Switch-disconnector3p160ABG2 Partno. N2

Switch-disconnector�3p�160A�BG2
Part�no.
Article�no.
N2-160
266008
Catalog�No.
Delivery�programme
Product range
Protective function
Standard/Approval
Installation type
Construction size
Description
Number of conductors
Standard equipment
Switch positions
Rated current = rated uninterrupted
current
Short-circuit protection max. fuse gLcharacteristic
In = Iu
A
Switch-disconnectors
Disconnectors/main switches
IEC
Fixed
N2
Main switch characteristics including
positive drive to IEC/EN 60204 and VDE
0113.
Isolating characteristics to IEC/EN
60947-3 and VDE 0660.
Busbar tag shroud to
VDE 0160 Part 100.
3 pole
Screw connection
I, +, 0
160
A gL
250
Switch-disconnectors
Rated surge voltage invariability
Uimp
V
8000
V
6000
Ue
V
AC
690
In = Iu
A
160
III/3
Ui
V
690
V
Rated operating voltage: 40-60 Hz
Weight
Temperature dependency, Derating
Effective power loss
Ic
kA
5.5
Icw
kA
3.5
Icw
kA
3.5
The rated short-time withstand current for PN2/N2 in conjunction with
earth-fault release NZM2-4-XFI...Icw = 1.5 kA
With back-up fuse
PN2(N2)-160…250: 250
400 … 415 V
A
gG/
gL
kA
100
kA
80
A
gG/
gL
PN2(N2)-160…250: 250
kA
100
kA
80
Ie
A
Ie
A
250
Ie
A
250
Ie
A
250
Main contacts
Auxiliary contacts
Rated operational voltage
Rated current = rated uninterrupted current
Overvoltage category/pollution degree
Rated insulation voltage
Use in unearthed supply systems
Other technical data (sheet catalogue)
Rated�short-circuit�making�capacity
690 V 50/60 H
Rated�short-time�withstand�current
t = 0.3 s
t=1s
Rated�conditional�short-circuit�current
690 V
With downstream fuse
400 … 415 V
690 V
Rated�making�and�breaking�capacity
Rated operational current
415 V
690 V
415 V
03/20/2014
HPL-ED2014 V2.13 EN
690
1/5
690 V
Ie
A
250
Operations
20000
Ops/
h
120
Operations
10000
Operations
10000
Operations
7500
Operations
7500
Operations
7500
Operations
5000
Current heat losses per pole at Iu are based on the maximum rated
operational current of the frame size.
For current heat loss per pole the specification refers to the maximum
rated operational current of the frame size.
W
16
Total downtime in a short-circuit
For current heat loss per pole the specification refers to the maximum
rated operational current of the frame size.
ms
< 10
Screw connection
Lifespan, mechanical
Max. operating frequency
Lifespan,�electrical
400 V V 50/60 Hz
415 V V 50/60 Hz
690 V 50/60 Hz
400 V 50/60 Hz
415 V 50/60 Hz
690 V 50/60 Hz
Terminal�capacity
Standard equipment
Overview
Round copper conductor
Box terminal
Solid
Basic
equipment
Box terminal
Screw connection
Accessories Box terminal
Screw connection
Tunnel terminal
Connection
on
rear
Flat conductor
terminal
Stranded
mm
Tunnel terminal
1 x (25 - 185)
2 x (25 - 70)
Stranded
Bolt terminal and rear-side connection
Direct on the switch
Solid
Stranded
Al conductors, Cu cable
Solid
Stranded
Stranded
Bolt terminal and rear-side connection
Flat copper strip, with holes
Flat copper strip, with holes
Cu strip (number of segments x width x segment thickness)
Box terminal
03/20/2014
●
-
-
-
-
●
●
●
-
●
●
-
●
-
-
●
●
●
●
●
●
●
●
●
-
-
-
●
mm
Stranded
Solid
2
1 x (4 - 16)
2 x (4 - 16)
2
2
mm
1 x (16 - 185)
mm
2
mm
2
1 x (25 - 185)
2
mm
1 x (4 - 16)
2 x (4 - 16)
mm
2
1 x (25 - 185)
2 x (25 - 70)
mm
mm
2
1 x 16
2
mm
2
1 x (25 - 185)
min.
mm
2 x 16 x 0.8
max.
mm
10 x 16 x 0.8
HPL-ED2014 V2.13 EN
2/5
min.
mm
max.
Bolt terminal and rear-side connection
Flat copper strip, with holes
Flat copper strip, with holes
Copper busbar (width x thickness)
Bolt terminal and rear-side connection
Screw connection
Direct on the switch
Control cables
2
2 x 9 x 0.8
mm
2
10 x 16 x 0.8
min.
mm
2 x 16 x 0.8
max.
mm
10 x 16 x 0.8
mm
M8
min.
mm
max.
2
16 x 5
mm
2
20 x 5
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Technical�data�ETIM�5.0
Low-voltage industrial components (EG000017) / Switch disconnector (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector
(ecl@ss8-27-37-14-03 [AKF060009])
Version as switch disconnector
1
compact
Version as main switch
1
Version as maintenance-/service
1
switch
Version as safety switch
0
Version as emergency stop installation
1
Max. rated operation voltage Ue AC
V
690
Rated permanent current Iu
A
160
Rated operation power AC-3, 400 V
kW
90
Rated operation power at AC-23, 400 V
kW
90
Conditioned rated short-circuit current
kA
100
Iq
Number of poles
3
Number of auxiliary contacts as
0
normally closed contact
Number of auxiliary contacts as
0
normally open contact
Number of auxiliary contacts as
0
change-over contact
Motor drive optional
1
Motor drive integrated
0
Voltage release optional
1
Device construction
Built-in device fixed built-in technique
Suitable for ground mounting
1
Suitable for front mounting
0
Suitable for front mounting center
0
Suitable for distribution board
1
installation
Suitable for intermediate mounting
1
Type of control element
Rocker lever
Interlockable
1
Connection type main current circuit
Screw connection
Degree of protection (IP), front side
IP20
Dimensions
03/20/2014
HPL-ED2014 V2.13 EN
3/5
Blow out area, minimum clearance to adjacent parts
Minimum clearance to adjacent parts
03/20/2014
HPL-ED2014 V2.13 EN
4/5
Additional�product�information�(links)
IL01206006Z�(AWA1230-1916)�Circuit-Breaker,�basic�unit
IL01206006Z (AWA1230-1916) CircuitBreaker, basic unit
03/20/2014
ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL01206006Z2013_07.pdf
Eaton Industries GmbH
http://www.eaton.eu
© 02/2014 by Eaton Industries GmbH
HPL-ED2014 V2.13 EN