Overview of Telecommunications Bonding & Grounding Systems Item # 6 Telecommunications Room (TR) Telecommunications Room (TR) TGB Telecommunications Room (TR) Description Part Number 1 Telecommunications Grounding Busbar (TGB) 2 Telecommunications Main GBI14420TGB Grounding Busbar (TMGB) 3 Bonding Conductor for #6 AWG up to #750 MCM Telecommunications (BCT) 4 Grounding Electrode Conductor #6 AWG up to #750 MCM 5 Grounding Electrode System Ultraweld connection to ground conductor & ground rod 6 Grounding Equalizer (GE) #6 AWG up to #750 MCM 7 Telecommunications Bonding Backbone (TBB) #6 AWG up to #750 MCM GBI14220TGB TGB 7 Telecommunications Room (TR) 7 TGB TGB Equipment Room (ER) Electrical Entrance Facility 7 2 1 5 Telecommunications Entrance Facility (TEF) 607B201117BG Courtesy of 3 4 Sizing the Grounding Equalizer (GE) The GE shall be, as a minimum, the same size as the largest TBB. #6 AWG up to #750 MCM Grounding Equalizer (GE). # RGBV145872A Equipment Rack Grounding Busbar. #GBI14220TGB Telecommunications Grounding Busbar (TGB). #6 AWG up to #750 MCM Telecommunications Bonding Backbone (TBB). 607B201127GESing Courtesy of Equipment Rack Bonding #6 AWG up to #750 MCM TEBC (TELECOMMUNICATION EQUIPMENT BONDING CONDUCTOR). TO TMGB / TGB #6 AWG up to #750 MCM RACK BONDING CONDUCTORS ROUTED TO TMGB / TGB # CT4666 THRU CT4/04/0 IRREVERSIBLE CRIMP CONNECTOR. # RGBH14119.25 TOP MOUNTED RACK GROUNDING BUSBAR. # RGBV145872A VERTICALLY MOUNTED RACK GROUNDING BUSBAR. # UBC61411/410 THRU UBC63811/410 UNIT BONDING CONDUCTOR (UBC) # UBC61411/410 THRU UBC63811/410 INDIVIDUAL UNIT BONDING CONDUCTORS (UBC) FROM EACH PIECE OF EQUIPMENT TO THE RACK BONDING CONDUCTOR. INDIVIDUAL EQUIPMENT GROUNDING TERMINAL (TYPICAL EACH PIECE OF EQUIPMENT) RACK BONDING CONDUCTOR EXTENDED TO BOTTOM OF RACK TO ACCOMMODATE FUTURE GROWTH MINIMUM BENDING RADIUS MUST BE MAINTAINED ON ALL CONDUCTORS Example “A” Example “B” Example “C” Example of three methods to bond equipment racks to ground. 607B201138ERB Courtesy of Grounding Equalizer (GE) When two or more TBB’s are used in a multistory building, the TBB’s shall be bonded together with a GE at the top floor and at a minimum of every third floor in between to the lowest floor level. Grounding Equalizer (GE) Part # RGBH14119.25 TGB TGB Part # GBI14220TGB Part # RGBV145872A Part # GBI14220TGB Telecommunications Bonding Backbone (TBB) 607B201151GE Courtesy of
© Copyright 2024 ExpyDoc