
4,0
4,9
5,6
38
49
66
49
52
55
40
43
46
CCN 14
1 (E) 2 (E)
3
Speed
MIN MED
Air flow
m3/h 140 180 220
Cooling total emission (E)
kW 0,97 1,19 1,44
Cooling sensible emission (E) kW 0,71 0,88 1,07
Heating (E)
kW 1,14 1,42 1,72
∆P Cooling (E)
kPa
4,7
6,7
9,2
∆P Heating (E)
kPa
3,7
5,4
7,6
Fan (E)
W
16
22
32
Sound power (E)
Lw dB(A) 35
41
46
Sound pressure (*)
Lp dB(A) 26
32
37
4
245
1,55
1,17
1,88
10,6
8,8
38
49
40
1 (E) 2 (E)
3
4 (E)
5
MIN MED
MAX
200 240 305 380 470
1,37 1,62 1,97 2,37 2,81
1,00 1,19 1,47 1,77 2,13
1,60 1,91 2,35 2,86 3,43
2,9
3,9
5,5
7,6 10,3
2,3
3,1
4,5
6,3
8,4
24
27
34
44
57
33
36
42
48
54
24
27
33
39
45
CCN 33
6
560
3,23
2,47
3,95
13,1
10,8
71
57
48
1 (E)
MIN
290
1,97
1,44
2,30
6,4
5,2
27
35
26
6
1
560
3,58
2,67
4,44
21,7
17,9
71
57
48
290
2,05
1,48
2,38
4,7
3,9
27
35
26
2
360
2,37
1,74
2,79
8,8
7,3
33
41
32
CCN 24
5 (E)
MAX
280
1,74
1,31
2,10
12,9
10,7
49
52
43
6
305
1,87
1,42
2,27
14,6
12,3
66
55
46
1 (E) 2 (E)
3
4 (E)
5
MIN MED
MAX
200 240 305 380 470
1,44 1,72 2,12 2,57 3,09
1,04 1,24 1,54 1,88 2,28
1,69 2,03 2,54 3,12 3,79
4,4
6,0
8,6 12,1 16,8
3,5
4,8
7,1 10,2 13,6
24
27
34
44
57
33
36
42
48
54
24
27
33
39
45
3 (E)
MED
440
2,84
2,11
3,37
12,1
9,8
42
46
37
4 (E)
MAX
540
3,34
2,51
4,02
16,2
13,4
59
52
43
5
6
620
3,75
2,83
4,53
19,8
16,3
72
55
46
680
4,05
3,07
4,88
22,7
18,6
84
57
48
5 (E)
MAX
620
4,02
2,98
4,77
15,5
12,6
72
55
46
6
CCN 34
2 (E)
MIN
360
2,49
1,81
2,90
6,7
5,5
33
41
32
3
440
3,00
2,20
3,51
9,3
7,3
42
46
37
4 (E)
MED
540
3,56
2,63
4,20
12,6
10,0
59
52
43
680
4,36
3,25
5,20
17,9
14,6
84
57
48
4-pipe units
The following standard rating conditions are used:
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
Model
CCN 13 + 1
1 (E) 2 (E)
3
Speed
MIN MED
Air flow
m3/h 140 180 220
Cooling total emission (E)
kW 0,88 1,06 1,26
Cooling sensible emission (E) kW 0,66 0,81 0,98
Heating (E)
kW 0,92 1,08 1,25
∆P Cooling (E)
kPa
2,4
3,3
4,5
∆P Heating (E)
kPa
1,6
2,1
2,7
Fan (E)
W
16
22
32
Sound power (E)
Lw dB(A) 35
41
46
Sound pressure (*)
Lp dB(A) 26
32
37
(E) = Eurovent certified performance.
4
5 (E)
6
MAX
245 280 305
1,35 1,50 1,60
1,06 1,18 1,27
1,34 1,47 1,56
5,1
6,1
6,8
3,1
3,6
4,0
38
49
66
49
52
55
40
43
46
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 70°C E.W.T. / + 60°C L.W.T.
CCN 23 + 1
1 (E) 2 (E)
3
4 (E)
5
MIN MED
MAX
200 240 305 380 470
1,37 1,62 1,97 2,37 2,81
1,00 1,19 1,47 1,77 2,13
1,49 1,71 2,02 2,35 2,73
2,9
3,9
5,5
7,6 10,3
0,9
1,2
1,6
2,0
2,6
24
27
34
44
57
33
36
42
48
54
24
27
33
39
45
CCN 33 + 1
6
560
3,23
2,47
3,07
13,1
3,2
71
57
48
1 (E)
MIN
290
1,97
1,44
2,12
6,4
2,0
27
35
26
2
360
2,37
1,74
2,47
8,8
2,6
33
41
32
3 (E)
MED
440
2,84
2,11
2,87
12,1
3,4
42
46
37
4 (E)
MAX
540
3,34
2,51
3,30
16,2
4,3
59
52
43
5
6
620
3,75
2,83
3,64
19,8
5,1
72
55
46
680
4,05
3,07
3,89
22,7
5,8
84
57
48
MIN-MED-MAX = Standard connected speeds.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room
and a reverberation time of 0.5 sec.
6
CCN Version
Carisma
Coanda
Working conditions and Air throw
Working conditions
Max. entering water temperature..................... + 80 °C
MIn. entering water temperature........................ + 5 °C
for entering water temperatures below + 5°C, contact “SABIANA” technical department
Max. rated pressure............................................1000 kPa (10 bars)
Installation height (m)
Model
1
2
3
Minimum
Maximum
2,6
3,2
2,6
3,2
2,6
3,5
Water flow limits for main coil (l/h)
3 rows
4 rows
Model
13
23
33
14
24
34
Minimum
Maximum
100
500
150
1000
150
1500
100
750
150
1000
200
2000
Water flow limits for additional coil (l/h)
1 row
2 rows
Model
1
2
3
1
2
3
Minimum
Maximum
50
250
100
450
100
650
50
250
100
450
100
650
1
2
3
66
0,30
71
0,32
84
0,38
Motor electrical data (max. absorption)
Model
230/1 50Hz
W
A
Air throw
C1 - Heating
L
C2 - Cooling
L
Model
Air throw
L (m)
C1
C2
Carisma Coanda CCN 1
Carisma Coanda CCN 2
Carisma Coanda CCN 3
1
1
1
2
3
4
5
6
3,8 4,5 5,8 6,3 6,8 7,2 4
3 3,6 4,6 5 5,4 5,7 3,2
2
5
4
3
4
5
6
2
3
4
5
6
6,1 7
8
9 4,5 5,2 6,3 7,5 8,8 9,5
4,8 5,6 6,4 7,2 3,6 4,1 5
6
7 7,6
7
CCN Version
Carisma
Coanda
Emissions
Cooling emission of 3 row coil
Entering air temperature: +27°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN
13
CCN
23
CCN
33
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
1,73
1,62
1,46
1,36
1,14
0,95
3,47
3,03
2,54
2,12
1,74
1,47
4,36
4,03
3,59
3,05
2,55
2,11
1,27
1,18
1,06
0,97
0,81
0,66
2,46
2,13
1,77
1,46
1,19
1,00
3,06
2,82
2,50
2,10
1,74
1,44
298
279
251
234
196
163
597
521
437
365
299
253
750
693
617
525
439
363
7,8
7,0
5,8
5,1
3,8
2,7
14,9
11,7
8,6
6,3
4,4
3,3
25,8
22,5
18,4
13,8
10,0
7,2
1,54
1,44
1,30
1,21
1,02
0,85
3,12
2,72
2,29
1,91
1,57
1,32
3,91
3,63
3,23
2,75
2,30
1,91
1,19
1,11
0,99
0,92
0,76
0,62
2,32
2,00
1,66
1,37
1,12
0,94
2,88
2,65
2,35
1,98
1,64
1,35
265
248
224
208
175
146
537
468
394
329
270
227
673
624
556
473
396
329
6,3
5,6
4,7
4,2
3,1
2,2
12,2
9,6
7,1
5,2
3,6
2,7
21,2
18,6
15,2
11,4
8,3
6,0
1,14
1,07
0,97
0,91
0,77
0,64
2,36
2,06
1,74
1,46
1,20
1,02
2,98
2,77
2,47
2,11
1,77
1,47
1,04
0,97
0,86
0,80
0,66
0,54
2,02
1,74
1,45
1,19
0,97
0,81
2,51
2,31
2,05
1,72
1,42
1,17
196
184
167
157
132
110
406
354
299
251
206
175
513
476
425
363
304
253
3,7
3,3
2,8
2,5
1,8
1,3
7,4
5,8
4,3
3,2
2,2
1,7
13,0
11,4
9,3
7,0
5,2
3,7
0,91
0,85
0,76
0,70
0,59
0,48
1,78
1,54
1,28
1,06
0,86
0,72
2,22
2,04
1,81
1,52
1,26
1,04
0,91
0,85
0,76
0,70
0,59
0,48
1,78
1,54
1,28
1,06
0,86
0,72
2,22
2,04
1,81
1,52
1,26
1,04
157
146
131
120
101
83
306
265
220
182
148
124
382
351
311
261
217
179
2,5
2,2
1,8
1,5
1,1
0,8
4,4
3,4
2,5
1,8
1,2
0,9
7,6
6,6
5,3
3,9
2,8
2,0
Entering air temperature: +26°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN
13
CCN
23
CCN
33
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
1,53
1,43
1,30
1,21
1,02
0,84
3,10
2,70
2,27
1,90
1,55
1,31
3,89
3,60
3,21
2,73
2,28
1,89
1,19
1,11
0,99
0,92
0,76
0,62
2,32
2,00
1,67
1,38
1,12
0,94
2,89
2,66
2,36
1,98
1,64
1,36
263
246
224
208
175
144
533
464
390
327
267
225
669
619
552
470
392
325
6,3
5,6
4,7
4,1
3,1
2,2
12,2
9,5
7,1
5,1
3,6
2,7
21,2
18,5
15,1
11,3
8,3
6,0
1,34
1,26
1,14
1,06
0,90
0,74
2,74
2,39
2,01
1,68
1,38
1,17
3,45
3,20
2,85
2,42
2,03
1,69
1,12
1,04
0,93
0,86
0,71
0,58
2,17
1,87
1,56
1,29
1,05
0,88
2,70
2,49
2,21
1,85
1,54
1,27
230
217
196
182
155
127
471
411
346
289
237
201
593
550
490
416
349
291
5,0
4,4
3,7
3,3
2,4
1,8
9,7
7,6
5,7
4,1
2,9
2,2
17,0
14,9
12,2
9,1
6,7
4,8
0,99
0,92
0,80
0,75
0,63
0,53
1,96
1,72
1,46
1,23
1,01
0,86
2,50
2,32
2,08
1,78
1,49
1,24
0,99
0,92
0,80
0,74
0,61
0,50
1,87
1,61
1,34
1,11
0,90
0,75
2,33
2,15
1,90
1,60
1,32
1,09
170
158
138
129
108
91
337
296
251
212
174
148
430
399
358
306
256
213
2,9
2,5
2,0
1,7
1,3
1,0
5,3
4,2
3,2
2,3
1,7
1,2
9,5
8,4
6,9
5,2
3,8
2,8
0,83
0,77
0,69
0,64
0,54
0,44
1,63
1,40
1,18
0,97
0,79
0,66
2,03
1,87
1,65
1,40
1,15
0,95
0,83
0,77
0,69
0,64
0,54
0,44
1,63
1,40
1,18
0,97
0,79
0,66
2,03
1,87
1,65
1,40
1,15
0,95
143
132
119
110
93
76
280
241
203
167
136
114
349
322
284
241
198
163
2,1
1,8
1,5
1,3
1,0
0,7
3,8
2,9
2,1
1,5
1,0
0,8
6,5
5,6
4,5
3,4
2,4
1,7
Entering air temperature: +25°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN
13
CCN
23
CCN
33
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
1,34
1,26
1,14
1,06
0,89
0,74
2,73
2,38
2,01
1,68
1,38
1,16
3,44
3,19
2,84
2,41
2,02
1,68
1,12
1,04
0,93
0,86
0,71
0,58
2,18
1,88
1,56
1,29
1,05
0,88
2,71
2,50
2,21
1,86
1,54
1,27
230
217
196
182
153
127
470
409
346
289
237
200
592
549
488
415
347
289
5,0
4,5
3,7
3,3
2,4
1,8
9,7
7,7
5,7
4,1
2,9
2,2
17,0
14,9
12,2
9,1
6,7
4,8
1,15
1,08
0,98
0,91
0,77
0,64
2,37
2,07
1,75
1,46
1,20
1,02
2,99
2,78
2,48
2,11
1,77
1,47
1,04
0,97
0,87
0,80
0,66
0,54
2,03
1,75
1,46
1,20
0,98
0,82
2,53
2,33
2,06
1,73
1,43
1,18
198
186
169
157
132
110
408
356
301
251
206
175
514
478
427
363
304
253
3,8
3,4
2,9
2,5
1,9
1,4
7,5
5,9
4,4
3,2
2,3
1,7
13,2
11,6
9,5
7,1
5,2
3,8
0,91
0,85
0,76
0,70
0,59
0,48
1,79
1,54
1,29
1,06
0,86
0,69
2,22
2,05
1,81
1,53
1,26
1,01
0,91
0,85
0,76
0,70
0,59
0,48
1,79
1,54
1,29
1,06
0,86
0,69
2,22
2,05
1,81
1,53
1,26
1,00
157
146
131
120
101
83
308
265
222
182
148
119
382
353
311
263
217
174
2,5
2,2
1,8
1,6
1,1
0,8
4,5
3,5
2,5
1,8
1,2
0,9
7,7
6,7
5,4
4,0
2,9
1,9
0,75
0,70
0,63
0,58
0,48
0,40
1,48
1,27
1,07
0,88
0,71
0,60
1,84
1,70
1,50
1,27
1,05
0,86
0,75
0,70
0,63
0,58
0,48
0,40
1,48
1,27
1,07
0,88
0,71
0,60
1,84
1,70
1,50
1,27
1,05
0,86
129
120
108
100
83
69
255
218
184
151
122
103
316
292
258
218
181
148
1,7
1,5
1,3
1,1
0,8
0,6
3,2
2,5
1,8
1,3
0,9
0,7
5,5
4,7
3,8
2,8
2,0
1,4
Legend
WT
= Water temperature
= Cooling Total emission
Pc
= Cooling Sensible emission
Ps
Qw
= Water flow
Dp(c) = Water side
pressure drop
Speed
MAX
MED
MIN
Qv
Correction factors for different R.H.
U.R.
48%
46%
8
WT:
Pc
Ps
Pc
Ps
7/12°C
0,95
1,00
0,90
1,00
8/13°C
0,94
1,00
0,88
1,00
10/15°C
1,00
1,00
1,00
1,00
12/17°C
1,00
1,00
1,00
1,00
= Fan speed
= High speed
= Medium speed
= Low speed
= Air flow
CCN Version
Carisma
Coanda
Emissions
Cooling emission of 4 row coil
Entering air temperature: +27°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN
14
CCN
24
CCN
34
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
2,01
1,87
1,67
1,54
1,28
1,05
3,85
3,32
2,76
2,28
1,84
1,54
4,69
4,32
3,83
3,22
2,67
2,20
1,42
1,31
1,16
1,07
0,88
0,71
2,66
2,28
1,88
1,54
1,24
1,04
3,24
2,98
2,62
2,19
1,81
1,48
346
322
287
265
220
181
662
571
475
392
316
265
807
743
659
554
459
378
16,7
14,6
12,1
10,5
7,6
5,3
24,7
19,0
13,7
9,8
6,8
4,9
20,3
17,6
14,2
10,5
7,5
5,4
1,80
1,68
1,50
1,39
1,15
0,94
3,47
2,99
2,49
2,06
1,67
1,40
4,22
3,89
3,45
2,91
2,41
1,99
1,33
1,23
1,09
1,00
0,83
0,67
2,50
2,14
1,77
1,45
1,17
0,97
3,05
2,80
2,47
2,06
1,70
1,39
310
289
258
239
198
162
597
514
428
354
287
241
726
669
593
501
415
342
13,7
12,0
9,9
8,6
6,2
4,4
20,4
15,7
11,4
8,1
5,6
4,1
16,8
14,6
11,8
8,7
6,3
4,5
1,36
1,27
1,14
1,06
0,88
0,72
2,65
2,30
1,92
1,59
1,29
1,09
3,23
2,98
2,65
2,24
1,86
1,54
1,16
1,07
0,95
0,87
0,72
0,58
2,18
1,86
1,54
1,26
1,01
0,85
2,65
2,44
2,15
1,79
1,48
1,21
234
218
196
182
151
124
456
396
330
273
222
187
556
513
456
385
320
265
8,2
7,3
6,0
5,3
3,8
2,7
12,6
9,7
7,1
5,1
3,5
2,6
10,4
9,0
7,3
5,4
3,9
2,8
1,02
0,95
0,84
0,77
0,64
0,52
1,93
1,65
1,36
1,11
0,85
0,72
2,34
2,15
1,90
1,59
1,30
1,01
1,02
0,95
0,84
0,77
0,64
0,52
1,93
1,65
1,36
1,11
0,85
0,71
2,34
2,15
1,90
1,59
1,30
1,01
175
163
144
132
110
89
332
284
234
191
146
124
402
370
327
273
224
174
4,9
4,3
3,5
3,0
2,1
1,5
7,0
5,4
3,8
2,7
1,7
1,2
5,8
5,0
4,0
2,9
2,1
1,3
Entering air temperature: +26°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN
14
CCN
24
CCN
34
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
1,79
1,67
1,49
1,38
1,15
0,94
3,44
2,97
2,47
2,04
1,65
1,39
4,19
3,87
3,43
2,88
2,39
1,97
1,33
1,23
1,10
1,01
0,83
0,67
2,51
2,15
1,77
1,45
1,17
0,98
3,06
2,81
2,47
2,07
1,70
1,40
308
287
256
237
198
162
592
511
425
351
284
239
721
666
590
495
411
339
13,6
12,0
9,9
8,6
6,2
4,3
20,3
15,6
11,3
8,1
5,6
4,1
16,7
14,5
11,7
8,7
6,2
4,4
1,58
1,47
1,32
1,22
1,02
0,83
3,06
2,64
2,20
1,82
1,48
1,24
3,72
3,43
3,05
2,57
2,13
1,76
1,25
1,15
1,03
0,94
0,78
0,63
2,35
2,01
1,66
1,36
1,10
0,91
2,86
2,63
2,31
1,93
1,59
1,31
272
253
227
210
175
143
526
454
378
313
255
213
640
590
525
442
366
303
10,9
9,6
7,9
6,9
5,0
3,5
16,3
12,6
9,2
6,6
4,5
3,3
13,5
11,7
9,5
7,0
5,1
3,6
1,14
1,06
0,96
0,89
0,74
0,61
2,24
1,94
1,62
1,35
1,10
0,92
2,72
2,52
2,24
1,89
1,58
1,31
1,07
0,99
0,88
0,81
0,67
0,54
2,02
1,73
1,43
1,17
0,94
0,78
2,46
2,26
1,99
1,66
1,37
1,12
196
182
165
153
127
105
385
334
279
232
189
158
468
433
385
325
272
225
6,0
5,3
4,4
3,9
2,8
2,0
9,3
7,2
5,3
3,8
2,6
2,0
7,7
6,7
5,4
4,0
2,9
2,1
0,94
0,87
0,77
0,71
0,58
0,47
1,76
1,51
1,25
1,02
0,82
0,68
2,15
1,97
1,74
1,45
1,19
0,98
0,94
0,87
0,77
0,71
0,58
0,47
1,76
1,51
1,25
1,02
0,82
0,68
2,15
1,97
1,74
1,45
1,19
0,98
162
150
132
122
100
81
303
260
215
175
141
117
370
339
299
249
205
169
4,2
3,7
3,0
2,6
1,8
1,3
6,0
4,6
3,3
2,3
1,6
1,1
5,0
4,3
3,5
2,5
1,8
1,3
Entering air temperature: +25°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN
14
CCN
24
CCN
34
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
1,58
1,47
1,32
1,22
1,01
0,83
3,05
2,63
2,19
1,81
1,47
1,23
3,71
3,42
3,03
2,56
2,12
1,75
1,25
1,16
1,03
0,94
0,78
0,63
2,36
2,02
1,66
1,36
1,10
0,92
2,87
2,63
2,32
1,94
1,60
1,31
272
253
227
210
174
143
525
452
377
311
253
212
638
588
521
440
365
301
10,9
9,6
7,9
6,9
5,0
3,5
16,4
12,6
9,2
6,6
4,5
3,3
13,5
11,7
9,5
7,0
5,0
3,6
1,37
1,27
1,14
1,06
0,88
0,72
2,66
2,30
1,92
1,59
1,29
1,08
3,24
2,99
2,65
2,24
1,86
1,54
1,16
1,08
0,96
0,88
0,72
0,58
2,19
1,88
1,55
1,27
1,02
0,85
2,67
2,45
2,16
1,80
1,49
1,22
236
218
196
182
151
124
458
396
330
273
222
186
557
514
456
385
320
265
8,4
7,4
6,1
5,4
3,9
2,7
12,8
9,9
7,2
5,2
3,6
2,6
10,5
9,2
7,4
5,5
4,0
2,8
1,03
0,95
0,84
0,78
0,64
0,52
1,93
1,65
1,31
1,09
0,90
0,76
2,35
2,16
1,91
1,53
1,28
1,07
1,03
0,95
0,84
0,78
0,64
0,52
1,93
1,65
1,31
1,07
0,86
0,72
2,35
2,16
1,91
1,52
1,25
1,03
177
163
144
134
110
89
332
284
225
187
155
131
404
372
329
263
220
184
5,0
4,4
3,5
3,1
2,2
1,5
7,2
5,5
3,6
2,6
1,9
1,4
5,9
5,1
4,1
2,8
2,0
1,5
0,85
0,78
0,70
0,64
0,53
0,43
1,60
1,37
1,14
0,93
0,75
0,62
1,95
1,79
1,58
1,32
1,09
0,89
0,85
0,78
0,70
0,64
0,53
0,43
1,60
1,37
1,14
0,93
0,75
0,62
1,95
1,79
1,58
1,32
1,09
0,89
146
134
120
110
91
74
275
236
196
160
129
107
335
308
272
227
187
153
3,5
3,1
2,5
2,2
1,5
1,1
5,1
3,9
2,8
2,0
1,3
1,0
4,2
3,6
2,9
2,1
1,5
1,1
Correction factors for different R.H.
U.R.
48%
46%
WT:
Pc
Ps
Pc
Ps
7/12°C
0,95
1,00
0,90
1,00
8/13°C
0,94
1,00
0,88
1,00
10/15°C
1,00
1,00
1,00
1,00
12/17°C
1,00
1,00
1,00
1,00
Legend
WT
= Water temperature
= Cooling Total emission
Pc
= Cooling Sensible emission
Ps
Qw
= Water flow
Dp(c) = Water side
pressure drop
Speed
MAX
MED
MIN
Qv
= Fan speed
= High speed
= Medium speed
= Low speed
= Air flow
9
CCN Version
Carisma
Coanda
Emissions
Heating emission of 3 row coil
Entering air temperature: +20°C
WT: 70/60°C
Model
CCN
13
CCN
23
CCN
33
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 60/50°C
WT: 50/40°
WT: 50/45°
WT: 45/40°
Qv
m3/h
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
3,54
3,29
2,94
2,71
2,26
1,84
6,64
5,77
4,79
3,95
3,20
2,68
8,20
7,61
6,73
5,65
4,67
3,85
304
283
253
233
194
158
571
496
412
340
275
230
705
654
579
486
402
331
6,3
5,6
4,6
4,0
2,9
2,0
10,7
8,3
6,0
4,3
2,9
2,2
18,0
15,8
12,7
9,4
6,7
4,8
2,71
2,51
2,25
2,07
1,73
1,41
5,10
4,43
3,68
3,03
2,46
2,07
6,30
5,85
5,18
4,35
3,60
2,96
233
216
194
178
149
121
439
381
316
261
212
178
542
503
445
374
310
255
4,1
3,6
2,9
2,5
1,9
1,3
6,9
5,4
3,9
2,8
1,9
1,4
11,7
10,3
8,3
6,1
4,4
3,1
1,87
1,74
1,56
1,44
1,20
0,98
3,55
3,09
2,57
2,12
1,72
1,45
4,40
4,09
3,62
3,04
2,52
2,08
161
150
134
124
103
84
305
266
221
182
148
125
378
352
311
261
217
179
2,2
1,9
1,6
1,4
1,0
0,7
3,8
3,0
2,1
1,5
1,1
0,8
6,4
5,6
4,6
3,4
2,4
1,7
2,16
2,01
1,80
1,66
1,38
1,12
4,06
3,52
2,93
2,41
1,95
1,64
5,01
4,65
4,11
3,45
2,85
2,35
372
346
310
286
237
193
698
605
504
415
335
282
862
800
707
593
490
404
9,5
8,4
6,9
6,0
4,3
3,0
16,1
12,5
9,0
6,4
4,4
3,3
27,1
23,8
19,2
14,1
10,1
7,2
1,75
1,62
1,45
1,34
1,12
0,91
3,29
2,86
2,38
1,96
1,59
1,33
4,07
3,77
3,34
2,80
2,32
1,91
301
279
249
230
193
157
566
492
409
337
273
229
700
648
574
482
399
329
6,7
5,9
4,8
4,2
3,0
2,1
11,3
8,8
6,4
4,5
3,1
2,3
19,1
16,8
13,5
9,9
7,1
5,1
Heating emission of 4 row coil
Entering air temperature: +20°C
WT: 70/60°C
Model
CCN
14
CCN
24
CCN
34
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 50/40°
WT: 50/45°
WT: 45/40°
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
3,80
3,52
3,14
2,89
2,37
1,92
7,46
6,37
5,22
4,25
3,40
2,82
8,72
8,00
7,04
5,87
4,83
3,96
327
303
270
249
204
165
642
548
449
366
292
243
750
688
605
505
415
341
11,7
10,2
8,4
7,2
5,1
3,5
18,2
13,8
9,7
6,7
4,5
3,3
13,9
12,0
9,6
6,9
4,9
3,5
2,92
2,70
2,42
2,22
1,83
1,48
5,75
4,92
4,03
3,28
2,63
2,18
6,71
6,16
5,42
4,52
3,72
3,06
251
232
208
191
157
127
495
423
347
282
226
187
577
530
466
389
320
263
7,6
6,6
5,5
4,7
3,3
2,3
11,8
9,0
6,3
4,4
3,0
2,2
9,1
7,8
6,2
4,5
3,2
2,3
2,03
1,88
1,69
1,55
1,28
1,03
4,04
3,46
2,84
2,31
1,85
1,54
4,70
4,31
3,80
3,18
2,62
2,15
175
162
145
133
110
89
347
298
244
199
159
132
404
371
327
273
225
185
4,2
3,6
3,0
2,6
1,8
1,3
6,6
5,0
3,5
2,5
1,7
1,2
5,0
4,3
3,4
2,5
1,8
1,3
2,32
2,15
1,92
1,77
1,45
1,17
4,56
3,90
3,19
2,60
2,08
1,73
5,33
4,89
4,30
3,59
2,95
2,42
399
370
330
304
249
201
784
671
549
447
358
298
917
841
740
617
507
416
17,7
15,4
12,7
10,9
7,7
5,3
27,3
20,7
14,6
10,1
6,9
4,9
20,9
18,0
14,4
10,4
7,4
5,2
1,88
1,74
1,56
1,43
1,18
0,95
3,71
3,17
2,60
2,12
1,69
1,41
4,33
3,97
3,40
2,92
2,40
1,97
323
299
268
246
203
163
638
545
447
365
291
243
745
683
585
502
413
339
12,4
10,8
8,9
7,7
5,4
3,7
19,4
14,7
10,4
7,2
4,9
3,5
14,8
12,7
10,2
7,4
5,3
3,7
Legend
WT
= Water temperature
Ph
= Emission
Qw
= Water flow
Dp(c) = Water side pressure drop
10
WT: 60/50°C
Qv
m3/h
Speed
MAX
MED
MIN
Qv
= Fan speed
= High speed
= Medium speed
= Low speed
= Air flow
CCN Version
Carisma
Coanda
Emissions
Heating emission of 1 row additional coil
Entering air temperature: +20°C
WT: 80/70°C
Model
CCN
13+1
14+1
CCN
23+1
24+1
CCN
33+1
CCN
34+1
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 75/65°
WT: 70/60°
WT: 65/55°
WT: 60/50°
WT: 55/45°
Qv
m3/h
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
680
620
540
440
360
290
1,95
1,83
1,67
1,57
1,35
1,15
3,84
3,41
2,94
2,52
2,14
1,86
4,84
4,53
4,10
3,57
3,07
2,64
4,84
4,53
4,10
3,57
3,07
2,64
168
157
144
135
116
99
330
293
253
217
184
160
416
390
353
307
264
227
416
390
353
307
264
227
5,8
5,2
4,4
3,9
3,0
2,3
4,7
3,8
2,9
2,2
1,7
1,3
8,2
7,3
6,2
4,8
3,7
2,8
8,2
7,3
6,2
4,8
3,7
2,8
1,75
1,65
1,51
1,41
1,22
1,03
3,46
3,07
2,65
2,27
1,93
1,68
4,36
4,08
3,70
3,22
2,77
2,38
4,36
4,08
3,70
3,22
2,77
2,38
151
142
130
121
105
89
298
264
228
195
166
144
375
351
318
277
238
205
375
351
318
277
238
205
4,9
4,4
3,7
3,3
2,5
1,9
3,9
3,2
2,5
1,9
1,4
1,1
7,0
6,2
5,2
4,1
3,1
2,4
7,0
6,2
5,2
4,1
3,1
2,4
1,56
1,47
1,34
1,25
1,08
0,92
3,07
2,73
2,35
2,02
1,71
1,49
3,89
3,64
3,30
2,87
2,47
2,12
3,89
3,64
3,30
2,87
2,47
2,12
134
126
115
108
93
79
264
235
202
174
147
128
335
313
284
247
212
182
335
313
284
247
212
182
4,0
3,6
3,1
2,7
2,1
1,6
3,2
2,6
2,0
1,6
1,2
0,9
5,8
5,1
4,3
3,4
2,6
2,0
5,8
5,1
4,3
3,4
2,6
2,0
1,36
1,28
1,17
1,10
0,95
0,81
2,37
2,10
1,82
1,57
1,33
1,16
3,41
3,19
2,89
2,52
2,17
1,86
3,41
3,19
2,89
2,52
2,17
1,86
117
110
101
95
82
70
204
181
157
135
114
100
293
274
249
217
187
160
293
274
249
217
187
160
3,2
2,9
2,5
2,2
1,7
1,3
1,0
0,8
0,6
0,5
0,4
0,3
4,7
4,1
3,5
2,7
2,1
1,6
4,7
4,1
3,5
2,7
2,1
1,6
1,17
1,10
1,00
0,94
0,81
0,69
2,31
2,05
1,77
1,52
1,29
1,13
2,94
2,75
2,49
2,17
1,87
1,61
2,94
2,75
2,49
2,17
1,87
1,61
101
95
86
81
70
59
199
176
152
131
111
97
253
237
214
187
161
138
253
237
214
187
161
138
2,5
2,2
1,9
1,7
1,3
1,0
2,0
1,6
1,3
1,0
0,7
0,6
3,6
3,2
2,7
2,1
1,6
1,3
3,6
3,2
2,7
2,1
1,6
1,3
0,97
0,92
0,84
0,78
0,68
0,58
1,93
1,71
1,48
1,27
1,08
0,94
2,46
2,31
2,09
1,82
1,57
1,35
2,46
2,31
2,09
1,82
1,57
1,35
83
79
72
67
58
50
166
147
127
109
93
81
212
199
180
157
135
116
212
199
180
157
135
116
1,8
1,6
1,4
1,3
1,0
0,7
1,5
1,2
0,9
0,7
0,5
0,4
2,7
2,4
2,0
1,6
1,2
0,9
2,7
2,4
2,0
1,6
1,2
0,9
Heating emission of 2 row additional coil
Entering air temperature: +20°C
WT: 65/55°C
Model
CCN
13+2
CCN
23+2
CCN
33+2
Speed
VI
V
IV
III
II
I
VI
V
IV
III
II
I
VI
V
IV
III
II
I
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
WT: 60/50°
WT: 55/45°
WT: 50/40°
WT: 45/40°
WT: 45/35°
Qv
m3/h
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
305
280
245
220
180
140
560
470
380
305
240
200
680
620
540
440
360
290
2,38
2,23
2,02
1,88
1,60
1,35
4,66
4,08
3,47
2,95
2,43
2,07
5,83
5,42
4,86
4,20
3,54
2,96
205
192
174
162
138
116
401
351
298
254
209
178
501
466
418
361
304
255
15,5
13,8
11,6
10,3
7,7
5,7
12,7
10,1
7,6
5,7
4,1
3,1
22,5
19,8
16,3
12,6
9,3
6,8
2,05
1,92
1,75
1,63
1,38
1,16
4,03
3,53
3,00
2,55
2,11
1,79
5,06
4,70
4,22
3,65
3,07
2,57
176
165
151
140
119
100
347
304
258
219
181
154
435
404
363
314
264
221
12,2
10,8
9,1
8,1
6,0
4,5
10,0
8,0
6,0
4,5
3,2
2,4
17,8
15,6
12,9
10,0
7,4
5,4
1,73
1,62
1,47
1,37
1,16
0,98
3,40
2,99
2,54
2,16
1,78
1,52
4,28
3,98
3,57
3,09
2,60
2,18
149
139
126
118
100
84
292
257
218
186
153
131
368
342
307
266
224
187
9,2
8,2
6,9
6,1
4,6
3,4
7,6
6,0
4,5
3,4
2,4
1,8
13,5
11,8
9,8
7,6
5,6
4,1
1,41
1,32
1,20
1,12
0,95
0,80
2,78
2,44
2,09
1,77
1,46
1,25
3,50
3,26
2,92
2,53
2,14
1,79
121
114
103
96
82
69
239
210
180
152
126
108
301
280
251
218
184
154
6,5
5,8
4,9
4,3
3,2
2,4
5,4
4,3
3,3
2,4
1,7
1,3
9,6
8,5
7,0
5,4
4,0
3,0
1,33
1,25
1,13
1,05
0,89
0,75
2,61
2,29
1,96
1,65
1,36
1,16
3,27
3,04
2,72
2,36
1,98
1,66
229
215
194
181
153
129
449
394
337
284
234
200
562
523
468
406
341
286
20,0
17,8
15,0
13,3
9,9
7,4
16,5
13,1
10,0
7,4
5,3
4,0
29,1
25,6
21,1
16,4
12,1
8,8
1,09
1,02
0,92
0,86
0,73
0,62
2,15
1,89
1,62
1,37
1,14
0,97
2,73
2,54
2,28
1,98
1,67
1,40
94
88
79
74
63
53
185
163
139
118
98
83
235
218
196
170
144
120
4,2
3,7
3,1
2,8
2,1
1,6
3,5
2,8
2,1
1,6
1,1
0,9
6,3
5,6
4,6
3,6
2,7
1,9
Legend
WT
= Water temperature
Ph
= Emission
Qw
= Water flow
Dp(c) = Water side pressure drop
Speed
MAX
MED
MIN
Qv
= Fan speed
= High speed
= Medium speed
= Low speed
= Air flow
11
Water side pressure drop
3 row coil
4 row coil
Dp
Dp
50
50
40
40
3
30
CCN Version
Carisma
Coanda
30
20
2
20
3
2
10
9
8
10
9
8
7
7
6
6
5
5
1
4
4
3
3
2
2
1
100
200
1
300
400
600
800 1000
1500
1
Qw
Pressure drop for mean water temperature of 10°C; for
different temperatures multiply the pressure drop figure by the
K correction factors in the table.
100
°C
K
200
20
0,94
30
0,90
1 row additional coil
40
0,86
600
50
0,82
800 1000
1500
60
0,78
Qw
70
0,74
80
0,70
Dp
60
60
50
50
40
40
30
30
20
20
10
9
8
7
6
10
9
8
7
6
3
5
5
4
4
3
2
1
3
1
2
2
2
1
50 60
80 100
200
300
400
600
800 1000
Legend
Qw = water flow (l/h)
Dp = pressure drop (kPa)
1
Qw
Pressure drop for mean water temperature of 65°C; for
different temperatures multiply the pressure drop figure by the
K correction factors in the table.
12
400
2 row additional coil
Dp
3
300
50 60
°C
K
80 100
40
1,14
200
50
1,08
300
400
60
1,02
600
800 1000
70
0,96
Qw
80
0,90
CCN Version
Carisma
Coanda
Accessories
VBP Main coil
3 way valve
VBA Additional coil
3 way valve
Control valve kit:3 way valve, ON-OFF, with electric motor
and mounting kit with micrometric lockshield valve.
Control valve kit:3 way valve, ON-OFF, with electric motor
and mounting kit with micrometric lockshield valve.
VS Simplified kit for 3 way valve
for main and additional coil
V2 2 way valve
for main and additional coil
3 way valve, (ON-OFF) with electric motor and mounting kit.
Valve with flat connection without micrometric lockshield
valve.
Control valve kit: 2 way valve, ON-OFF, with electric motor
and mounting kit.
Valve
type
mod.
Main
1-2
DN
(Ø)
Kvs
Micrometric
lockshield valve
DN
(Ø)
Kvs
15
1/2"
1,6
15
Valve
1/2"
2
Code
Fitted
Not Fitted
9066561H
9066560H
VBP
VBA
Valves pressure drop
Kvs 2
Dp
3
20
3/4"
2,5
15
1/2"
2
9060471H
9060474H
Additional
All
15
1/2"
1,6
15
1/2"
2
9060472H
9060475H
1-2
15
1/2"
1,6
-
-
-
9066571H
9066570H
3
20
3/4"
2,5
-
-
-
9060484H
9060481H
4
All
15
1/2”
1,6
-
-
-
9060483H
9060480H
2
1-2
15
1/2"
1,7
-
-
-
9060476H
9060478H
1
3
20
3/4"
2,8
-
-
-
9060477H
9060479H
All
15
1/2”
1,7
-
-
-
9060476H
9060478H
Main
Additional
Kvs 1,6
Kvs 2,5
Kvs 2,8
40
Main
VS
Kvs 1,7
30
20
10
9
8
7
6
5
3
100
200
300 400
600 800 1000
2000 3000 4000
Main
V2
Additional
Qw
Legend
Qw = water flow (l/h)
Dp = pressure drop (kPa)
13
CCN Version
Carisma
Coanda
Accessories
BEL Electric heater
1 PHASE 230V
Electric heater with integral: safety thermostat and relay control.
ID
Size
Watt
Code
BEL
1
350
9064051
2
550
9064031
700
9064052
3
1150
9064032
900
9064053
1400
9064033
BSO Extension condensate collection tray
to cover valve assembly
Connection side
ID
Code
left
BSO
BSO-SX
6060402
right
BSO-DX
6060403
SCR plastic condensate drain pipe with
fast connection
It helps regular drainage of condensate thereby preventing the
formation of bends.
ID
Code
SCR
6060420
PCC condensate drain pump
ID
Fitted
PCC-M
Not fitted
PCC-S
Code
9064011
9064010
Height for vertical
flow (m)
1
2
3
4
Water flow (l/h) depending on the length of
horizontal flow
5m
10 m
6,8
6,3
5,5
5,0
4,2
3,8
3,0
2,6
FRC fresh air connection
Code
FRC 100
ID
6064191
Code
TCX 3.9 x 9.5
6064192
TCX 3.9 x 9.5
98
14
FRC 120
122
ID
CONTROL
IDENTIFICATION
CONTROL CODES
Installation of bimetallic low temperature CUT-OUT thermostat (TMM)
Installation of electronic low temperature CUT-OUT thermostat (TME)
Room thermostat for fan and electric heater control
Room thermostat for chilled water valve (SUMMER) and electric heater (WINTER) control (in winter only
the heater is working)
Simultaneous thermostatic control of the valves and fan
Room thermostat for 2 valve control (4 pipe installation)
Room thermostat for 1 valve control (2 pipe installation)
Room thermostat for fan control (ON-OFF)
Automatic Summer/Winter switch with neutral zone for 4 pipe installation with 2 valves
Remote centralized Summer/Winter switch or by an automatic change-over fitted on the water pipe
Summer/Winter switch
Manual/Automatic 3 speed selection
Manual 3 speed switch
ON-OFF switch for electric heater
ON-OFF switch
CONTROL
OPERATIONS
Control operations
Carisma
Coanda
CCN Version
Electrical diagrams are shown on the installation, use and maintenance manual
T2T
9060174
TMO-DI
9060165
TMO-503-SV2
9060173
TMO-503-S
9060171
TMO-T-AU
9060164
TMO-T
9060161
CR-T
9066330
MO-3V
9060160
15
Carisma
Coanda
Wall electronic controls
ID
Code
MO-3V
9060160
CCN Version
• ON-OFF switch and speed switch, without thermostatic control.
• It allows to control the low temperature cut-out thermostat (TMM).
Dimensions: 133x93x37 mm
ID
Code
CR-T
9066330
•
•
•
•
•
•
Manual speed switch.
Manual Summer/Winter switch.
Electronic thermostat for fan control (ON-OFF).
Electronic thermostat for valve control (ON-OFF).
It allows to control the low temperature cut-out thermostat (TMM).
It allows to control the chilled water valve (ON-OFF) and the electric
heater (BEL) only in case that hot water is not used in winter
(otherwise please use TMO-T-IAQ control with on/off switch for the
electric heater described in the Carisma Fan Coil units technical
documentation).
Dimensions: 133x93x37 mm
ID
Code
TMO-T
9060161
•
•
•
•
•
•
Manual speed switch.
Manual Summer/Winter switch.
Electronic thermostat for fan control (ON-OFF).
Electronic thermostat for valve control (ON-OFF).
It allows to control the low temperature cut-out thermostat (TME).
It allows to control the chilled water valve (ON-OFF) and the electric
heater (BEL) only in case that hot water is not used in winter
(otherwise please use TMO-T-IAQ control with on/off switch for the
electric heater described in the Carisma Fan Coil units technical
documentation).
• It allows to install the Summer/Winter switch centralized and
remote, or to control it with an automatic change-over fitted on
the water pipe (for 2-pipe systems only). The latter case needs the
adjustment of the jumper on the control board (see the instruction
leaflet supplied with the control).
Dimensions: 133x93x37 mm
ID
Code
TMO-T-AU
9060164
Dimensions: 133x93x37 mm
•
•
•
•
•
•
•
Manual or automatic speed switch.
Manual Summer/Winter switch.
Electronic thermostat for fan control (ON-OFF).
Electronic thermostat for valve control (ON-OFF).
Simultaneus thermostatic control on the valves and fan (ON-OFF).
It allows to control the low temperature cut-out thermostat (TME).
It allows to control the chilled water valve (ON-OFF) and the electric
heater (BEL) only in case that hot water is not used in winter
(otherwise please use TMO-T-AU-IAQ control with on/off switch for
the electric heater described in the Carisma Fan Coil units technical
documentation).
• It allows to install the Summer/Winter switch centralized and
remote, or to control it with an automatic change-over fitted on
the water pipe (for 2-pipe systems only). The latter case needs the
adjustment of the jumper on the control board (see the instruction
leaflet supplied with the control).
Note: with 4-pipe systems and continuous chilled and hot water supply,
it allows the automatic summer/winter change-over in accordance
to the room temperature (-1°C = Winter, +1°C = Summer, Dead
Zone 2°C).
16
Carisma
Coanda
Wall electronic controls
ID
Code
TMO-503-S
9060171
CCN Version
The TMO-503-S control for fan coils without valves, is designed to be
installed in a DIN 503 wall box. The control is supplied integral with
the external frame, but it is possible to use frames of the most known
brand on the market (BTicino, Vimar, AVE, Gewiss).
The highest working electric absorbtion is 200 W; if the fan coil has
an higher absorbtion or more units are connected to the same control,
the speed switch SEL-S must be installed.
• Manual or automatic speed switch.
• Manual Summer/Winter switch.
• Electronic thermostat for fan control (ON-OFF).
•It allows to control the low temperature cut-out thermostat
(included with the control).
Dimensions: 118x87x8 mm
ID
Code
TMO-503-SV2
9060173
The TMO-503-SV2 control for fan coils with valves, is designed to be
installed in a DIN 503 wall box. The control is supplied integral with
the external frame, but it is possible to use frames of the most known
brand on the market (BTicino, Vimar, AVE, Gewiss).
The highest working electric absorbtion is 200 W; if the fan coil has an
higher absorbtion or more units are connected to the same control, the
speed switch SEL-S must be installed.
•
•
•
•
•
Dimensions: 118x87x8 mm
ID
Code
TMO-DI
9060165
Dimensions on the wall: 133x93x27 mm
Dimensions in the DIN 503 box: 133x93x18 mm
ID
Code
T2T
9060174
Manual or automatic speed switch.
Manual Summer/Winter switch.
Electronic thermostat for valve(s) control (ON-OFF).
Simultaneus thermostatic control on the valves and fan (ON-OFF)..
It allows to control the low temperature cut-out thermostat (included
with the control).
Note: with 4-pipe systems and continuous chilled and hot water supply,
it allows the automatic summer/winter change-over in accordance
to the room temperature (-1°C = Winter, +1°C = Summer, Dead
Zone 2°C).
To be installed on the wall or in the DIN 503 box.
• Manual or automatic speed switch.
• Manual or automatic Summer/Winter switch.
• Electronic thermostat for fan control (ON-OFF).
• Electronic thermostat for valve control (ON-OFF).
• Simultaneus thermostatic control on the valves and fan (ON-OFF).
• It allows to control the low temperature cut-out thermostat (TME).
• It allows to control the chilled water valve (ON-OFF) and the electric
heater (BEL) only in case that hot water is not used in winter.
• It allows to control the fan and the heating electric resistance.
• It allows to control up to 10 units with SEL-DI speed switch.
Note: with 4-pipe systems and continuous chilled and hot water supply,
it allows the automatic summer/winter change-over in accordance
to the room temperature (-1°C = Winter, +1°C = Summer, Dead
Zone 2°C).
2-pipes units only
•
•
•
•
•
•
•
ON-OFF switch.
3 speed switch.
Manual Summer/Winter switch.
Electronic thermostat for fan control.
Thermostatic control on the valve and continuous fan operation.
Simultaneus thermostatic control on the valves and fan.
Cannot be used with speed switch (master-slave).
Dimensions: 128x75x25 mm
17
Speed switches
ID
Code
SEL-S
9079110
• Speed switch (slave).
• It allows to control up to 8 units with only one centralized thermostat
using one speed switch for each unit.
• For controls:
CR-T, MO-T, TMO-T-AU, TMO-503-S and TMO-503-SV2.
ID
Code
SEL-DI
9060139
• Repeater for TMO-DI
• It allows to control up to 10 units with only one TMO-DI centralized
thermostat.
18
Carisma
Coanda
CCN Version
Electronic control accessories
Carisma
Coanda
CCN Version
TME low temperature cut-out thermostat
ID
Code
TME
3021091
To be fitted between the coil fins.
When connecting the control, the TME probe cable must be separated from the power supply wires.
To be used with the following controls: TMO-T, TMO-T-AU, TMO-DI.
It stops the fan when the water temperature is lower than 38°C and it starts the fan when is higher than 42°C.
TMM low temperature cut-out thermostat
ID
Code
TMM
9053048
To be installed in contact with the hot water circuit.
To be used with the following controls only: MO-3V, CR-T.
For units working on heating only.
It stops the fan when the water temperature is lower than 30°C
and it starts the fan when is higher than 38°C.
A
Legend
B A = red
B = brown
Change-Over CH 15-25
ID
Code
CH 15 -25
9053049
Automatic summer/winter switch to be installed in contact
with the water circuit.
For 2-tube installations only (not to be used with 2 way valve).
To be used with the following controls only:
TMO-T, TMO-T-AU, TMO-DI.
A
Legend
B A = red
B = black
19
CCN Version
Carisma
Coanda
FreeSabiana Wireless control system
Free Sabiana
Free Sabiana is an innovative, fully wireless electronic system
for use with fan coil units, based on radio communication.
This technology provides installation flexibility and a more
accurate measurement of the room temperature.
The probe can be moved until the most suitable position is found, without the worry of changes in the environment layout and
of its furniture and also without mounting it on a wall. If a new fan coil unit is added, no electrical wiring for the control system
is required: just define the control unit and the probe which regulates it. The improved measurement accuracy derives from
the possibility to position the probe near the typical location of the user: this enables to keep the temperature exactly at the
required value with more energy savings compared with a traditional measurement system.
Transmission is based on communication protocol IEE802.15.4, the most suitable way to transmit a relatively low amount of
information with very low consumption and high reliability.
The system has been certified by a leading independent body, officially recognized by the EU authorities and its sale has
been authorized in all the EU and EFTA countries.
Main components
Free Sabiana includes 3 main components:
• A remote control which features a button panel and
LCD display and can be wall mounted or positioned on a
dedicated table support.
It enables the control of all the operating variables of the fan
coil units in different configurations. The control is battery
powered.
The temperature and the operating speed of the fan coil
unit are set with two large buttons featuring user friendly
graphics.
Description
Remote control
ID
Code
Free-Com
9060572
Control unit with support
• A power unit to be installed on the fan coil (fan coil
interface).
It controls the fan and the valves of the fan coil. The power
unit is connected to the electric supply.
The power unit receives the information required to control
the fan coil both from the remote control and locally, such
as the temperature of the coil.
Description
Power unit fitted on the unit
Power unit not fitted on the unit
ID
Code
Free-Upm
Free-Ups
9060571
9060570
Power unit
• A room temperature probe, which can be wall mounted
or positioned on a dedicated table support.
It is a battery powered device, able to measure the air
temperature in the spot where it is positioned, generating
temperature information which is communicated to the
other devices.
Description
Temperature probe
ID
Code
Free-Sen
9060573
Probe with support
20
FreeSabiana Wireless control system
Carisma
Coanda
CCN Version
Main features of the remote control
The control enables:
• Fan coil on/off switching
•Fan speed selection (high - medium - low - automatic)
•Summer/winter operation selection
•Valve on/off
•Real time clock setting
•Temperature setting
•Daily switch on/off setting (timer function)
•Enable/disable the timer function
•Activation of the (eventual) electrostatic filter
•Activation of the (eventual) electric resistance
Main information displayed:
1 = On-off status
2 = Summer operation
3 = Winter operation
4 = Automatic season change
5 = Electric resistance
6 = Crystall filter
7 = Room temperature (with decimal accuracy)
8 = Fan operating speed
9 = Required/measured temperature
10= Timer
11= Clock
12= Transmission signal
13= Battery level
Main features of the power unit to be installed on the fan coil
The power unit controls the fan and the valves of the fan coil.
The power unit receives the information required to control such
units both from the remote control and locally.
It enables the following main actions:
•Fan on/off at a set speed
•Fan speed change (fan on/off)
•Water valve/s on/off (1 valve for 2 tube system - 2 valves for 4 tube system)
•Fan speed change operating the water valve/s
•Control of the electric resistance as main heating unit or as integration to the battery supplied with hot water
•Control of the operation of the electrostatic filter (in parallel to the fan)
•Management of the dead zone function for 4-tube systems
•Available functional inputs:
- Consent for remote on/off
- Consent for remote Summer/Winter switch (centralized)
- Consent for the activation of the Energy Saving function with setting change
- Minimum probe
- Probe for season change
Main features of the temperature probe
This device is able to measure the temperature of the air in
the spot where it is positioned and to transmit it by means of
radio communication to the other devices in the system. It is
battery powered and can be freely positioned in the area to be
air-conditioned.
Display:
•Measured environment temperature
•Transmission signal
•Clock
•Battery status
21
CCN Version
Carisma
Coanda
Controls and units MB version
All the Carisma Coanda units can be supplied with a wide range of controls, which allows managing one single unit or several
units by using the Modbus RTU - RS 485 communication protocol.
Units can be managed according to the Master/Slave logic (up to 20 units) or by supervisory components.
The system consists in a MB board and a series of controls, such as the T-MB wall control, the RT03 infra-red remote control,
the PSM-DI multifunction control and the Sabianet supervisory program.
T-MB Wall
control
PSM-DI Multifunction
control
PC
Sabianet Screenshot
RT03 Infra-red
remote control
Sabianet Software
All the controls for the ECM version and their functions are described in detail from Page 39.
22
Coanda
ECM
Coanda ECM
Carisma
Coanda
CCN-ECM Version
ECM Version
One Way Cassette Fan Coil with EC Brushless Electronic Motor and
Inverter Board
Constructional features of the main components
Casing
Made from 1 mm galvanized steel insulated with polyolefin (PO) foam (class M1).
Diffuser with intake grille
In prepainted metal sheet in RAL 9003 colour with intake grille that can be opened for inspection and maintenance of the air filter.
Air Filter
Polypropylene cellular fabric regenerating filter.
Fan Assembly
The fans have aluminium or plastic blades directly keyed on the motor with double aspiration and they are dynamically and
statically balanced during manufacture in order to have an extremely quiet operation.
Electronic motor
Three phase permanent magnet brushless electronic motor that is controlled with current reconstructed according to a BLAC
sinusoidal wave. The inverter board that controls the motor operation is powered by 230 Volt, single-phase and, with a switching
system, it generates a three-phase frequency modulated, wave form power supply. The electric power supply required for the
machine is therefore single-phase with voltage of 230-240V and frequency of 50-60Hz.
Heat exchange coil
It is manufactured from drawn copper tube and the aluminium fins are mechanically bonded onto the tube by an expansion
process. The coil has two 1/2 inch BSP internal connections and 1/8 inch BSP air vent and drain.
The heat exchanger is not suitable for use in corrosive atmosphere or in environments where aluminium may be subject to
corrosion.
The connection side cannot be changed on site.
Condensate Collection Tray
Made from plastic (ABS UL94 HB), with an “L”-shape fitted on the inner casing; the try is insulated with polyolefin (PO) foam
(class M1). The outside diameter of the condensate discharge pipe is 15mm.
Round diffuser
The Carisma Coanda one-way cassette units are supplied
with round diffusers suitably designed to generate an airflow
with “coanda” effect. The direction of diffuser air flow can be
adjusted on site.
23
Dimensions, Weight,
Water content
Carisma Coanda Gr 1 - 3 diffusers
Carisma
Coanda
CCN-ECM Version
Carisma Coanda Gr 2 - 5 diffusers
A
592
592
A
Carisma Coanda Gr 3 - 6 diffusers
592
A
Water
inlet
Water
outlet
Coil connections
on the left
24
Dimensions, weight
Water content
Carisma
Coanda
CCN-ECM Version
W
730
370
DIMENSIONS (mm)
Model
A
E
F
W
1
2
3
592
454
78
750
970
884
43
1130
1192
1099
46,5
1350
weight (kg)
Model
Rows
3
3+1
3+2
4
4+1
1
Weight packed unit
2
3
Weight unpacked unit
1
2
3
18
20
23
20
23
34
40
46
37
42
44
51
58
48
54
16
19
22
18
21
33
38
43
35
40
42
48
54
45
51
Water content (l)
Rows
Model
3
4
+1
+2
1
2
3
0,6
0,8
0,2
0,4
1,3
1,7
0,4
0,8
1,7
2,4
0,5
1,0
25
Carisma
Coanda
EUROVENT certifications
CCN-ECM Version
www.eurovent-certification.com
www.certiflash.com
Technical features
2-pipe units
The following standard rating conditions are used:
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
Model
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 50°C E.W.T.
Water flow rate as for the cooling conditions
CCN-ECM 13
dB(A)
1 (E)
MIN
130
0,82
0,62
1,02
2,1
1,7
8
35
26
Air flow
m3/h
Cooling total emission (E)
kW
Cooling sensible emission (E) kW
Heating (E)
kW
∆P Cooling (E)
kPa
∆P Heating (E)
kPa
Fan (E)
W
Sound power (E)
Lw dB(A)
Sound pressure (*)
Lp dB(A)
1 (E)
MIN
130
0,91
0,66
1,07
4,1
3,3
8
35
26
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
∆P Cooling (E)
∆P Heating (E)
Fan (E)
m3/h
kW
kW
kW
kPa
kPa
W
Sound power (E)
Lw dB(A)
Sound pressure (*)
Lp
Model
3
165
1,00
0,76
1,25
3,0
2,4
11
41
32
5 (E)
MED
205
1,18
0,91
1,50
4,0
3,3
14
46
37
7,5
250
1,37
1,07
1,75
5,2
4,3
21
51
42
CCN-ECM 23
10 (E)
MAX
295
1,56
1,24
2,02
6,5
5,3
29
55
46
1 (E)
MIN
215
1,46
1,07
1,72
3,2
2,6
8
34
25
10 (E)
MAX
295
1,81
1,38
2,20
13,9
11,6
29
55
46
1 (E)
MIN
215
1,55
1,11
1,82
5,0
4,1
8
34
25
CCN-ECM 14
Speed
3
165
1,12
0,82
1,32
5,9
4,8
11
41
32
5 (E)
MED
205
1,34
0,99
1,60
8,1
6,6
14
46
37
7,5
250
1,58
1,18
1,90
10,9
9,0
21
51
42
3
295
1,92
1,42
2,28
5,2
4,2
11
40
31
5 (E)
MED
370
2,31
1,73
2,79
7,3
6,0
16
46
37
7,5
450
2,74
2,07
3,33
9,8
8,0
24
52
43
CCN-ECM 33
10 (E)
MAX
540
3,16
2,41
3,85
12,6
10,4
37
56
47
1 (E)
MIN
275
1,87
1,37
2,19
5,8
4,7
10
36
27
10 (E)
MAX
540
3,50
2,60
4,32
20,8
17,1
37
56
47
1 (E)
MIN
275
1,95
1,41
2,25
4,3
3,5
10
36
27
CCN-ECM 24
3
295
2,06
1,49
2,46
8,2
6,7
11
40
31
5 (E)
MED
370
2,51
1,84
3,03
11,6
9,4
16
46
37
7,5
450
3,00
2,21
3,68
15,9
13,2
24
52
43
3
345
2,31
1,70
2,72
8,4
6,9
13
42
33
5 (E)
MED
430
2,78
2,06
3,30
11,7
9,4
19
48
39
7,5
525
3,28
2,45
3,93
15,7
12,9
29
54
45
10 (E)
MAX
620
3,75
2,83
4,54
19,8
16,6
42
58
49
CCN-ECM 34
3
345
2,42
1,76
2,82
6,4
5,2
13
42
33
5 (E)
MED
430
2,94
2,15
3,44
8,9
7,4
19
48
39
7,5
525
3,49
2,57
4,12
12,1
10,0
29
54
45
10 (E)
MAX
620
4,02
2,98
4,78
15,5
13,0
42
58
49
4-pipe units
The following standard rating conditions are used:
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
Model
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 70°C E.W.T. / + 60°C L.W.T.
CCN-ECM 13 + 1
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
∆P Cooling (E)
∆P Heating (E)
Fan (E)
m3/h
kW
kW
kW
kPa
kPa
W
Sound power (E)
Lw dB(A)
Sound pressure (*)
Lp
dB(A)
1 (E)
MIN
130
0,82
0,62
0,87
2,1
1,4
8
35
26
3
165
1,00
0,76
1,03
3,0
1,9
11
41
32
5 (E)
MED
205
1,18
0,91
1,18
4,0
2,5
14
46
37
7,5
250
1,37
1,07
1,35
5,2
3,1
21
51
42
CCN 23-ECM + 1
10 (E)
MAX
295
1,56
1,24
1,52
6,5
3,8
29
55
46
1 (E)
MIN
215
1,46
1,07
1,58
3,2
1,0
8
34
25
3
295
1,92
1,42
1,97
5,2
1,5
11
40
31
5 (E)
MED
370
2,31
1,73
2,31
7,3
2,0
16
46
37
7,5
450
2,74
2,07
2,66
9,8
2,5
24
52
43
CCN 33-ECM + 1
10 (E)
MAX
540
3,16
2,41
3,01
12,6
3,1
37
56
47
1 (E)
MIN
275
1,87
1,37
2,04
5,8
1,8
10
36
27
3
345
2,31
1,70
2,42
8,4
2,5
13
42
33
5 (E)
MED
430
2,78
2,06
2,82
11,7
3,3
19
48
39
7,5
525
3,28
2,45
3,24
15,7
4,2
29
54
45
10 (E)
MAX
620
3,75
2,83
3,64
19,8
5,1
42
58
49
(E) = Eurovent certified performance.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room
and a reverberation time of 0.5 sec.
26
CCN-ECM Version
Carisma
Coanda
Working conditions and Air throw
Working conditions
Max. entering water temperature..................... + 80 °C
MIn. entering water temperature........................ + 5 °C
for entering water temperatures below + 5°C, contact “SABIANA” technical department
Max. rated pressure............................................1000 kPa (10 bars)
Installation height (m)
Model
1
2
3
Minimum
Maximum
2,6
3,2
2,6
3,2
2,6
3,5
Water flow limits for main coil (l/h)
3 rows
4 rows
Model
13
23
33
14
24
34
Minimum
Maximum
100
500
150
1000
150
1500
100
750
150
1000
200
2000
Water flow limits for additional coil (l/h)
1 row
2 rows
Model
1
2
3
1
2
3
Minimum
Maximum
50
250
100
450
100
650
50
250
100
450
100
650
1
2
3
29
37
42
Motor electrical data (max. absorption)
Model
230/1 50Hz
W
Air throw
C1 - Heating
L
C2 - Cooling
L
Carisma Coanda
CCN-ECM 1
Model
Air throw
L (m)
1
C1
C2
2
3
4
5
Carisma Coanda
CCN-ECM 2
6
1
3,8 4,5 5,8 6,3 6,8 7,2 4
3 3,6 4,6 5 5,4 5,7 3,2
2
5
4
3
4
5
Carisma Coanda
CCN-ECM 3
6
1
2
3
4
5
6
6,1 7
8
9 4,5 5,2 6,3 7,5 8,8 9,5
4,8 5,6 6,4 7,2 3,6 4,1 5
6
7 7,6
27
CCN-ECM Version
Carisma
Coanda
Emissions
Cooling emission of 3 row coil
Entering air temperature: +27°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN-ECM
13
CCN-ECM
23
CCN-ECM
33
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Vdc
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
1,69
1,48
1,27
1,08
0,89
3,40
2,94
2,49
2,06
1,57
4,03
3,53
2,99
2,48
2,01
1,23
1,07
0,91
0,76
0,62
2,41
2,06
1,73
1,42
1,07
2,82
2,45
2,06
1,70
1,37
291
255
218
186
153
585
506
428
354
270
693
607
514
427
346
7,5
6,0
4,6
3,4
2,4
14,3
11,1
8,3
5,9
3,7
22,5
17,8
13,3
9,6
6,6
1,50
1,32
1,14
0,97
0,80
3,05
2,64
2,23
1,85
1,42
3,63
3,17
2,69
2,24
1,82
1,16
1,01
0,85
0,71
0,58
2,26
1,94
1,62
1,33
1,01
2,65
2,30
1,93
1,59
1,28
258
227
196
167
138
525
454
384
318
244
624
545
463
385
313
6,1
4,8
3,7
2,8
2,0
11,7
9,1
6,8
4,9
3,0
18,6
14,7
11,0
7,9
5,5
1,11
0,98
0,85
0,72
0,60
2,31
2,01
1,70
1,42
1,09
2,77
2,43
2,06
1,72
1,40
1,01
0,88
0,74
0,62
0,51
1,97
1,69
1,41
1,16
0,87
2,31
2,01
1,68
1,39
1,12
191
169
146
124
103
397
346
292
244
187
476
418
354
296
241
3,5
2,8
2,2
1,7
1,2
7,1
5,5
4,2
3,0
1,9
11,4
9,0
6,8
4,9
3,4
0,89
0,77
0,65
0,55
0,45
1,74
1,49
1,25
1,03
0,77
2,04
1,77
1,49
1,23
0,98
0,89
0,77
0,65
0,55
0,45
1,74
1,49
1,25
1,03
0,77
2,04
1,77
1,49
1,23
0,98
153
132
112
95
77
299
256
215
177
132
351
304
256
212
169
2,3
1,8
1,4
1,0
0,7
4,3
3,2
2,4
1,7
1,0
6,6
5,1
3,8
2,7
1,8
Entering air temperature: +26°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN-ECM
13
CCN-ECM
23
CCN-ECM
33
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Vdc
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
1,49
1,31
1,13
0,96
0,79
3,03
2,63
2,22
1,84
1,41
3,60
3,15
2,67
2,22
1,80
1,16
1,01
0,85
0,72
0,58
2,27
1,95
1,63
1,34
1,01
2,66
2,31
1,94
1,60
1,29
256
225
194
165
136
521
452
382
316
243
619
542
459
382
310
6,0
4,8
3,7
2,8
2,0
11,7
9,1
6,8
4,9
3,0
18,5
14,6
10,9
7,9
5,5
1,31
1,15
0,99
0,85
0,70
2,68
2,32
1,97
1,63
1,25
3,20
2,80
2,38
1,98
1,61
1,09
0,94
0,80
0,67
0,55
2,12
1,82
1,52
1,25
0,94
2,49
2,16
1,81
1,50
1,20
225
198
170
146
120
461
399
339
280
215
550
482
409
341
277
4,8
3,8
2,9
2,2
1,6
9,3
7,3
5,4
3,9
2,4
14,9
11,8
8,8
6,4
4,4
0,97
0,84
0,70
0,60
0,50
1,92
1,68
1,43
1,19
0,92
2,32
2,04
1,74
1,45
1,19
0,97
0,84
0,69
0,57
0,47
1,83
1,57
1,31
1,07
0,81
2,15
1,86
1,56
1,29
1,03
167
144
120
103
86
330
289
246
205
158
399
351
299
249
205
2,8
2,1
1,6
1,2
0,9
5,1
4,1
3,1
2,2
1,4
8,4
6,7
5,0
3,7
2,6
0,81
0,70
0,60
0,50
0,41
1,59
1,36
1,15
0,94
0,71
1,87
1,62
1,37
1,12
0,90
0,81
0,70
0,60
0,50
0,41
1,59
1,36
1,15
0,94
0,71
1,87
1,62
1,37
1,12
0,90
139
120
103
86
71
273
234
198
162
122
322
279
236
193
155
2,0
1,5
1,2
0,9
0,6
3,6
2,8
2,0
1,4
0,9
5,6
4,4
3,2
2,3
1,6
Entering air temperature: +25°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN-ECM
13
CCN-ECM
23
CCN-ECM
33
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Vdc
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
1,31
1,15
0,99
0,84
0,70
2,67
2,32
1,96
1,63
1,24
3,19
2,79
2,37
1,97
1,60
1,09
0,94
0,80
0,67
0,55
2,13
1,82
1,53
1,25
0,95
2,50
2,16
1,82
1,50
1,21
225
198
170
144
120
459
399
337
280
213
549
480
408
339
275
4,8
3,8
2,9
2,2
1,6
9,4
7,3
5,4
3,9
2,4
14,9
11,8
8,8
6,4
4,4
1,12
0,99
0,85
0,73
0,60
2,32
2,01
1,71
1,42
1,09
2,78
2,43
2,07
1,72
1,40
1,01
0,88
0,74
0,62
0,51
1,98
1,70
1,42
1,17
0,88
2,33
2,02
1,69
1,39
1,12
193
170
146
126
103
399
346
294
244
187
478
418
356
296
241
3,6
2,9
2,2
1,7
1,2
7,2
5,7
4,2
3,1
1,9
11,6
9,2
6,9
5,0
3,5
0,89
0,77
0,65
0,55
0,45
1,74
1,49
1,26
1,03
0,77
2,05
1,77
1,50
1,23
0,96
0,89
0,77
0,65
0,55
0,45
1,74
1,49
1,26
1,03
0,77
2,05
1,77
1,50
1,23
0,95
153
132
112
95
77
299
256
217
177
132
353
304
258
212
165
2,4
1,9
1,4
1,0
0,7
4,3
3,3
2,4
1,7
1,0
6,7
5,2
3,9
2,7
1,8
0,73
0,63
0,54
0,46
0,37
1,44
1,24
1,04
0,85
0,64
1,70
1,47
1,24
1,02
0,82
0,73
0,63
0,54
0,46
0,37
1,44
1,24
1,04
0,85
0,64
1,70
1,47
1,24
1,02
0,82
126
108
93
79
64
248
213
179
146
110
292
253
213
175
141
1,7
1,3
1,0
0,7
0,5
3,1
2,3
1,7
1,2
0,7
4,7
3,7
2,7
1,9
1,3
Correction factors for different R.H.
U.R.
48%
46%
28
WT:
Pc
Ps
Pc
Ps
7/12°C
0,95
1,00
0,90
1,00
8/13°C
0,94
1,00
0,88
1,00
10/15°C
1,00
1,00
1,00
1,00
12/17°C
1,00
1,00
1,00
1,00
Legend
WT
= Water temperature
Vdc = Inverter power
Qv
= Air flow
Dp(c) = Water side
pressure drop
Pc
Qw
Ps
= Cooling Total emission
= Water flow
= Cooling Sensible
emission
CCN-ECM Version
Carisma
Coanda
Emissions
Cooling emission of 4 row coil
Entering air temperature: +27°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN-ECM
14
CCN-ECM
24
CCN-ECM
34
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Vdc
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
1,95
1,70
1,44
1,20
0,98
3,76
3,22
2,69
2,21
1,66
4,32
3,75
3,15
2,60
2,09
1,37
1,18
0,99
0,82
0,66
2,60
2,21
1,83
1,49
1,12
2,98
2,57
2,15
1,76
1,41
335
292
248
206
169
647
554
463
380
286
743
645
542
447
359
15,9
12,4
9,2
6,8
4,7
23,6
18,0
13,2
9,3
5,6
17,6
13,7
10,1
7,2
4,9
1,75
1,52
1,29
1,08
0,88
3,38
2,90
2,43
1,99
1,50
3,89
3,38
2,85
2,35
1,89
1,29
1,11
0,93
0,77
0,62
2,44
2,08
1,72
1,40
1,05
2,80
2,41
2,02
1,65
1,32
301
261
222
186
151
581
499
418
342
258
669
581
490
404
325
13,0
10,2
7,6
5,6
3,9
19,5
14,9
10,9
7,7
4,7
14,6
11,4
8,4
6,0
4,1
1,33
1,16
0,98
0,83
0,68
2,59
2,23
1,87
1,54
1,16
2,98
2,60
2,19
1,81
1,46
1,12
0,97
0,81
0,67
0,54
2,12
1,81
1,50
1,22
0,91
2,44
2,10
1,75
1,44
1,15
229
200
169
143
117
445
384
322
265
200
513
447
377
311
251
7,8
6,2
4,6
3,4
2,4
12,1
9,3
6,8
4,8
2,9
9,0
7,1
5,2
3,7
2,6
0,99
0,85
0,72
0,60
0,48
1,88
1,60
1,33
1,08
0,77
2,15
1,86
1,55
1,27
0,97
0,99
0,85
0,72
0,60
0,48
1,88
1,60
1,33
1,08
0,76
2,15
1,86
1,55
1,27
0,96
170
146
124
103
83
323
275
229
186
132
370
320
267
218
167
4,7
3,6
2,6
1,9
1,3
6,7
5,1
3,7
2,5
1,4
5,0
3,9
2,8
2,0
1,2
Entering air temperature: +26°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN-ECM
14
CCN-ECM
24
CCN-ECM
34
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Vdc
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
1,74
1,51
1,28
1,08
0,87
3,36
2,88
2,41
1,98
1,49
3,87
3,36
2,82
2,33
1,87
1,29
1,11
0,93
0,78
0,63
2,45
2,08
1,73
1,41
1,05
2,81
2,42
2,02
1,66
1,33
299
260
220
186
150
578
495
415
341
256
666
578
485
401
322
13,0
10,1
7,6
5,5
3,8
19,4
14,9
10,8
7,6
4,6
14,5
11,3
8,3
5,9
4,1
1,54
1,34
1,14
0,95
0,78
2,99
2,57
2,15
1,76
1,33
3,43
2,99
2,52
2,08
1,67
1,21
1,04
0,87
0,73
0,58
2,29
1,95
1,62
1,32
0,98
2,63
2,26
1,89
1,55
1,24
265
230
196
163
134
514
442
370
303
229
590
514
433
358
287
10,3
8,1
6,1
4,5
3,1
15,7
12,0
8,8
6,2
3,8
11,7
9,1
6,8
4,8
3,3
1,11
0,97
0,83
0,70
0,57
2,19
1,89
1,58
1,31
0,99
2,52
2,19
1,85
1,54
1,24
1,04
0,89
0,75
0,62
0,50
1,97
1,68
1,39
1,13
0,84
2,26
1,95
1,62
1,33
1,06
191
167
143
120
98
377
325
272
225
170
433
377
318
265
213
5,7
4,5
3,4
2,5
1,8
8,9
6,9
5,1
3,6
2,2
6,7
5,2
3,9
2,8
1,9
0,91
0,78
0,66
0,55
0,44
1,72
1,46
1,22
0,99
0,74
1,97
1,71
1,42
1,16
0,93
0,91
0,78
0,66
0,55
0,44
1,72
1,46
1,22
0,99
0,74
1,97
1,71
1,42
1,16
0,93
157
134
114
95
76
296
251
210
170
127
339
294
244
200
160
4,0
3,1
2,2
1,6
1,1
5,8
4,3
3,1
2,2
1,3
4,3
3,3
2,4
1,7
1,1
Entering air temperature: +25°C - Relative Humidity: 50%
WT: 7/12 °C
Model
CCN-ECM
14
CCN-ECM
24
CCN-ECM
34
WT: 8/13 °C
WT: 10/15 °C
WT: 12/17 °C
Vdc
Qv
m3/h
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
Pc
kW
Ps
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
1,54
1,34
1,13
0,95
0,77
2,98
2,56
2,14
1,76
1,32
3,42
2,97
2,50
2,07
1,66
1,21
1,04
0,88
0,73
0,59
2,30
1,95
1,62
1,32
0,99
2,63
2,27
1,90
1,55
1,24
265
230
194
163
132
513
440
368
303
227
588
511
430
356
286
10,4
8,1
6,1
4,5
3,1
15,7
12,0
8,8
6,2
3,8
11,7
9,1
6,8
4,8
3,3
1,33
1,16
0,99
0,83
0,68
2,60
2,23
1,87
1,54
1,16
2,99
2,60
2,19
1,81
1,46
1,13
0,97
0,81
0,68
0,54
2,14
1,82
1,51
1,23
0,92
2,45
2,11
1,77
1,45
1,16
229
200
170
143
117
447
384
322
265
200
514
447
377
311
251
8,0
6,3
4,7
3,5
2,4
12,3
9,4
6,9
4,9
3,0
9,2
7,2
5,3
3,8
2,6
1,00
0,86
0,72
0,60
0,46
1,88
1,60
1,28
1,06
0,81
2,16
1,87
1,50
1,25
1,02
1,00
0,86
0,72
0,60
0,46
1,88
1,60
1,27
1,04
0,77
2,16
1,87
1,49
1,22
0,98
172
148
124
103
79
323
275
220
182
139
372
322
258
215
175
4,7
3,6
2,7
1,9
1,2
6,9
5,2
3,5
2,5
1,6
5,1
4,0
2,7
1,9
1,4
0,82
0,71
0,60
0,50
0,40
1,56
1,33
1,11
0,90
0,67
1,79
1,55
1,29
1,06
0,84
0,82
0,71
0,60
0,50
0,40
1,56
1,33
1,11
0,90
0,67
1,79
1,55
1,29
1,06
0,84
141
122
103
86
69
268
229
191
155
115
308
267
222
182
144
3,4
2,6
1,9
1,4
0,9
4,9
3,7
2,7
1,8
1,1
3,6
2,8
2,0
1,4
1,0
Correction factors for different R.H.
U.R.
48%
46%
WT:
Pc
Ps
Pc
Ps
7/12°C
0,95
1,00
0,90
1,00
8/13°C
0,94
1,00
0,88
1,00
10/15°C
1,00
1,00
1,00
1,00
12/17°C
1,00
1,00
1,00
1,00
Legend
WT
= Water temperature
Vdc = Inverter power
Qv
= Air flow
Dp(c) = Water side
pressure drop
Pc
Qw
Ps
= Cooling Total emission
= Water flow
= Cooling Sensible
emission
29
Carisma
Coanda
Emissions
CCN-ECM Version
Heating emission of 3 row coil
Entering air temperature: +20°C
WT: 70/60°C
Model
CCN-ECM
13
CCN-ECM
23
CCN-ECM
33
WT: 60/50°C
WT: 50/40°
WT: 50/45°
WT: 45/40°
Vdc
Qv
m3/h
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
3,44
2,98
2,54
2,12
1,72
6,49
5,60
4,67
3,82
2,88
7,61
6,59
5,53
4,54
3,65
296
256
218
182
148
558
482
402
329
248
654
567
476
390
314
6,0
4,7
3,5
2,6
1,8
10,2
7,9
5,8
4,0
2,4
15,8
12,3
9,0
6,4
4,3
2,63
2,28
1,94
1,62
1,32
4,98
4,30
3,59
2,94
2,22
5,85
5,07
4,25
3,50
2,82
226
196
167
139
114
428
370
309
253
191
503
436
366
301
243
3,9
3,0
2,3
1,7
1,1
6,6
5,1
3,7
2,6
1,6
10,3
8,0
5,9
4,2
2,8
1,82
1,58
1,35
1,13
0,92
3,47
3,00
2,51
2,06
1,55
4,09
3,55
2,98
2,45
1,98
313
272
232
194
158
597
516
432
354
267
703
611
513
421
341
2,1
1,6
1,2
0,9
0,6
3,6
2,8
2,1
1,4
0,9
5,6
4,4
3,2
2,3
1,6
2,10
1,82
1,55
1,30
1,05
3,96
3,42
2,85
2,34
1,76
4,65
4,03
3,38
2,78
2,23
361
313
267
224
181
681
588
490
402
303
800
693
581
478
384
9,1
7,0
5,3
3,9
2,7
15,4
11,9
8,6
6,1
3,7
23,8
18,5
13,5
9,6
6,5
1,70
1,47
1,26
1,05
0,85
3,21
2,78
2,32
1,90
1,43
3,77
3,27
2,74
2,26
1,82
292
253
217
181
146
552
478
399
327
246
648
562
471
389
313
6,4
4,9
3,7
2,7
1,9
10,9
8,4
6,1
4,3
2,6
16,8
13,0
9,6
6,8
4,6
Heating emission of 4 row coil
Entering air temperature: +20°C
WT: 70/60°C
Model
CCN-ECM
14
CCN-ECM
24
CCN-ECM
34
WT: 50/40°
WT: 50/45°
WT: 45/40°
Vdc
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
3,69
3,19
2,68
2,22
1,78
7,27
6,17
5,08
4,11
3,04
8,00
6,89
5,74
4,70
3,75
317
274
230
191
153
625
531
437
353
261
688
593
494
404
323
11,1
8,6
6,3
4,5
3,1
17,3
13,0
9,2
6,3
3,7
12,0
9,2
6,7
4,7
3,2
2,83
2,45
2,06
1,71
1,37
5,60
4,76
3,93
3,17
2,35
6,16
5,30
4,43
3,62
2,90
243
211
177
147
118
482
409
338
273
202
530
456
381
311
249
7,2
5,6
4,1
3,0
2,0
11,3
8,5
6,0
4,2
2,5
7,8
6,0
4,4
3,1
2,1
1,97
1,71
1,44
1,19
0,96
3,93
3,35
2,76
2,24
1,66
4,31
3,72
3,11
2,55
2,04
339
294
248
205
165
676
576
475
385
286
741
640
535
439
351
3,9
3,1
2,3
1,6
1,1
6,3
4,7
3,4
2,3
1,4
4,3
3,3
2,4
1,7
1,2
2,25
1,95
1,64
1,36
1,09
4,44
3,77
3,11
2,51
1,86
4,89
4,21
3,51
2,87
2,30
387
335
282
234
187
764
648
535
432
320
841
724
604
494
396
16,7
13,0
9,5
6,8
4,7
26,1
19,6
13,9
9,6
5,6
18,0
13,8
10,0
7,1
4,8
1,83
1,58
1,33
1,10
0,89
3,62
3,07
2,53
2,05
1,52
3,97
3,42
2,85
2,34
1,87
315
272
229
189
153
623
528
435
353
261
683
588
490
402
322
11,8
9,2
6,7
4,8
3,3
18,5
13,9
9,9
6,8
4,0
12,7
9,8
7,1
5,0
3,4
Ph
Qw
Dp(c)
= Emission
= Water flow
= Water side
pressure drop
Legend
WT
= Water temperature
Vdc = Inverter power
Qv
= Air flow
30
WT: 60/50°C
Qv
m3/h
CCN-ECM Version
Carisma
Coanda
Emissions
Heating emission of 1 row additional coil
Entering air temperature: +20°C
WT: 80/70°C
Model
CCN-ECM
13+1
14+1
CCN-ECM
23+1
24+1
CCN-ECM
33+1
34+1
WT: 75/65°
WT: 70/60°
WT: 65/55°
WT: 60/50°
WT: 55/45°
Vdc
Qv
m3/h
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
1,90
1,69
1,48
1,28
1,09
3,77
3,33
2,88
2,46
1,97
4,53
4,04
3,51
3,01
2,53
163
145
127
110
94
324
286
248
212
169
390
347
302
259
218
5,5
4,5
3,5
2,8
2,1
4,5
3,6
2,8
2,1
1,4
7,3
6,0
4,7
3,6
2,6
1,71
1,52
1,33
1,16
0,98
3,39
2,99
2,59
2,22
1,77
4,08
3,64
3,17
2,71
2,28
147
131
114
100
84
292
257
223
191
152
351
313
273
233
196
4,7
3,8
3,0
2,3
1,7
3,8
3,1
2,4
1,8
1,2
6,2
5,1
4,0
3,0
2,2
1,52
1,35
1,18
1,03
0,87
3,01
2,66
2,31
1,97
1,58
3,64
3,24
2,82
2,42
2,04
131
116
101
89
75
259
229
199
169
136
313
279
243
208
175
3,8
3,1
2,5
1,9
1,4
3,1
2,5
2,0
1,5
1,0
5,1
4,2
3,3
2,5
1,8
1,33
1,18
1,04
0,90
0,76
2,64
2,33
2,02
1,73
1,38
3,19
2,85
2,48
2,12
1,79
114
101
89
77
65
227
200
174
149
119
274
245
213
182
154
3,1
2,5
2,0
1,5
1,2
2,5
2,0
1,6
1,2
0,8
4,1
3,4
2,7
2,0
1,5
1,14
1,02
0,89
0,77
0,66
2,26
2,00
1,74
1,49
1,19
2,75
2,45
2,14
1,83
1,54
98
88
77
66
57
194
172
150
128
102
237
211
184
157
132
2,4
1,9
1,5
1,2
0,9
2,0
1,6
1,2
0,9
0,6
3,2
2,6
2,1
1,6
1,2
0,95
0,85
0,74
0,64
0,55
1,89
1,67
1,45
1,24
1,00
2,31
2,06
1,79
1,54
1,30
82
73
64
55
47
163
144
125
107
86
199
177
154
132
112
1,8
1,4
1,1
0,9
0,7
1,4
1,2
0,9
0,7
0,5
2,4
2,0
1,5
1,2
0,9
Heating emission of 2 row additional coil
Entering air temperature: +20°C
WT: 65/55°C
Model
CCN-ECM
13+2
CCN-ECM
23+2
CCN-ECM
33+2
WT: 60/50°
WT: 55/45°
WT: 50/40°
WT: 45/40°
WT: 45/35°
Vdc
Qv
m3/h
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
Ph
kW
Qw
l/h
Dp(c)
kPa
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
295
250
205
165
130
540
450
370
295
215
620
525
430
345
275
2,32
2,04
1,77
1,51
1,26
4,56
3,98
3,42
2,86
2,21
5,42
4,77
4,12
3,45
2,82
200
175
152
130
108
392
342
294
246
190
466
410
354
297
243
14,8
11,9
9,2
6,9
5,1
12,3
9,6
7,4
5,4
3,4
19,8
15,8
12,2
8,9
6,3
2,00
1,77
1,53
1,30
1,09
3,94
3,44
2,97
2,48
1,91
4,70
4,14
3,58
3,00
2,45
172
152
132
112
94
339
296
255
213
164
404
356
308
258
211
11,6
9,3
7,2
5,5
4,0
9,7
7,6
5,8
4,3
2,7
15,6
12,5
9,7
7,1
5,0
1,69
1,49
1,29
1,10
0,92
3,33
2,91
2,51
2,10
1,62
3,98
3,51
3,03
2,54
2,08
145
128
111
95
79
286
250
216
181
139
342
302
261
218
179
8,8
7,0
5,4
4,1
3,0
7,3
5,7
4,4
3,2
2,1
11,8
9,5
7,3
5,4
3,8
1,37
1,21
1,05
0,90
0,75
2,72
2,38
2,05
1,72
1,33
3,26
2,87
2,49
2,08
1,71
118
104
90
77
65
234
205
176
148
114
280
247
214
179
147
6,2
5,0
3,9
2,9
2,2
5,2
4,1
3,2
2,3
1,5
8,5
6,8
5,3
3,9
2,7
1,30
1,14
0,99
0,84
0,71
2,55
2,23
1,92
1,60
1,24
3,04
2,67
2,31
1,93
1,58
224
196
170
144
122
439
384
330
275
213
523
459
397
332
272
19,2
15,4
11,9
9,0
6,6
15,9
12,5
9,6
7,0
4,4
25,6
20,5
15,8
11,6
8,1
1,06
0,94
0,81
0,69
0,58
2,11
1,84
1,59
1,33
1,03
2,54
2,24
1,94
1,63
1,33
91
81
70
59
50
181
158
137
114
89
218
193
167
140
114
4,0
3,2
2,5
1,9
1,4
3,4
2,7
2,1
1,5
1,0
5,6
4,5
3,5
2,5
1,8
Legend
WT
= Water temperature
Vdc = Inverter power
Qv
= Air flow
Ph
Qw
Dp(c)
= Emission
= Water flow
= Water side
pressure drop
31
Water side pressure drop
3 row coil
4 row coil
Dp
Dp
50
50
40
40
3
30
CCN-ECM Version
Carisma
Coanda
30
20
2
20
3
2
10
9
8
10
9
8
7
7
6
6
5
5
1
4
4
3
3
2
2
1
100
200
1
300
400
600
800 1000
1500
1
Qw
Pressure drop for mean water temperature of 10°C; for
different temperatures multiply the pressure drop figure by the
K correction factors in the table.
100
°C
K
200
20
0,94
30
0,90
1 row additional coil
40
0,86
600
50
0,82
800 1000
1500
60
0,78
Qw
70
0,74
80
0,70
Dp
60
60
50
50
40
40
30
30
20
20
10
9
8
7
6
10
9
8
7
6
3
5
5
4
4
3
2
1
3
1
2
2
2
1
50 60
80 100
200
300
400
600
800 1000
Legend
Qw = water flow (l/h)
Dp = pressure drop (kPa)
1
Qw
Pressure drop for mean water temperature of 65°C; for
different temperatures multiply the pressure drop figure by the
K correction factors in the table.
32
400
2 row additional coil
Dp
3
300
50 60
°C
K
80 100
40
1,14
200
50
1,08
300
400
60
1,02
600
800 1000
70
0,96
Qw
80
0,90
CCN-ECM Version
Carisma
Coanda
Accessories
VBP Main coil
3 way valve
VBA Additional coil
3 way valve
Control valve kit:3 way valve, ON-OFF, with electric motor
and mounting kit with micrometric lockshield valve.
Control valve kit:3 way valve, ON-OFF, with electric motor
and mounting kit with micrometric lockshield valve.
VS Simplified kit for 3 way valve
for main and additional coil
V2 2 way valve
for main and additional coil
3 way valve, (ON-OFF) with electric motor and mounting kit.
Valve with flat connection without micrometric lockshield
valve.
Control valve kit: 2 way valve, ON-OFF, with electric motor
and mounting kit.
Valve
type
mod.
Main
1-2
DN
(Ø)
Kvs
Micrometric
lockshield valve
DN
(Ø)
Kvs
15
1/2"
1,6
15
Valve
1/2"
2
Code
Fitted
Not Fitted
9066561H
9066560H
VBP
VBA
Valves pressure drop
Kvs 2
Dp
3
20
3/4"
2,5
15
1/2"
2
9060471H
9060474H
Additional
All
15
1/2"
1,6
15
1/2"
2
9060472H
9060475H
1-2
15
1/2"
1,6
-
-
-
9066571H
9066570H
3
20
3/4"
2,5
-
-
-
9060484H
9060481H
4
All
15
1/2”
1,6
-
-
-
9060483H
9060480H
2
1-2
15
1/2"
1,7
-
-
-
9060476H
9060478H
1
3
20
3/4"
2,8
-
-
-
9060477H
9060479H
All
15
1/2”
1,7
-
-
-
9060476H
9060478H
Main
Additional
Kvs 1,6
Kvs 2,5
Kvs 2,8
40
Main
VS
Kvs 1,7
30
20
10
9
8
7
6
5
3
100
200
300 400
600 800 1000
2000 3000 4000
Main
V2
Additional
Qw
Legend
Qw = water flow (l/h)
Dp = pressure drop (kPa)
33
Carisma
Coanda
Accessories
CCN-ECM Version
BSO Extension condensate collection tray
to cover valve assembly
Connection side
ID
Code
left
BSO
BSO-SX
6060402
right
BSO-DX
6060403
SCR plastic condensate drain pipe with
fast connection
It helps regular drainage of condensate thereby preventing the
formation of bends.
ID
Code
SCR
6060420
PCC condensate drain pump
ID
Fitted
PCC-M
Not fitted
PCC-S
Code
9064011
9064010
Height for vertical
flow (m)
1
2
3
4
Water flow (l/h) depending on the length of
horizontal flow
5m
10 m
6,8
6,3
5,5
5,0
4,2
3,8
3,0
2,6
FRC fresh air connection
Code
FRC 100
ID
6064191
Code
TCX 3.9 x 9.5
6064192
TCX 3.9 x 9.5
98
34
FRC 120
122
ID
CCN–ECM configuration
Carisma
Coanda
CCN-ECM Version
For this fan coil configuration, the 1-10 Vdc signal, which controls the inverter, must be supplied by a controller with the following
signal specifications:
• Impedance < 100 Ω;
• Maximum speed 10 Vdc;
• Fan OFF with V < 0,9 Vdc.
• Signal 0,3 / 13 V.
CCN–ECM electric wiring diagram
CM
CP
Legend
CONTROLLER
ECM BLAC BOARD
M
CM
CP
= Controller
= Inverter circuit board
= Electronic motor
= Motor fan connection
= Motor fan thermal protection connection
35
Carisma
Coanda
CR-T-ECM Wall electronic control
ID
Code
CR-T-ECM
9066342
CCN-ECM Version
The control must always be connected with UPM-ECM power
unit (fitted on the unit) or with UPS-ECM power unit (not fitted
on the unit).
•
•
•
•
•
•
•
•
•
It allows to control up to 16 units (one power unit for each unit).
ON-OFF switch.
Manual 3 speed switch or automatic continuous speed control.
Manual Summer/Winter switch.
Continuous speed control based on the difference between ambient
temperature and Set temperature (speed switch in Auto position).
Electronic room thermostat for fan or valves control (ON-OFF).
Simultaneus thermostatic control of the valves and fan.
It allows to control the low temperature cut-out thermostat (NTC).
It allows to control the summer/winter cycle with a centralized and
remote switch or with an automatic change-over fitted on the water
pipe (for 2-tube installations only).
Dimensions: 133x93x37 mm
Description
Power unit for CR-T-ECM remote control (fitted on the unit)
Power unit for CR-T-ECM remote control (not fitted on the unit)
ID
Code
UPM-ECM
UPS-ECM
9066341
9066340
Power unit to be installed on the fan coil (fan coil interface).
It controls the fan and the valves of the fan coil.
The power unit is connected to the electric supply.
The power unit receives the information required from the control.
Control power absorption: 1,5 VA
36
CR-T-ECM Accessories
Carisma
Coanda
CCN-ECM Version
NTC low temperature cut-out thermostat
ID
Code
NTC
3021090
To be fitted between the coil fins; when connecting the control, the NTC probe cable must be separated from the power supply
wires.
To be used with the following controls: CR-T-ECM
It stops the fan when the water temperature is lower than 28°C and it starts the fan when is higher than 33°C.
Change-Over CH 15-25
ID
Code
CH 15 -25
9053049
Automatic summer/winter switch to be installed in contact
with the water circuit.
For 2-tube installations only (not to be used with 2 way valve).
To be used with the following controls: CR-T-ECM.
A
B
Legend
A = red
B = black
37
CCN / CCN-ECM Version
Carisma
Coanda
Controls and units MB version
All the Carisma Coanda units can be supplied with a wide range of controls, which allows managing one single unit or several
units by using the Modbus RTU - RS 485 communication protocol.
Units can be managed according to the Master/Slave logic (up to 20 units) or by supervisory components.
The system consists in a MB board and a series of controls, such as the T-MB wall control, the RT03 infra-red remote control,
the PSM-DI multifunction control and the Sabianet supervisory program.
T-MB Wall
control
PSM-DI Multifunction
PC
Sabianet Screenshot
RT03 Infra-red
remote control
Sabianet Software
38
control
CCN / CCN-ECM Version
Carisma
Coanda
Controls and units MB version
MB electronic board
Description
Version
CCN
CCN
CCN_ECM
CCN_ECM
MB electronic board fitted on the unit
MB electronic board supplied with separate packaging
MB electronic board fitted on the unit
MB electronic board supplied with separate packaging
ID
Code
MB-M
MB-S
MB-ECM-M
MB-ECM-S
9066332
9066333
9066334
9066335
The MB electronic board, to be mounted on the fan coil internal
unit, is set to carry out different functions and adjustment
modes, in order to meet the installation requirements. These
modes are selected by setting the configuration dip switches
on the board.
• 2/4 pipe system.
• Fan ON/OFF thermostatic control.
• Valve ON/OFF thermostatic control
and continuous
ventilation.
• Valve and simultaneous ventilation ON/OFF
thermostatic
control.
• Fan operation control depending on the coil temperature
(cut-out T3 probe fitted), which can be activated
only in
heating mode or heating and cooling mode.
• Automatic switch of the operating mode by means of T2
water probe (optional) applied on the 2 pipe system.
• Seasonal switch by means of remote contact.
• ON/OFF of the fan coil by means of the remote contact
(window or clock contact).
• Electric heater control
By activating the cut-out T3 probe function, the fan is stopped in winter when the coil temperature is lower than 32°C and
started when the temperature reaches 36°C. In summer mode, the fan stops when the temperature inside the coil exceeds 22°C
and starts when it drops below 18°C.
The following connections are located on the power board:
• Receiver for infra-red remote control.
• T-MB wall control.
• RS 485 serial connection to manage several fan coils in Master/Slave configuration or to create a supervisory network.
39
CCN / CCN-ECM Version
Controls and units MB version
Carisma
Coanda
T-MB wall control
Description
Wall control (to be used with MB board only)
ID
Code
T-MB
9066331E
Wall control with display that allows controlling one or more
units in Master/Slave mode. The control is equipped with
internal sensor to detect the room temperature, which can
be defined as a priority compared to the return air sensor on
the fan coil.
The T-MB control features the following functions:
•
•
•
•
•
•
•
•
40
Switch the appliance ON and OFF.
Temperature set.
Modify the set point (when used as a +/- 3° variation of the set point configured from Sabianet supervisory program).
Set the fan speed (low, medium, high or autofan).
Set the operation mode (fan only, cooling, heating; auto for 4 pipe systems with mode selection depending on the air temperature).
Time setting.
Weekly ON/OFF program.
Display and change of the fan coil operation parameters.
CCN / CCN-ECM Version
Controls and units MB version
Carisma
Coanda
RT03 infra-red remote control
Description
RT03 infra-red remote control with receiver supplied with separate packaging
(to be used with MB board only)
RT03 infra-red remote control supplied with separate packaging
(to be used with MB board only)
Receiver for RT03 infra-red remote control supplied with separate packaging
(to be used with MB board only)
ID
Code
RS-RT03
9066337
RT03
3021203
RS
9066338
The infra-red remote control allows setting by a remote
position the fan coil operation parameters.
The RT03 infra-red remote control features the following
functions:
• Switch the appliance ON and OFF.
• Temperature set.
• Set the fan speed (low, medium, high or autofan).
• Set the operation mode (fan only, cooling, heating; auto for
4 pipe systems with mode selection depending on the air
temperature).
• Time setting.
• 24 hours ON/OFF program.
Installation
example with
infra-red remote
ID
Code
RT03
3021203
control
ID
Code
ID
Code
RS-RT03
9066337
RS
9066338
41
CCN / CCN-ECM Version
Carisma
Coanda
Controls and units MB version
A group of Carisma Coanda units with MB electronic board can be connected via a serial link and can consequently be
managed at the same time by just one T-MB wall control or RT03 infra-red remote control. Using the special jumper present on
the MB board, one unit must be configured as the master, and all the others as slaves. It is clear that the remote control must
be pointed at the receiver on the master unit. To avoid problems, it is recommended to install and connect the receiver only on
the master unit.
With T-MB wall control
One control for each unit
(Maximum length of the connection cable = 20 m)
Max
20 m
One control for more units
(20 units max.)
(Maximum total length of the connection cable = 800 m)
Max
20 m
With RT03 infra-red remote control
One control for each unit
One control for more units
(20 units max.)
(Maximum total length of the connection cable = 800 m)
T2 accessory for units with MB electronic board
ID
Code
T2
9025310
The T2 sensor can be combined with MB boards to be placed on the water supply pipe upstream 3 way valves (not to be used
with 2 way valve). The T2 sensor must be used as described below:
• Change-Over for 2-pipe system for the automatic switch of the operating mode. If water temperature is lower than 20°C, cooling
mode is set; on the other hand, if water temperature exceeds 30°C, heating mode is set.
• It can be used on units with electric heater and hot water supply. The T2 priority probe activates the electric heater or water valve,
depending on the water temperature detected. If water temperature exceeds 34°C, the water valve ON-OFF control is activated; on
the other hand, if water temperature is lower than 30°C, the electric heater is activated.
42
CCN / CCN-ECM Version
Controls and units MB version
Carisma
Coanda
PSM-DI Multifunction control
Description
Multifunction control (to be used with MB board only)
ID
Code
PSM-DI
3021293
Another option available for the serial communication between
the units is the possibility to connect up to 60 Carisma
Coanda units in series and manage them with just one wall
mounted PSM-DI controller.
The wall mounted controller can be used to set the operating
mode for each individual unit connected, display the operating
conditions of each individual unit, and set the ON/OFF time
sets for each day of the week (the program can be set for all
the units and for a maximum of two groups of units).
If more than 60 units need to be connected, two or more
controllers must be used. Each wall mounted controller only
manages the units it is connected to.
The PSM-DI control is used to manage a series of fan coils,
up to a maximum of 60 units (the maximum length of the RS
485 connection cable must not exceed 800 m), from one
single control point.
The PSM-DI control communicates via a serial line with all the units connected, with the possibility of controlling them all
together or individually. In fact, the unique address of each individual fan coil means that all the units can be called at the same
time, or the individual unit called, to perform the following functions:
- display the current operating mode, the fan speed, the set point;
- display the room temperature measured on the individual unit;
- turn all the units ON and OFF at the same time or alternatively each unit individually;
- change the operating mode (fan only, heating, cooling, automatic changeover);
- change the set point;
- modify the values and operation parameters of the fan speed.
Each function can then be sent to all the units connected, or alternatively to each individual unit.
Different set points or operating modes can be set for each individual unit.
The PSM-DI panel can also be used for the time management of the units over the week. Four ON times and four OFF times
can be set on the units for each day of the week. A different Temperature set that will be considered as Operation set for all
connected appliances, can be set for each event. If the Temperature set is not entered for the individual event, it must be set
during programming for each individual unit or for the entire network.
Units without receiver or with receiver can be connected within the network: the former can receive instructions only from the
PSM-DI wall mounted panel; while the latter can receive information from both the wall mounted panel (PSM-DI) and infra-red
remote control. Use the infra-red remote control to force ON mode of the individual unit, if ON/OFF daily time programming has
been set. The unit will regain the settings from the PSM-DI panel during execution of successive start-up program.
The PSM-DI panel cannot be used
together with the Sabianet management program (see next page).
Note: set the configuration Dip Switches of each fan coil as illustrated in the remote control use manual, based on the required
solutions.
Note: the RS 485 network’s overall length must not exceed 700/800 metres.
43
Management system for a network
of units
CCN / CCN-ECM Version
Carisma
Coanda
Sabianet program for managing a network of Sabiana MB fan coils
Description
Hardware/software supervisory system (to be used with MB board only)
ID
Code
Sabianet
9079118
Sabianet is a centralised control system for networks of
Sabiana MB fan coils, based on software that runs on LINUX™.
The Sabianet software offers a practical and economical
solution for managing the units, with the simple click of the
mouse.
The main characteristics include simplicity of use, an extremely
complete and functional weekly program, and the possibility
to access the historical operating data for each individual
appliance connected.
The program exploits all the potential of our units with remote
controls, representing an addition to the latter.
The Sabianet program is a control tool that can be used as
a replacement for the remote control, or in parallel, however
the settings made using Sabianet can have priority over those
made using the remote control.
The program can be used to:
• Create uniform groups (groups of units on individual floors, in offices or rooms).
• Save weekly programs configured for different types of operation (summer, winter, mid seasons, closing periods etc.); these
can then be recalled and activated with a simple click of the mouse.
Weekly on/off cycles can be set for individual units or groups of units.
• Set the operating conditions for each individual unit or groups of units (operating mode, fan speed, temperature setting).
• Set the set point limits for each individual unit or groups of units.
• Switch each individual unit or groups of units ON or OFF.
“MONITORING” Screen
The main program screen can display and interact with the entire network of units. An individual unit, a group of units or the
entire network can be called so as to make modifications to the operating mode and the set point. The user can then check
the operating status of each individual unit, read the room temperature, the coil temperature and the operating status of the
condensate drain pump or any alarms.
44
Management system for a network
of units
CCN / CCN-ECM Version
Carisma
Coanda
Displaying a unit
The “MONITORING” screen shows the units that are
connected to the network and scanned by the program.
The icon of the terminal unit
provides the following information:
- Unit name ( C01000001 )
- Set temperature ( TSET )
- Room temperature ( TA )
- Unit status: ON
or OFF
-Mode:
•
Summer
•
Auto
•
Winter
•
Fan only
- Fan speed:
•
Low
•
High
•
Medium
•
Autofan
“EVENT MANAGEMENT”
screen
The “Weekly Program” can be used to set the unit operating parameters for each day of the week. Up to 20 different weekly
programs can be set.
Time bands are available for each day of the week. The time and the type of operation to be performed by the unit can be set
for each band. The time and the operating parameters can then be displayed before being sent to the unit and implemented.
45
Management system for a network
of units
CCN / CCN-ECM Version
Carisma
Coanda
PC Sabianet Software
Connection of a
Carisma Coanda network
with MB electronic board
60 units max.
Carisma Coanda
Unit
Carisma Coanda
Unit
Carisma Coanda
Unit
MC2 jumper
to close
network end.
(*) In the event of more than
60 units, add one or more
Router-S (see below).
RS 485 serial connection cable
Shielded cable to be used:
Belden 9841, RS-485, 1x2x24 AWG SFTP, 120 Ohm
PSM-DI and Sabianet electronic boards for Coanda units
ID
Code
SIOS
3021092
SIOS is a board equipped with 8 relays with potential free contact to control the
activation or deactivation of remote electric utilities. Moreover, the board has 8 digital
inlets to display the actuators or external consents, such as motor or other. The SIOS
boards can be connected:
- inside a network managed by Sabianet;
- to a PSM-DI panel (one SIOS for each PSM-DI panel).
ID
Code
Router-S
3021290
The Router-S is an electronic board that:
-allows creating networks with more than 60 units (minimum 2 Router-S are required)
or to divide the network (per floor, building, etc.);
-allows creating a Master/Slave sub-network to be controlled as an indipendent group.
The Router-S can be used only inside a network managed by Sabianet.
The number of Router-S to be used is:-up to 60 units: no Router-S
- from 61 to 120 units: 2 Router-S
- every 60 subsequent units: 1 additional Router-S
46
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right,
whilst maintaining the essential characteristics of the types described and illustrated, to make, at any time,
without the requirement to promptly update this piece of literature, any changes that it considers useful for the
purpose of improvement or for any other manufacturing or commercial requirements.