Enon 12W Outdoor 1

SELF-LIMITING
HEATING TAPE HTL
FEATURES
Heat output is automatically adjusted in
response to pipe temperature changes
Can be cut to required length without any
property changes affected by this
Protected against overheating or burning out
even in case of overlapping
Full range of control facilities and accessories
Approved to be used in non-hazardous,
hazardous and corrosive environments
Ideal solution for heating equipment and small
diameter pipes
Operating voltage 230VAC (120VAC upon
request)
DESCRIPTION
The HTL self-limiting heating tape is used for
electrical heat tracing for frost protection.
The temperature dependant resistive element
between the parallel bus wires adjusts the
heat output of the heating tape according to
the ambient temperature. Typical applications
for the HTL heating tape are roof and gutter
heating. It can be cut to any required length at
site, and the exact pipe length can be achieved
without any complicated design alterations.
HTL is approved for the use in safe and explosion hazardous zones according to worldwide
standards.
The self-limiting performance increases the
tape’s safety and reliability. HTL does not get
overheated or burned even in case its parts are
overlapping. Its power output is automatically
adjusted in response to temperature changes.
The installation of the HTL tape is easy, quick
and requires no special skills or tools. All components for termination, splicing and power
connection are available in convenient kits.
CABLE DESIGN
Self-limiting heating tape HTL-S2 and HTL-B2
2nd insulation
Earthing conductor
Aluminium foil
Braiding
1st insulation
Heating matrix
Bus wire 0.75 mm2
Heating matrix
Bus wire 0.75 mm 2
TECHNICAL DATA
Rated voltage
Maximum operation temperature
(switched on)
Maximum operation temperature
(switched off)
Minimum operation temperature
Minimum storage temperature
Minimum installation temperature
Minimum bending radius
Dimensions for HTL-S2
Dimensions for HTL-B2
Polyolefin outer sheath
Fluoropolymer outer sheath
230 VAC
65°C
85°C
– 45 °C
– 45 °C
– 30 °C
25 mm
9,0×5,5 mm
8,5×5,7 mm
5,2×8,0 mm
Enon “inspiring in heating” - Bijsterhuizen 3007a - 6604 LP Wijchen - [email protected] - www.enon.nl
40
Proektiruemyj proezd 5274 Build. 7 Mytischi, Moscow reg., RUSSIA
Phone/fax: +7 495 258-90-40, +7 495 728-80-80
E-mail: [email protected], www.i-warm.com
Outdoor Heating Solutions
PRODUCT REFERENCES
Heating circuit length*
Type
12 HTL-S2-BT
12 HTL-S2-BP
Heating circuit length*
Start-up
temperature,
C
16A
20A
32A
–20
0
+10
–20
0
+10
100
100
100
100
100
100
–
–
–
–
–
–
–
–
–
–
–
–
Heating circuit length
Start-up
Heating circuit length
temperature,
16A
20A
32A
C
Type
12 HTL-B2-BT
12 HTL-B2-BP
–20
0
+10
–20
0
+10
100
100
100
100
100
100
–
–
–
–
–
–
–
–
–
–
–
–
* Circuit breaker Type C according to BS EN 60 898,1991.
TEMPERATURE RATINGS
INSTALLATION
12 HTL-S2
Power output [W/m]
Applicable norms, rules and data sheets as well as
instructions and manuals are to be followed!
The installation of the HTL tape is simple and quick.
All components for termination, splicing and power
connection are available in convenient kits.
For detailed installation instructions please use the
“Roof de-icing system TEPLOSKAT Installation manual”
INST-1017 and “GT 200E electronic temperature controller for roof and gutter de-icing systems Operating
Manual” INST-1009.
TYPES
Workpiece temperature [°C]
12 HTL-B2
Power output [W/m]
12 HTL-x2-BT
12 HTL-x2-BP
Polyolefin outer sheet
Flouropolymer outer sheet
APPROVAL DETAILS
The compliance with all necessary requirements is
approved by appropriate Certificates:
Certificate of
Compliance
Certifi-cate VDE
Certificates according to other national
standards upon request.
Workpiece temperature [°C]
.. nigshofen
Enon “inspiring in heating” - Bijsterhuizen 3007a - 6604 LP Wijchen
- [email protected]
- www.enon.nl
41
Tel.: + 49 9343 62738-0, Fax: +49 9343 62738-10