MXZ-C H2i Engineering Manual Section

MXZ MULTI-ZONE SYSTEMS
H2i® MXZ Outdoor units
1. SPECIFICATIONS............................................................................................................................................... H2i-MXZ-2
MXZ-2C20NAHZ............................................................................................................................................... H2i-MXZ-3
MXZ-3C24NAHZ............................................................................................................................................... H2i-MXZ-4
MXZ-3C30NAHZ............................................................................................................................................... H2i-MXZ-5
MXZ-4C36NAHZ............................................................................................................................................... H2i-MXZ-6
MXZ-5C42NAHZ............................................................................................................................................... H2i-MXZ-7
MXZ-8C48NAHZ............................................................................................................................................... H2i-MXZ-8
Branch Box........................................................................................................................................................ H2i-MXZ-9
PAC-MKA50BC PAC-MKA30BC..................................................................................................................... H2i-MXZ-9
Efficiency Ratings............................................................................................................................................ H2i-MXZ-10
1-1. Compatibility Table....................................................................................................................................H2i-MXZ-11
1-2. Cooling and Heating Capacity and Characteristics.................................................................................. H2i-MXZ-12
1-3. Standard Operation Data (Reference Data)............................................................................................ H2i-MXZ-13
1-4. Standard Capacity Diagram..................................................................................................................... H2i-MXZ-14
2. EXTERNAL DIMENSIONS................................................................................................................................ H2i-MXZ-20
MXZ-2C20NAHZ ............................................................................................................................................ H2i-MXZ-20
MXZ-3C24NAHZ MXZ-3C30NAHZ................................................................................................................ H2i-MXZ-21
MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ................................................................................... H2i-MXZ-22
Branch Box...................................................................................................................................................... H2i-MXZ-23
PAC-MKA50BC PAC-MKA30BC
4. ELECTRICAL WIRING DIAGRAMS.................................................................................................................. H2i-MXZ-24
MXZ-2C20NAHZ............................................................................................................................................. H2i-MXZ-24
MXZ-3C24NAHZ MXZ-3C30NAHZ................................................................................................................ H2i-MXZ-25
MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ................................................................................... H2i-MXZ-26
Branch Box...................................................................................................................................................... H2i-MXZ-27
PAC-MKA50BC PAC-MKA30BC
5. REFRIGERANT SYSTEM DIAGRAMS............................................................................................................. H2i-MXZ-28
MXZ-2C20NAHZ............................................................................................................................................. H2i-MXZ-28
MXZ-3C24NAHZ MXZ-3C30NAHZ................................................................................................................ H2i-MXZ-29
MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ................................................................................... H2i-MXZ-30
Piping Connection Size................................................................................................................................... H2i-MXZ-31
6. CAPACITY CORRECTION CURVE BY TEMPERATURE................................................................................ H2i-MXZ-32
7. CAPACITY CORRECTION TABLE BY TEMPERATURE.................................................................................. H2i-MXZ-33
8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH..................................................... H2i-MXZ-34
MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ................................................................................... H2i-MXZ-34
9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH...................................................... H2i-MXZ-35
10. SOUND PRESSURE LEVELS........................................................................................................................ H2i-MXZ-36
MXZ-2C20NAHZ............................................................................................................................................. H2i-MXZ-36
MXZ-3C30NAHZ............................................................................................................................................. H2i-MXZ-36
MXZ-3C24NAHZ............................................................................................................................................. H2i-MXZ-36
MXZ-4C36NAHZ............................................................................................................................................. H2i-MXZ-37
MXZ-8C48NAHZ............................................................................................................................................. H2i-MXZ-37
MXZ-5C42NAHZ............................................................................................................................................. H2i-MXZ-37
11. STANDARD OPERATION RANGE................................................................................................................. H2i-MXZ-38
MXZ-2C20NAHZ MXZ-3C24NAHZ MXZ-3C30NAHZ................................................................................... H2i-MXZ-38
12. ACCESSORIES............................................................................................................................................... H2i-MXZ-39
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-1
1. SPECIFICATIONS
• Highly energy-efficient system that features 100% heating capacity at 5º F with guaranteed capacity down to -13º F
• Compact side discharge outdoor unit
• Indoor unit powered from outdoor unit using A-control (MXZ-2C20/3C24/3C30NAHZ only)
• Auto restart following a power outage
• Wired or wireless controller
• Quiet operation
• Built-in base pan heater to prevent ice in drain pan
• MXZ- 2C20,3C24,3C30NAHZ
- M-Net adaptor kits are available as an option*
• Limited warranty: five years parts and seven years compressor
*Included standard in PAC-MKA30/50BC Branch Box
For all MXZ H2i® Series outdoor units a minimum of two indoor units must be connected and the minimum installed
capacity cannot be less than 12,000 Btu/h.
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-2
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
MXZ-2C20NAHZ
Item
Capacity
Power
consumption
Cooling
Heating 47
Heating 17
Cooling
Heating 47
Heating 17
Cooling
Cooling
Heating
Heating
*1
*1
*2
*1
*1
*2
Outdoor model
Indoor type
Btu/h
Btu/h
Btu/h
W
W
W
EER
SEER
HSPF IV(V)
COP
External finish
Power supply
V, phase, Hz
Max. fuse size (time delay)
A
Min. circuit ampacity
A
Fan motor
F.L.A
Model
Winding resistance
Ω
(at 68 ºF)
Compressor
R.L.A
L.R.A
Refrigerant control
Sound level
dB(A)
Defrost method
W
in.
Dimensions
D
in.
H
in.
Weight
lb.
Remote controller
Control voltage (by built-in transformer)
Refrigerant piping
Liquid
in.
Valve size
Gas
in.
Indoor
Connection method
Outdoor
Refrigerant charge (R410A)
lb.
Refrigeration oil (Model)
oz.
MXZ-2C20NAHZ
Non-Duct (09+09)
Duct (09+12)
18,000
20,000
22,000
22,000
13,700
13,700
1,334
1,819
1,612
1,748
1,450
1,588
13.5
11.0
17.0
15.0
9.8
9.5
4.00
3.69
Munsell 3.0Y 7.8/1.1
208/230, 1, 60
40
28.9
1.90
MNB33FBTMC-L
U-V 0.30 V-W 0.30 W-U 0.30
20
28.8
LEV
54.0 / 58.0
Reverse cycle
37-13/32
13
41-17/64
187
Wireless type
4
Not supplied (optional parts)
1/4
A,B: 3/8
Flared
Flared
8 lb. 13 oz.
37.4 (FV50S)
NOTE : Test conditions are based on ARI 210/240.
Unit: °F
Mode
Cooling
Heating
Indoor air condition Outdoor air condition
Dry bulb Wet bulb Dry bulb Wet bulb
Test
*1: "A" Cooling steady state at rated compressor speed
"B-2" Cooling steady state at rated compressor speed
"B-1" Cooling steady state at minimum compressor speed
Low ambient cooling steady state at minimum compressor speed
Intermediate cooling steady state at intermediate compressor speed
*1: Standard rating-heating at rated compressor speed
*2: Low temperature heating at maximum compressor speed
Maximum temperature heating at minimum compressor speed
High temperature heating at minimum compressor speed
Frost accumulation at rated compressor speed
Frost accumulation at intermediate compressor speed
80
80
80
80
80
70
70
70
70
70
70
67
67
67
67
67
60
60
60
60
60
60
95
82
82
67
87
47
17
62
47
35
35
(75)
(65)
(65)
(53.5)
(69)
43
15
56.5
43
33
33
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-3
1. SPECIFICATIONS
MXZ-3C24NAHZ
Item
Capacity
Power
consumption
Cooling
Heating 47
Heating 17
Cooling
Heating 47
Heating 17
Cooling
Cooling
Heating
Heating
*1
*1
*2
*1
*1
*2
Outdoor model
Indoor type
Btu/h
Btu/h
Btu/h
W
W
W
EER
SEER
HSPF IV(V)
COP
External finish
Power supply
V, phase, Hz
Max. fuse size (time delay)
A
Min. circuit ampacity
A
Fan motor
F.L.A
Model
Winding resistance
Ω
(at 68 ºF)
Compressor
R.L.A
L.R.A
Refrigerant control
Sound level
dB(A)
Defrost method
W
in.
Dimensions
D
in.
H
in.
Weight
lb.
Remote controller
Control voltage (by built-in transformer)
Refrigerant piping
Liquid
in.
Valve size
Gas
in.
Indoor
Connection method
Outdoor
Refrigerant charge (R410A)
lb.
Refrigeration oil (Model)
oz.
MXZ-3C24NAHZ
Non-Duct (06+06+09)
Duct (09+09+09)
22,000
23,600
25,000
24,600
14,000
14,000
1,630
2,360
1,725
1,871
1,622
1,635
13.5
10.0
19.0
15.5
10.0
9.0
4.25
3.80
Munsell 3.0Y 7.8/1.1
208/230, 1, 60
40
29.9
1.90
MNB33FBTMC-L
U-V 0.30 V-W 0.30 W-U 0.30
20
28.8
LEV
54.0 / 58.0
Reverse cycle
37-13/32
13
41-17/64
189
Wireless type
4
Not supplied (optional parts)
1/4
A: 1/2 B,C: 3/8
Flared
Flared
8 lb. 13 oz.
37.4 (FV50S)
NOTE : Test conditions are based on ARI 210/240.
Unit: °F
Mode
Cooling
Heating
Test
*1: "A" Cooling steady state at rated compressor speed
"B-2" Cooling steady state at rated compressor speed
"B-1" Cooling steady state at minimum compressor speed
Low ambient cooling steady state at minimum compressor speed
Intermediate cooling steady state at intermediate compressor speed
*1: Standard rating-heating at rated compressor speed
*2: Low temperature heating at maximum compressor speed
Maximum temperature heating at minimum compressor speed
High temperature heating at minimum compressor speed
Frost accumulation at rated compressor speed
Frost accumulation at intermediate compressor speed
Indoor air condition Outdoor air condition
Dry bulb Wet bulb Dry bulb Wet bulb
80
80
80
80
80
70
70
70
70
70
70
67
67
67
67
67
60
60
60
60
60
60
95
82
82
67
87
47
17
62
47
35
35
(75)
(65)
(65)
(53.5)
(69)
43
15
56.5
43
33
33
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-4
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
MXZ-3C30NAHZ
Item
Capacity
Power
consumption
Cooling
Heating 47
Heating 17
Cooling
Heating 47
Heating 17
Cooling
Cooling
Heating
Heating
*1
*1
*2
*1
*1
*2
Outdoor model
Indoor type
Btu/h
Btu/h
Btu/h
W
W
W
EER
SEER
HSPF IV(V)
COP
External finish
Power supply
V, phase, Hz
Max. fuse size (time delay)
A
Min. circuit ampacity
A
Fan motor
F.L.A
Model
Winding resistance
Ω
(at 68 ºF)
Compressor
R.L.A
L.R.A
Refrigerant control
Sound level
dB(A)
Defrost method
W
in.
Dimensions
D
in.
H
in.
Weight
lb.
Remote controller
Control voltage (by built-in transformer)
Refrigerant piping
Liquid
in.
Valve size
Gas
in.
Indoor
Connection method
Outdoor
Refrigerant charge (R410A)
lb.
Refrigeration oil (Model)
oz.
MXZ-3C30NAHZ
Non-Duct (09+09+12)
Duct (09+09+12)
28,400
27,400
28,600
27,600
18,000
17,000
2,272
2,661
2,096
2,187
1,991
1,993
12.5
10.3
18.0
16.0
11.0
9.8
4.00
3.70
Munsell 3.0Y 7.8/1.1
208/230, 1, 60
40
29.9
1.90
MNB33FBTMC-L
U-V 0.30 V-W 0.30 W-U 0.30
20
28.8
LEV
54.0 / 58.0
Reverse cycle
37-13/32
13
41-17/64
189
Wireless type
4
Not supplied (optional parts)
1/4
A: 1/2 B,C: 3/8
Flared
Flared
8 lb. 13 oz.
37.4 (FV50S)
NOTE : Test conditions are based on ARI 210/240.
Unit: °F
Mode
Cooling
Heating
Indoor air condition Outdoor air condition
Dry bulb Wet bulb Dry bulb Wet bulb
Test
*1: "A" Cooling steady state at rated compressor speed
"B-2" Cooling steady state at rated compressor speed
"B-1" Cooling steady state at minimum compressor speed
Low ambient cooling steady state at minimum compressor speed
Intermediate cooling steady state at intermediate compressor speed
*1: Standard rating-heating at rated compressor speed
*2: Low temperature heating at maximum compressor speed
Maximum temperature heating at minimum compressor speed
High temperature heating at minimum compressor speed
Frost accumulation at rated compressor speed
Frost accumulation at intermediate compressor speed
80
80
80
80
80
70
70
70
70
70
70
67
67
67
67
67
60
60
60
60
60
60
95
82
82
67
87
47
17
62
47
35
35
(75)
(65)
(65)
(53.5)
(69)
43
15
56.5
43
33
33
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-5
1. SPECIFICATIONS
MXZ-4C36NAHZ
Indoor type
Rated*1
Cooling
Capacity
BTU/h
Rated power consumption*1
W
EER
BTU/Wh
SEER
BTU/Wh
Capacity Rated 47°F*1
BTU/h
Capacity Max. 17°F*2
BTU/h
Capacity Max. 5°F
BTU/h
Rated power consumption 47°F*1
W
COP 47°F*1
BTU/Wh
HSPF IV(V)
BTU/Wh
Connectable indoor units (Max.)
Max. Connectable Capacity
Power supply
Breaker Size / Max. fuse size
Min. circuit ampacity
Sound level (Cool/Heat)
dB
External finish
Refrigerant control
Compressor
Model
Motor output
kW
Starting method
Heat exchanger
Fan (drive) × No.
Fan
Fan motor output
kW
Airflow
m³/min (CFM)
W
in (mm)
Dimensions
D
in (mm)
(H × W × D)
H
in (mm)
Weight
lb (kg)
Refrigerant
Charge
lb (kg)
Oil/ Model
oz (L)
High pressure protection
Protection deCompressor protection
vices
Fan motor protection
(cool)
Guaranteed operation range
(heat)
Total Piping length (Max.)
ft (m)
Farthest
ft (m)
Max. Height difference
ft (m)
Chargeless length
ft (m)
Liquid
in (mm)
Piping diameter
Gas
in (mm)
Connection meth- Indoor side
od
Outdoor side
Heating
Standard performance
OUTDOOR UNIT
REFRIGERANT PIPING
MXZ-4C36NAHZ
Outdoor model
Item
Ducted
Mix
36,000
36,000
2,875
3,180
12.52
11.32
17.5
15.8
45,000
45,000
45,000
45,000
45,000
45,000
3,795
4,250
3.48
3.10
10.7/8.9
10.1/8.5
4
46,000
1 Phase 208 / 230 V, 60 Hz
50 A/ 52 A
42 A
49/ 53
Munsell 3Y 7.8/ 1.1
Linear Expansion Valve
Hermetic
ANB33FJSMT
2.8
Inverter
Plate fin coil
Propeller fan × 2
0.06 + 0.06
110 (3885)
41-11/32 (1050)
13+1 (330+25)
52-11/16 (1338)
276 (125)
R410A
10 lbs. 9 oz.(4.8)
73 (2.3)
HP switch
Compressor thermo, Overcurrent detection
Overheating / Voltage protection
D.B 23 to 115°F . [ D.B.−5 to 46°C ] *3
D.B. −13 to 70°F [D.B. −25 to 21°C ]
492 (150)
262 (80)
164 (50)*4
0
3/8 (9.52)
5/8 (15.88)
Flared
Flared
Non-Ducted
36,000
2,570
14.01
19.1
45,000
45,000
45,000
3,340
3.95
11.3/9.2
*1 Rating conditions
Cooling Indoor : D.B. 80°F/ W.B. 67 °F [D.B.26.7°C/ W.B. 19.4°C]
Outdoor : D.B. 95°F [D.B. 35.0°C]
Heating Indoor : D.B. 70°F [D.B. 21.1°C]
Outdoor : D.B. 47°F/ W.B. 43°F [D.B. 8.3°C/ W.B. 6.1°C]
*2 Conditions
Heating Indoor : D.B. 70°F [D.B. 21.1°C]
Outdoor : D.B. 17°F/ W.B. 15°F [D.B. −8.3°C/ W.B. −9.4°C]
*3 D.B. 5 to 115°F [D.B. −15 to 46°C], when an optional Air Outlet Guide is installed.
*4 131 ft [40 m], in case of installing outdoor unit lower than indoor unit.
Note: Refer to the indoor unit's service manual for the indoor units specifications.
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-6
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
MXZ-5C42NAHZ
Cooling
Capacity
Rated power consumption*1
EER
SEER
Capacity Rated 47°F*1
Capacity Max. 17°F*2
Capacity Max. 5°F
Rated power consumption 47°F*1
COP 47°F*1
HSPF IV(V)
Connectable indoor units (Max.)
Max. Connectable Capacity
Power supply
Breaker Size / Max. fuse size
Min. circuit ampacity
Sound level (Cool/Heat)
External finish
Refrigerant control
Compressor
Model
Motor output
Starting method
Heat exchanger
Fan (drive) × No.
Fan motor output
Fan
Heating
Standard performance
OUTDOOR UNIT
Indoor type
Rated*1
Airflow
Dimensions
(H × W × D)
Weight
Refrigerant
REFRIGERANT PIPING
MXZ-5C42NAHZ
Outdoor model
Item
W
D
H
BTU/h
W
BTU/Wh
BTU/Wh
BTU/h
BTU/h
BTU/h
W
BTU/Wh
BTU/Wh
dB
kW
kW
m³/min
(CFM)
in (mm)
in (mm)
in (mm)
lb (kg)
Charge
lb (kg)
Oil/ Model
oz (L)
High pressure protection
Protection deCompressor protection
vices
Fan motor protection
(cool)
Guaranteed operation range
(heat)
Total Piping length (Max.)
ft (m)
Farthest
ft (m)
Max. Height difference
ft (m)
Chargeless length
ft (m)
Liquid
in (mm)
Piping diameter
Gas
in (mm)
Indoor side
Connection
method
Outdoor side
42,000
3,130
13.42
19.0
48,000
48,000
48,000
3,430
4.10
11.0/9.1
42,000
3,510
11.97
17.0
48,000
48,000
48,000
3,890
3.62
10.6/9.0
5
54,000
1 Phase 208 / 230 V, 60 Hz
50 A/ 52 A
42 A
50/ 54
Munsell 3Y 7.8/ 1.1
Linear Expansion Valve
Hermetic
ANB33FJSMT
3.0
Inverter
Plate fin coil
Propeller fan × 2
0.06 + 0.06
42,000
3,890
10.80
15.0
48,000
48,000
48,000
4,350
3.23
10.1/8.8
110 (3885)
41-11/32 (1050)
13+1 (330+25)
52-11/16 (1338)
276 (125)
R410A
10 lbs. 9 oz.(4.8)
73 (2.3)
HP switch
Compressor thermo, Overcurrent detection
Overheating / Voltage protection
D.B 23 to 115°F . [ D.B.−5 to 46°C ] *3
D.B. −13 to 70°F [D.B. −25 to 21°C ]
492 (150)
262 (80)
164 (50)*4
0
3/8 (9.52)
5/8 (15.88)
Flared
Flared
*1 Rating conditions
Cooling Indoor : D.B. 80°F/ W.B. 67 °F [D.B.26.7°C/ W.B. 19.4°C]
Outdoor : D.B. 95°F [D.B. 35.0°C]
Heating Indoor : D.B. 70°F [D.B. 21.1°C]
Outdoor : D.B. 47°F/ W.B. 43°F [D.B. 8.3°C/ W.B. 6.1°C]
*2 Conditions
Heating Indoor : D.B. 70°F [D.B. 21.1°C]
Outdoor : D.B. 17°F/ W.B. 15°F [D.B. −8.3°C/ W.B. −9.4°C]
*3 D.B. 5 to 115°F [D.B. −15 to 46°C], when an optional Air Outlet Guide is installed.
*4 131 ft [40 m], in case of installing outdoor unit lower than indoor unit.
Note: Refer to the indoor unit's service manual for the indoor units specifications.
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-7
1. SPECIFICATIONS
MXZ-8C48NAHZ
Outdoor model
OUTDOOR UNIT
Cooling
Capacity Rated*1
Rated power consumption*1
EER
SEER
Capacity Rated 47°F*1
Capacity 17°F*2
Capacity 5°F
Rated power consumption 47°F*1
COP 47°F*1
HSPF IV(V)
Connectable indoor units (Max.)
Max. Connectable Capacity
Power supply
Breaker Size / Max. fuse size
Min. circuit ampacity
Sound level (Cool/Heat)
External finish
Refrigerant control
Compressor
Model
Motor output
Starting method
Heat exchanger
Fan (drive) × No.
Fan motor output
Fan
Airflow
Heating
Standard performance
Item
Dimensions
(H × W × D)
REFRIGERANT PIPING
Weight
Refrigerant
W
D
H
Indoor type
BTU/h
W
BTU/Wh
BTU/Wh
BTU/h
BTU/h
BTU/h
W
BTU/Wh
BTU/Wh
Non-Ducted
48,000
4,000
12.00
18.9
54,000
54,000
54,000
4,220
3.75
11.0/9.2
dB
kW
kW
m³/min
(CFM)
in (mm)
in (mm)
in (mm)
lb (kg)
Charge
lb (kg)
Oil / Model
oz (L)
High pressure protection
Protection
Compressor protection
devices
Fan motor protection
(cool)
Guaranteed operation range
(heat)
Total Piping length (Max.)
ft (m)
Farthest
ft (m)
Max. Height difference
ft (m)
Chargeless length
ft (m)
Liquid
in (mm)
Piping diameter
Gas
in (mm)
Indoor side
Connection
method
Outdoor side
MXZ-8C48NAHZ
Mix
Ducted
48,000
48,000
4,525
5,050
10.61
9.50
16.8
14.7
54,000
54,000
54,000
54,000
54,000
54,000
4,605
4,990
3.44
3.17
10.5/9.2
10.0/9.2
8
62,000
1 Phase 208 / 230 V, 60 Hz
50 A/ 52 A
42 A
51/ 54
Munsell 3Y 7.8 / 1.1
Linear Expansion Valve
Hermetic
ANB33FJSMT
3.4
Inverter
Plate fin coil
Propeller fan × 2
0.06 + 0.06
110 (3885)
41-11/32 (1050)
13+1 (330+25)
52-11/16 (1338)
276 (125)
R410A
10 lbs. 9 oz. (4.8 )
73 (2.3)
HP switch
Compressor thermo, Over current detection
Overheating / Voltage protection
D.B. 23 to 115°F [ D.B. −5 to 46°C]*3
D.B. −13 to 70°F [D.B. −25 to 21°C]
492 (150)
262 (80)
164 (50)*4
0
3/8 (9.52)
5/8 (15.88)
Flared
Flared
*1 Rating conditions
Cooling Indoor : D.B. 80°F/ W.B. 67°F [D.B. 26.7°C/ W.B. 19.4°C]
Outdoor : D.B. 95°F [D.B. 35.0°C]
Heating Indoor : D.B. 70°F [D.B. 21.1°C]
Outdoor : D.B. 47°F/ W.B. 43°F [D.B. 8.3°C / W.B. 6.1°C]
*2 Conditions
Heating Indoor : D.B. 70°F [D.B. 21.1°C]
Outdoor : D.B. 17°F/ W.B. 15°F [D.B. −8.3°C/ W.B. −9.4°C]
*3 D.B. 5 to 115°F [D.B. −15 to 46°C], when an optional Air Outlet Guide is installed.
*4 131 ft [40 m], in case of installing outdoor unit lower than indoor unit.
Note: Refer to the indoor unit's service manual for the indoor units specifications.
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-8
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
Branch Box
PAC-MKA50BC PAC-MKA30BC
Model name
Connectable number of indoor units
Power supply
Input
Running current
External finish
Width
Depth
Dimensions
Height
Weight
Branch (indoor side)*
Piping
connection
(Flare)
Main (outdoor side)
PAC-MKA50BC
Maximum 5
kW
A
Liquid
in (mm)
in (mm)
in (mm)
lb (kg)
in (mm)
Gas
in (mm)
Liquid
Gas
in (mm)
in (mm)
PAC-MKA30BC
Maximum 3
Single phase, 208/230 V, 60 Hz
0.003
0.05
Galvanized sheets
17-23/32 (450)
11-1/32 (280)
6-11/16 (170)
15 (6.7 )
16 (7.4)
[1/4(6.35) × 5 {A,B,C,D,E}
[1/4(6.35) × 3 {A,B,C}
[ 3/8(9.52) × 4 {A,B,C,D},
[ 1/2(12.7) × 1{E}
[3/8(9.52) × 3 {A,B,C}
[3/8 (9.52)
[ 5/8 (15.88)
*The piping connection size differs according to the type and capacity of indoor units. Match the piping connection size
for indoor and branch box. If the piping connection size of branch box does not match the piping connection size of
indoor units, use optional different-diameter (deformed) joints to the branch box side. (Connect deformed joint directly
to the branch box side.)
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-9
1. SPECIFICATIONS
Efficiency Ratings
Model
MXZ-2C20NAHZ
MXZ-3C24NAHZ
MXZ-3C30NAHZ
MXZ-4C36NAHZ
MXZ-5C42NAHZ
MXZ-8C48NAHZ
Configuration
SEER
EER
HSPF
COP
@ 47° F
COP
@ 17° F
Non-Ducted
17.0
13.50
9.8
4.00
2.77
Ducted
15.0
11.00
9.5
3.69
2.53
Non-Ducted
19.0
13.50
10.0
4.25
2.53
Ducted
15.5
10.00
9.0
3.80
2.51
Non-Ducted
18.0
12.50
11.0
4.00
2.65
Ducted
16.0
10.30
9.8
3.70
2.50
Non-Ducted
19.1
14.01
11.3
3.95
2.85
Ducted
15.8
11.32
10.1
3.10
2.30
Non-Ducted
19.0
13.42
11.0
4.10
2.85
Ducted
15.0
10.80
10.1
3.23
2.50
Non-Ducted
18.9
10.00
11.0
3.75
2.70
Ducted
14.7
9.5
10
3.17
2.40
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-10
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
1-1. Compatibility Table
OUTDOOR UNIT
INDOOR UNIT
MSZ-FE09NA
2C20NAHZ 3C24NAHZ 3C30NAHZ 4C36NAHZ 5C42NAHZ 8C48NAHZ
○
MSZ-FE12NA
Wall
Mounted
M-Series
○
○
○
○
○
○
○
○
○
○
MSZ-FH09NA
○
○
○
○
○
○
MSZ-FH12NA
○
○
○
○
○
○
MSZ-FH15NA
○
○
○
○
○
○
MSZ-FH18NA
○
○
○
○
○
MSZ-GE06NA
○
○
○
○
○
○
MSZ-GE09NA
○
○
○
○
○
○
MSZ-GE12NA
○
○
○
○
○
○
MSZ-GE15NA
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
MSZ-GE18NA
MSZ-GE24NA
Floor
Standing
4-way
Cassette
S-Series
Ceiling
Conceald
MFZ-KA09NA
○
○
○
○
○
○
MFZ-KA12NA
○
○
○
○
○
○
○
○
○
○
○
MFZ-KA18NA
SLZ-KA09NA
○
○
○
○
○
○
SLZ-KA12NA
○
○
○
○
○
○
○
○
○
○
○
SLZ-KA18NA
SEZ-KD09NA
○
○
○
○
○
○
SEZ-KD12NA
○
○
○
○
○
○
SEZ-KD15NA
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
PEAD-A30AA
○
○
○
PEAD-A36AA
○
○
○
SEZ-KD18NA
PLA-A12BA
4-way
Cassette
P-Series
Ceiling
Suspended
Ceiling
Conceald
PLA-A18BA
PLA-A24BA
PLA-A30BA
PLA-A36BA
PCA-A24KA
○
PEAD-A24AA
○
MVZ-A12AA4
○
○
○
○
○
○
○
○
○
○
○
○
○
○
MVZ-A30AA4
○
○
○
MVZ-A36AA4
○
○
○
MVZ-A18AA4
Vertical
Multi Position MVZ-A24AA4
○
Notes:
• Minimum of two Indoor Units must be connected to the MXZ-2C20,3C24,3C30,4C36,5C42,8C48NAHZ.
• Minimum installed capacity cannot be less than 12,000 Btu/h.
• System can operate with only one Indoor Unit turned on.
• May connect to any style indoor unit or combination.
• Information provided at 208/230V.
• Refer to the MXZ Technical & Service Manual for detailed specifications and additional information per Indoor Unit
Combination.
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-11
1. SPECIFICATIONS
1-2. Cooling and Heating Capacity and Characteristics
MXZ-4C36NAHZMXZ-5C42NAHZMXZ-8C48NAHZ
1-2-1. Method for obtaining system cooling and heating capacity:
To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up
the ratings of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the
standard capacity with the help of the tables on 1-4. STANDARD CAPACITY DIAGRAM.
(1) Capacity of indoor unit
M series
P series
SEZ
SLZ
MVZ
Model Number for Model 06 Model 09 Model 12 Model 15 Model 18 Model 24 Model 30 Model 36
indoor unit
14.0*1
17.2*3
─
─
6.0
9.0
12.0
22.5
2
15.0*
18.0*4
─
─
─
Model Capacity
12.0
18.0
24.0
30.0
35.0
─
─
─
─
[kBtu/h]
8.1
11.5
14.1
17.2
─
─
─
─
─
8.4
11.1
15.0
─
─
─
12.0
18.0
24.0
30.0
36.0
*1 The value is for MSZ-GE15NA.
*2 The value is for MSZ-FH15NA.
*3 The value is for MSZ-GE/FH18NA.
*4 The value is for MSZ-FE18NA or MFZ-KA18NA.
(2) Sample calculation
1 System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than that of
the outdoor unit)
• Outdoor unit MXZ-5C42NAHZ
• Indoor unit MSZ-GE09NA × 2 + MSZ-FH15NA ×2
2 According to the conditions in 1, the total capacity of the indoor unit will be: 9.0 × 2 + 15.0 × 2 = 48.0
3 The following figures are obtained from the 16.8 total capacity of indoor units, referring the standard capacity diagram in "4-3-3. MXZ-5C42NAHZ <cooling>" and "4-3-4. MXZ-5C42NAHZ <heating>". Capacity (kBTU/h)
Outdoor unit power consumption (kW)
Outdoor unit current (A)/ 230 V
Cooling
Heating
Cooling
Heating
Cooling
Heating
A 42.0
B 48.0
3.46
4.37
15.26
19.31
1-2-2. Method for obtaining the heating and cooling capacity of an indoor unit:
(1) The capacity of each indoor unit (kW) = the capacity A (or B ) X
model capacity
total model capacity of all indoor units
(2) Sample calculation (using the system described above in 4-1-1. (2) ):
During heating:
During cooling:
• The total model capacity of the indoor unit is:
9.0 × 2 + 15.0 × 2 = 48.0 kBTU/h
Therefore, the capacity of MSZ-GE09NA and
MSZ-FH15NA will be calculated as follows by
using the formula in 4-1-2. (1):
9.0
= 7.88 kBTU/h
48.0
15.0
Model 15 = 42.0 ×
= 13.13 kBTU/h
48.0
Model 09 = 42.0 ×
• The total model capacity of indoor unit is:
10.9 × 2 + 18.0 × 2 = 57.8 kBTU/h
Therefore, the capacity of MSZ-GE09NA and MSZFH15NA will be calculated as follows by using the
formula in 4-1-2. (1):
10.9
Model 25 = 48.0 × 57.8= 9.05 kBTU/h
18.0
Model 50 = 48.0 × 57.8 = 14.95 kBTU/h
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-12
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
1-3. Standard Operation Data (Reference Data)
MXZ-4C36NAHZMXZ-5C42NAHZMXZ-8C48NAHZ
Outdoor unit model
Operation
MXZ-4C36NAHZ
Indoor
Ambient
temperature Outdoor
Indoor unit
Operating
conditions
No. of
connected
units
70°F / 60°F
80°F / 67°F
70°F / 60°F
80°F / 67°F
70°F / 60°F
95°F / 75°F
47°F / 43°F
95°F / 75°F
47°F / 43°F
95°F / 75°F
47°F / 43°F
To t a l p i p e
length
Fan speed
Amount of refrigerant
4
4
4
4
4
4
Unit
—
09 × 4
09 × 2 + 12 ×2
12 × 4
9.84 (3)
9.84 (3)
9.84 (3)
14.76 (4.5)
14.76 (4.5)
14.76 (4.5)
68.90 (21)
68.90 (21)
68.90 (21)
—
Hi
Hi
Hi
lb oz
(kg)
17 lb 7 oz (7.9)
17 lb 7 oz (7.9)
17 lb 7 oz (7.9)
Main pipe
Branch pipe
MXZ-8C48NAHZ
80°F / 67°F
No. of units
in operation
Model
Piping
Outdoor
unit
DB/WB
MXZ-5C42NAHZ
m
Electric current
A
Voltage
V
Compressor frequency
Hz
59
74
70
80
86
91
14.1
18.7
17.2
230
19.1
22.1
230
21.9
230
LEV
opening
Indoor unit
Pulse
112
128
129
128
112
132
Pressure
High pressure/Low pressure
MPa
2.57/ 0.98
2.78/ 0.64
2.72/ 0.80
2.80/ 0.56
2.83/ 0.77
2.82/ 0.55
Discharge
62.1
66.4
64.8
63.2
69.8
65.1
Heat
exchanger
outlet
38.2
2.6
38.8
2.0
40.9
1.3
10.3
2.3
9.7
1.6
8.4
0.8
8.4
1.1
7.4
0.4
5.8
−0.8
LEV inlet
21.1
39.7
28.7
37.9
21.7
37.1
Heat
exchanger
inlet
12.3
59.4
9.8
55.7
8.6
57.0
Temp.
of each
section
Outdoor
unit
Accumulator
inlet
Compressor
inlet
Indoor unit
°C
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-13
1. SPECIFICATIONS
1-4. Standard Capacity Diagram
Before calculating the sum of total capacity of indoor units, please convert the value into the kW model capacity following the
formula on
"1-2-1. Method for obtaining system cooling and heating capacity".
1-4-1. MXZ-4C36NAHZ <cooling>
Capacity (kBTU/h)
40
35
30
25
20
15
10
5
0
6
12
18
24
30
36
42
48
54
48
54
Total capacity of indoor units (kBTU/h)
4.0
Input (kBTU/h)
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
6
12
18
24
30
36
42
Total capacity of indoor units (kBTU/h)
18
Current (A)
16
14
230 V
12
208 V
10
8
6
4
2
0
6
12
18
24
30
36
42
48
54
Total capacity of indoor units (kBTU/h)
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-14
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
1-4-2. MXZ-4C36NAHZ <heating>
Capacity (kBTU/h)
50
45
40
35
30
25
20
15
10
5
0
6
12
18
24
30
36
42
48
54
48
54
Total capacity of indoor units (kBTU/h)
5.0
Input (kBTU/h)
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
6
12
18
24
30
36
42
Total capacity of indoor units (kBTU/h)
25
230 V
Current (A)
20
208 V
15
10
5
0
6
12
18
24
30
36
42
48
54
Total capacity of indoor units (kBTU/h)
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-15
1. SPECIFICATIONS
1-4-3. MXZ-5C42NAHZ <cooling>
Capacity (kBTU/h)
45.0
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
6
12
18
24
30
36
42
48
54
60
54
60
Total capacity of indoor units (kBTU/h)
4.5
Input (kBTU/h)
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
6
12
18
24
30
36
42
48
Total capacity of indoor units (kBTU/h)
25.0
208 V
Current (A)
20.0
230 V
15.0
10.0
5.0
0.0
6
12
18
24
30
36
42
48
54
60
Total capacity of indoor units (kBTU/h)
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-16
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
1-4-4. MXZ-5C42NAHZ <heating>
Capacity (kBTU/h)
60.0
50.0
40.0
30.0
20.0
10.0
0.0
6
12
18
24
30
36
42
48
54
60
54
60
Total capacity of indoor units (kBTU/h)
6.0
Input (kBTU/h)
5.0
4.0
3.0
2.0
1.0
0.0
6
12
18
24
30
36
42
48
Total capacity of indoor units (kBTU/h)
Current (A)
30.0
25.0
208 V
20.0
230 V
15.0
10.0
5.0
0.0
6
12
18
24
30
36
42
48
54
60
Total capacity of indoor units (kBTU/h)
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-17
1. SPECIFICATIONS
1-4-5. MXZ-8C48NAHZ <cooling>
Capacity (kBTU/h)
60.0
50.0
40.0
30.0
20.0
10.0
0.0
6
12
18
24
30
36
42
48
54
60
66
54
60
66
Total capacity of indoor units (kBTU/h)
6.0
Input (kBTU/h)
5.0
4.0
3.0
2.0
1.0
0.0
6
12
18
24
30
36
42
48
Total capacity of indoor units (kBTU/h)
30.0
Current (A)
25.0
208 V
230 V
20.0
15.0
10.0
5.0
0.0 6
12
18
24
30
36
42
48
54
60
66
Total capacity of indoor units (kBTU/h)
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-18
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
1-4-6. MXZ-8C48NAHZ <heating>
Capacity (kBTU/h)
60.0
50.0
40.0
30.0
20.0
10.0
0.0
6
12
18
24
30
36
42
48
54
60
66
54
60
66
Total capacity of indoor units (kBTU/h)
6.0
Input (kBTU/h)
5.0
4.0
3.0
2.0
1.0
0.0
6
12
18
24
30
36
42
48
Total capacity of indoor units (kBTU/h)
Current (A)
30.0
25.0
208 V
20.0
230 V
15.0
10.0
5.0
0.0 6
12
18
24
30
36
42
48
54
60
66
Total capacity of indoor units (kBTU/h)
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-19
2. EXTERNAL DIMENSIONS
MXZ-2C20NAHZ
Unit: mm <in>
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-20
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
2. EXTERNAL DIMENSIONS
MXZ-3C24NAHZMXZ-3C30NAHZ
Unit: mm <in>
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-21
Min. 150mm<5-29/32>
Service space
15 <19/32>
Min.
Front trunking hole
(Knockout)
Conduit hole
({37<1-15/32>Knockout)
60 <2-3/8>
Front piping hole
(Knockout)
92 <3-5/8>
75 <2-15/16>
{92
>
<3-5/8
53 <2-3/32>
92 <3-5/8>
29 <1-5/32>
55 <2-3/16>
{92
<3-5/8>
Right piping hole
(Knockout)
Conduit hole
( {24<15/16>Knockout)
55 <2-3/16>
Piping Knockout Hole Details
*1.......Indication of STOP VALVE connection location.
60
<2-3/8>
5
<3/16>
30 <1-3/16>
Max.
Min.
Right trunking hole
(Knockout)
Conduit hole
( {37<1-15/32>Knockout)
60 <2-3/8>
Conduit hole
( { 24<15/16>Knockout)
500
<19-11/16>
Handle for
moving
500
<19-11/16>
Min.
1……Refrigerant GAS pipe connection (FLARE){15.88 (5/8F)
2……Refrigerant LIQUID pipe connection (FLARE){9.52 (3/8F)
Example of Notes
Min. 1000mm<39-3/8>
Min. 15mm<19/32>
Rear trunking hole
(Knockout)
55 <2-3/16>
FOUNDATION
5<3/16>
60 <2-3/8>
73 <2-7/8>
Min. 15mm<19/32>
92
<3-5/8>
<Foundation bolt height>
75 <2-15/16>
92 <3-5/8>
Rear piping hole
(Knockout)
{ 92
8>
<3-5/
Conduit hole
( { 37<1-15/32>Knockout)
1/2 inch Conduit
attachment
{ 22.2<7/8>
Scale 1:5
101.5 <4>
24 <15/16>
110 <4-11/32>
45 <1-25/32>
1 inch Conduit
attachment
mm<inch>
{ 34.5<1-23/64>
60 <2-3/8>
330 <13>
Handle for moving
Side Air Intake
When installing the conduit.
Set the attachment to the
inner side of each panel.
Side Air Intake
Handle for
moving
Conduit hole
( { 24<15/16>Knockout)
60 <2-3/8>
Rear Air Intake
4 PIPING-WIRING DIRECTIONS
Piping and wiring connections
can be made from 4 directions:
FRONT, Right, Rear and Below.
5<3/16>
FREE
3 FOUNDATION BOLTS
60 <2-3/8>
Min.
Please secure the unit firmly
with 4 foundation (M10<W3/8>) bolts.
(Bolts and washers must be
purchased locally.)
5<3/16>
150
<5-29/32>
2 SERVICE SPACE
55 <2-3/16>
1338 <52-11/16>
24.7 <31/32>
632 <24-7/8>
369 <14-17/32>
Dimensions of space needed
for service access are
shown in the below diagram.
73 <2-7/8>
26 <1-1/32>
55 <2-3/16>
27 <1-1/16>
27 <1-1/16>
26 <1-1/32>
73 <2-7/8>
26 <1-1/32>
160
<6-5/16>
362 <14-1/4>
225
<8-27/32>
160
<6-5/16>
160
<6-5/16>
42 <1-21/32>
56 <2-7/32>
Drain hole
(5-{33<1-5/16>)
For the
branch box
power supply
For the
transmission line
Bottom piping hole
(Knockout)
2
1
Handle for moving
Service panel
Ground for the
branch box
power supply
For concentration
control
Rear piping cover
Front piping cover
Air intake
Ground for the transmission line
Ground for concentration control
For the
power supply
Terminal connection
From left to right
53 <2-3/32>
33.2 <1-5/16>
0
56 <2-7/32>
2-U Shaped notched holes
(Foundation Bolt M10<W3/8>)
2-12×36 Oval holes
(Foundation Bolt M10<W3/8>)
225
<8-27/32>
81 <3-3/16>
Ground for the power supply
("GR"marking position)
1050 <41-11/32>
Air Discharge
Installation Feet
70
<2-3/4>
Rear Air Intake
417 <16-13/32>
600
<23-5/8>
MXZ-4C36NAHZMXZ-5C42NAHZMXZ-8C48NAHZ
27 <1-1/16>
86 <3-3/8>
25 <1>
26 <1-1/32>
154
<6-1/16>
136
<5-11/32>
19 <3/4>
370 <14-9/16>
28 <1-3/32>
426 <16-25/32> *1
1 FREE SPACE (Around the unit)
1067 <42>
H2i-MXZ-22
510 <20-3/32> *1
The diagram below shows a basic example.
Explantion of particular details are
given in the installation manuals etc.
2. EXTERNAL DIMENSIONS
Unit: mm <in>
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
2. EXTERNAL DIMENSIONS
Branch Box
PAC-MKA50BC
Unit: mm <in>
When installing the conduit.
Set the attachment to the
inner side of each panel.
58 <2-9/32>
SUSPENSION BOLT PITCH
320 <12-5/8>
28
<1-3/32>
48 <1-7/8>
24
<15/16>
129 <5-3/32>
48 <1-7/8>
24
<15/16>
5- { 22<7/8>
1/2 inch Conduit
attachment
12 <1/2>
17 <21/32>
15 <19/32>
12 <15/32>
REFRIGERANT PIPE FLARED CONNECTION
TO OUTDOOR UNIT
A
B
C
D
E
LIQUID PIPE 1/4F 1/4F 1/4F 1/4F 1/4F 3/8F
GAS PIPE
3/8F 3/8F 3/8F 3/8F 1/2F 5/8F
24 <1>
402 <15-7/8>
SUSPENSION BOLT : W3/8(M10)
SUSPENSION BOLT PITCH
105
<4-1/8>
20
<25/32>
66 <2-19/32>
91
<3-19/32>
B
C
A
B
A
TERMINAL BLOCK
TO INDOOR UNIT
5-ELECTRIC WIRE INLET
25
25
25
25
<1>
<1>
<1>
<1>
70
70
70
70
<2-3/4> <2-3/4> <2-3/4> <2-3/4>
TB3E
TB2B
25
<1>
CONTROL COVER
TO OUTDOOR UNIT
SERVICE PANEL
(for LEV,THERMISTOR)
TB3D
C
D
83
87
70
<3-9/32> <3-7/16> <2-3/4>
TB3B
D
E
TERMINAL BLOCK
TO M-NET UNIT
40 <1-17/32>
280 <11-1/32 >
TB3C
E
TO INDOOR UNIT
96
<3-25/32>
TB3A
65
<2-9/16>
67 <2-9/16>
73
<2-7/8>
111
<4-3/8>
450 <17-23/32>
TB5
170 <6-11/16>
46 <1-13/16>
(1:2)
TERMINAL BLOCK
TO OUTDOOR UNIT
CONDUIT PLATE
PAC-MKA30BC
When installing the conduit.
Set the attachment to the
inner side of each panel.
SUSPENSION BOLT PITCH
320 <12-5/8>
58 <2-9/32>
5- { 22<7/8>
129 <5-3/32>
48 <1-7/8>
1/2 inch Conduit
attachment
15 <19/32>
12 <15/32>
12 <1/2>
48 <1-7/8>
24
<15/16>
105
<4-1/8>
24 <1>
TO OUTDOOR UNIT
3/8F
5/8F
24
<15/16>
REFRIGERANT PIPE FLARED CONNECTION
A
B
C
LIQUID PIPE 1/4F 1/4F 1/4F
GAS PIPE
3/8F 3/8F 3/8F
28
<1-3/32>
66 <2-19/32>
17 <21/32>
SUSPENSION BOLT : W3/8(M10)
SUSPENSION BOLT PITCH
402 <15-7/8>
20
<25/32>
(1:2)
91 <3-19/32>
TO INDOOR UNIT
25
<1>
B
A
25
<1>
70
70
<2-3/4> <2-3/4>
5-ELECTRIC WIRE INLET
A
TERMINAL BLOCK
TO INDOOR UNIT
TB3C
25
<1>
B
TERMINAL BLOCK
TO M-NET UNIT
40 <1-17/32>
TB3B
CAP
C
280 <11-1/32>
87
70
<3-7/16> <2-3/4>
TB3A
C
83
<3-9/32>
TB2B
65
<2-9/16>
CAP
96
<3-25/32>
111
<4-3/8>
73
<2-7/8>
208 <8-3/16>
TB5
170 <6-11/16>
46 <1-13/16>
450 <17-23/32>
TO OUTDOOR UNIT
SERVICE PANEL
(for LEV.THERMISTOR)
CONTROL COVER
CONDUIT PLATE
TERMINAL BLOCK
TO OUTDOOR UNIT
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-23
4. ELECTRICAL WIRING DIAGRAMS
MXZ-2C20NAHZ
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-24
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
4. ELECTRICAL WIRING DIAGRAMS
MXZ-3C24NAHZMXZ-3C30NAHZ
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-25
3
CNDC
(PNK)
S
M2
1
CNF2
7(WHT)
RED
YLW
2
POWER SUPPLY
~208 / 230V 60Hz
TO BRANCH BOX
B2
B1
TB1B
GR
L2
L1
TB1
FUSE2
FUSE1
FOR CENTRALIZED
CONTROL
DC 30V(Non-polar)
S
M2
M1 YLW
TB7
t゜
t゜
t゜
1 3
63LS
(BLU)
2
1 2
CN4
(WHT)
SV1
3 SV1 1
(GRY)
W V U
W
GRN/YLW
BLU
RED
SV2
3 SV2 1
(BLU)
MC
MS
3~
V
1 3
63H
(YLW)
U
t゜
7
+
+
-
DCL
3
2
~
~
IGBT
2
1
CN4
(WHT)
1 2
CNDC
(PNK)3
DCL2 DCL1
P2
N2
CN2
(RED)
2
M
M
5
2
EI
E4
1
3
2
52C
52C
NI
CN52C
3(RED)
P. B.
3
1
3
1
2
MXZ-8C48NAHZ
MXZ-5C42NAHZ
MXZ-4C36NAHZ
MODELS
ON
OFF
ON
OFF
ON
OFF
56
56
56
SW2
ON
OFF
ON
OFF
ON
OFF
123456
123456
123456
SW4
ON
OFF
ON
OFF
ON
OFF
12
12
12
SW8
The black square( )indicates a switch position.
BLK
2
BLK
2
※1 MODEL SELECTION
LI
4
LED2
1
4
CN2
(WHT)
BLK TB1
CN1
(WHT)
5 3 1
M-NET P.B.
CN102
(WHT)
1
4
LED1
※1
※1
SW8 SW2
※1
SW6
SW4 SW3 SW7
SW1
SW5
is the switch position.
SWU2 SWU1 SW9
CNS1 CNS2 CN41
CN40
(YLW)
(RED)
(WHT) (WHT)
1 4
1
2 1 2 1 4
CN51
(WHT)
1
1
5
CNLVB
(RED)
LEV-B
LEV-A
3 1
5
CNLVA
CN52C (WHT)
(RED)
1 3
3 1
LED3
3 1
3 SS 1 2 CNAC
(WHT)
(RED)
TH8
1
7
BH
F2
F1
7
1
CN3D CN3S CN3N
(WHT)
(RED)
(BLU)
CN2
1 (RED) 7
1 3 1
4 1 2 2 1 1 2
63HS TH7/6 TH3 TH4 TH2
(WHT)
(BLK)
(RED)
(WHT)
(WHT)
TRANS
3 21S4 1
(GRN)
21S4
3 52C 1
(BLK)
2
2
M1 RED
TB3
1
1
CNF1
7(WHT)
TO BRANCH BOX
CONNECTING WIRES
DC 30V(Non-polar)
MF2
MS
3~
1
X503
MF1
MS
3~
X505
t゜ t゜
WHT
X502
BLK
WHT
RED
X501
63H
WHT
X504
TH2
BLK
63LS 63HS TH7 TH6 TH3 TH4
BLK
E3
CNAC2
(RED)
E2
H2i-MXZ-26
CNAC1
(WHT)
MULTI. B.
SYMBOL
NAME
3
21S4
2
52C
4
SV1
5
SV2
7
ー
6
ー
8
Always lit
Trouble
Serial transmission trouble
Compressor temperature trouble
High pressure trouble
Excessive refrigerant replenishment
Insufficient refrigerant trouble
Blocked valve in cooling mode
Four-way valve disconnection trouble
Drain pump trouble
Drain sensor trouble (THd)
Overcurrent trouble (Overload, compressor lock)
Fan controller trouble (Indoor unit)
Compressor overcurrent trouble
Inverter trouble
Overheat protection of heat sink
Power module trouble or Overcurrent trouble
Check code
Trouble
4400
Fan controller trouble (Outdoor)
5101
Air inlet sensor trouble (TH21) or
Compressor temperature sensor trouble (TH4)
5102
Liquid pipe temp.sensor trouble (TH22) or
Suction pipe temperature sensor trouble (TH6)
5103
Gas pipe temperature sensor trouble (TH23)
5105
Piping temperature sensor trouble (TH3)
5106
Ambient temperature sensor trouble (TH7)
5109
HIC piping temperature sensor trouble (TH2)
5110
IGBT heat sink temperature sensor trouble
(TH8)
5201
High Pressure sensor trouble (63HS)
5202
Low Pressure sensor trouble (63LS)
Current sensor trouble
5300
6600
Dupricated unit address setting
NAME
Check code
Trouble
6602
Transmission error
(Transmission processor hardware error)
6603
Transmission error (Transmission route BUSY)
6606
Transmission and reception error (Communication
trouble with transmission processor)
6607
Transmission and reception error (No ACK error)
6608
Transmission and reception error
(No responsive frame error)
7100
Total capacity error
7101
Capacity code error
7102
Connecting unit number error
7105
Address set error
7111
Remote controller sensor trouble
7130
Combination error
〔Example〕
When the compressor and
SV1 are turned during cooling
operation.
1 23 45 67 8
Switch〈Function Selection〉
Switch〈Model Selection〉
Switch〈Function Selection〉
Switch〈Unit Address Selection, 1st digit〉
Switch〈Unit Address Selection, 2nd digit〉
Connector〈Branch box/Outdoor Transmission Line〉
Connector〈Centralized Control Transmission Line〉
Connector〈Base heater〉
Connector〈Connection For Option〉
Connector〈Connection For Option〉
Connector〈Connection For Option〉
Connector〈Connection For Option〉
LED〈Operation Inspection Display〉
LED〈Power Supply to Main Microcomputer〉
Fuse〈T6,3AL250V〉
Relay
M-NET Power Circuit Board
ConnectionTerminal〈Ground〉
NOTES:
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
! WARNING: When the main supply is turned off, the voltage [340 V] in the main capacitor will drop to 20 V in approx. 2
minutes (input voltage: 230 V). When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then
wait for at least 1 minute.
• Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual.
Do not replace the outdoor board without checking.
Cautions when servicing
• Use copper supply wires.
Caution for electrical work
1508
2502
2503
4100
4116
4210
4220
4230
4250
Check code
0403
1102
1302
1500
1501
● When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which
the fault has occurred.
Bit
1
Compressor
Indication operated
SYMBOL
SW7
Thermistor〈Suction Pipe〉
SW8
Thermistor〈Ambient〉
SW9
Thermistor〈Heat Sink〉
Electronic Expansion Valve
SWU1
Reactor
SWU2
Power Circuit Board
CNS1
Connection Terminal〈U/V/W-Phase〉
CNS2
Connection Terminal〈L-Phase〉
SS
Connection Terminal〈N-Phase〉
CN3D
CN3S
Connection Terminal〈Reactor〉
CN3N
Power Module
Connection Terminal〈Ground〉
CN51
Controller Circuit Board
LED1,LED2
LED3
Switch〈Display Selection〉
Switch〈Function Selection〉
F1,F2
X501~505
Switch〈Test Run〉
M-NET P.B.
Switch〈Model Selection〉
TB1
Switch〈Function Selection〉
Switch〈Function Selection〉
● During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
NAME
Terminal Block 〈Power Supply〉
TH6
Terminal Block 〈Branch Box〉
TH7
Terminal Block
TH8
〈Branch box/Outdoor Transmission Line〉LEV-A,LEV-B
TB7
Terminal Block
DCL
〈Centralized Control Transmission Line〉P.B.
U/V/W
FUSE1,FUSE2 Fuse 〈T20AL250V〉
LI
MC
Motor For Compressor
NI
MF1,MF2
Fan Motor
21S4
Solenoid Valve〈Four-Way Valve〉
DCL1,DCL2
IGBT
63H
High Pressure Switch
EI,E2,E3,E4
63HS
High Pressure Sensor
MULTI.B.
63LS
Low Pressure Sensor
SW1
Solenoid Valve〈Bypass Valve〉
SV1
SW2
Solenoid Valve〈Switching Valve〉
SV2
SW3
BH
Base heater
SW4
Thermistor〈Hic Pipe〉
TH2
SW5
Thermistor〈Outdoor Liquid Pipe〉
TH3
SW6
Thermistor〈Compressor〉
TH4
SYMBOL
TB1
TB1B
TB3
4. ELECTRICAL WIRING DIAGRAMS
MXZ-4C36NAHZMXZ-5C42NAHZMXZ-8C48NAHZ
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
4. ELECTRICAL WIRING DIAGRAMS
Branch Box
PAC-MKA50BCPAC-MKA30BC
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-27
5. REFRIGERANT SYSTEM DIAGRAMS
MXZ-2C20NAHZ
R.V.coil
OFF
ON
Refrigerant flow in heating
Refrigerant flow in cooling
Accumulator
Compressor
Oil separator
Compressor shell
temperature
thermistor RT62
Service port
High pressure switch
Union
Header(Gas)
Service port
Φ3/8
Indoor unit A
4-way valve
Stop valve
(with service port)
Header(Evaporator)
2-way
solenoid valve
Φ3/8
Outdoor
heat exchanger
Capillary tube
O.D.0.10 x I.D.0.02 x 39.37
(Ø2.5 x Ø0.6 x 1000)
Outdoor
heat exchanger
temperature
thermistor
RT68
Indoor unit B
Union
Φ1/4
Strainer
#100
Capillary tube
O.D.0.16 x I.D.0.11 x 3.94
(Ø4.0 x Ø2.8 x 100)
LEV-A
Indoor unit A
Strainer
#100
Φ1/4
Strainer
#100
Defrost
temperature
thermistor
RT61
Capillary tube
Stop valve
Ambient
temperature
thermistor
RT65
Distributor
LEV-B
Indoor unit B
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-28
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
5. REFRIGERANT SYSTEM DIAGRAMS
MXZ-3C24NAHZMXZ-3C30NAHZ
R. V. coil
OFF
ON
Refrigerant flow in heating
Refrigerant flow in cooling
Accumulator
Compressor
Service port
Compressor shell
temperature
thermistor RT62
Oil separator
High pressure switch
Union
Indoor unit A
Indoor unit B
Indoor unit C
Header(Gas)
Service port
Φ1/2
Φ3/8
4-way valve
Stop valve
(with service port)
Header(Evaporator)
2-way
solenoid valve
Φ3/8
Union Strainer
Φ1/4 #100
LEV-A
Strainer
#100
Strainer
#100
LEV-B
Strainer
Φ1/4 #100
LEV-C
Indoor unit B
Indoor unit C
Outdoor
heat exchanger
temperature
thermistor
RT68
Capillary tube
O.D.0.16 x I.D.0.11 x 3.94
(Ø4.0 x Ø2.8 x 100)
Indoor unit A
Φ1/4
Outdoor
heat exchanger
Capillary tube
O.D.0.10 x I.D.0.02 x 39.37
(Ø2.5 x Ø0.6 x 1000)
Defrost
temperature
thermistor
RT61
Capillary tube
Stop valve
Ambient
temperature
thermistor
RT65
Distributor
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-29
5. REFRIGERANT SYSTEM DIAGRAMS
MXZ-4C36NAHZMXZ-5C42NAHZMXZ-8C48NAHZ
Thermistor(TH-A–E)
<Gas pipe temperature>
4-Way Valve
(21S4)
Strainer
Room temperature
thermistor
(TH1 or RT11)
Ball valve
High pressure
Oil separator switch(63H)
Solenoid valve(SV1)
<Bypass>
Strainer
Check valve
Strainer
Capillary
tube
Thermistor(TH4)
<Compressor>
Solenoid valve(SV2)
<Switching>
LEV-A~E
(Linear expansion)
Service port
Strainer
Accumulator
Low pressure
sensor(63LS)
Thermistor(TH2)
<HIC pipe>
Stop valve
Strainer
Strainer
Compressor
Branch box
Thermistor(TH8)
<Heat Sink>
HIC
Strainer
LEV-B
LEV-A
Strainer
Refrigerant flow in cooling
Reftigerant flow in heating
Capillary
tube2
Indoor
Distributor
Thermistor(TH3)
<Outdoor Liquid pipe>
High
pressure
sensor(63HS)
Thermistor(TH6)
<Suction pipe>
Condenser /
evaporator
temperature
thermistor
Pipe temperature
thermistor
(TH2 or RT13)
Thermistor(TH7)
<Ambient>
Check valve
Service port
Outdoor unit
Unit: in (mm)
MXZ-4C36NAHZ
Outdoor unit MXZ-5C42NAHZ
MXZ-8C48NAHZ
Branch box
Capillary tube 1
(For return of oil from oil separator)
Capillary tube 2 behind LEV
(in cooling mode)
[0.098 o [0.031 o L(39-1/2)
([2.5 o [0.8 o L1000)
PAC-MKA50BC
([0.157 o [0.117 o L(5-1/8)) o 5
(([4 o [3.0 o L130) o 5)
PAC-MKA30BC
([0.157 o [0.117 o L(5-1/8)) o 3
(([4 o [3.0 o L130) o 3)
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-30
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
5. REFRIGERANT SYSTEM DIAGRAMS
Piping Connection Size
MXZ-4C36NAHZMXZ-5C42NAHZMXZ-8C48NAHZ
B
A
Liquid (mm)
9.52
Gas (mm)
15.88
The pipe connection size differs according to the type and capacity of
indoor units. Match the piping connection size of branch box with indoor
unit.
If the piping connection size of branch box does not match the piping
connection size of indoor unit, use optional different-diameter (deformed)
joints to the branch box side. (Connect deformed joint directly to the
branch box side.)
■ In case of using 1-branch box
Flare connection employed (No. brazing)
Branch box
A
B
B
B
B
B
■ In case of using 2-branch boxes
■ installation procedure (2 branch pipe (joint))
Refer to the installation manuals of
MSDD-50AR-E and MSDD-50BR-E.
2 branches pipe (joint)
: optional parts
A
A
Branch box #1
A
B
B
B
B
B
Branch box #2
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-31
6. CAPACITY CORRECTION CURVE BY TEMPERATURE
DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,
SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-32
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
7. CAPACITY CORRECTION TABLE BY TEMPERATURE
DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,
SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-33
8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH
MXZ-4C36NAHZMXZ-5C42NAHZMXZ-8C48NAHZ
(1) During cooling, obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and
the total in-use indoor capacity, and find the capacity ratio corresponding to the standard piping length from
Figure 3. Then multiply by the cooling capacity from Figure 1 to obtain the actual capacity.
(2) During heating, find the equivalent piping length, and find the capacity ratio corresponding to standard piping
length from Figure 3. Then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
Capacity Correction Factor
Fig. 1 Capacity correction curve
Cooling
Heating
1.00
Heating 4C36, 5C42,
8C48 models
Capacity ratio
0.95
0.90
Cooling 4C36 model
0.85
Cooling 5C42 model
Cooling 8C48 model
0.80
0.75
0.70
0
70
130
195
260 [ft]
Equivalent pipe length
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-34
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,
SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-35
10. SOUND PRESSURE LEVELS
MXZ-2C20NAHZ
FAN SPEED FUNCTION SPL(dB(A))
High
Cooling
54
High
Heating
58
LINE
MXZ-3C24NAHZ
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
Cooling
54
High
Heating
58
LINE
80
70
NC-60
50
NC-50
40
NC-40
30
NC-30
NC-20
125
250
500
1000
2000
4000
8000
NC-70
60
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
80
10
High
90
90
20
FAN SPEED FUNCTION SPL(dB(A))
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
MXZ-3C30NAHZ
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
FAN SPEED FUNCTION SPL(dB(A))
High
Cooling
54
High
Heating
58
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
OUTDOOR UNIT
39.4 in.
MICROPHONE
Test conditions
Cooling: Dry-bulb temperature 95°F Wet-bulb temperature 75°F
Heating: Dry-bulb temperature 45°F Wet-bulb temperature 43°F
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-36
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
10. SOUND PRESSURE LEVELS
MODE SPL(dB)
COOLING
49
HEATING
53
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
MXZ-5C42NAHZ
MXZ-5C42NAHZ
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MXZ-4C36NAHZ
MXZ-4C36NAHZ
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
MXZ-8C48NA
MXZ-8C48NAHZ
MXZ-8C48NAHZ
MODE SPL(dB)
COOLING
50
HEATING
54
MODE SPL(dB)
COOLING
51
HEATING
54
LINE
90
80
70
NC-70
MICROPHONE
1m(3.3ft)
60
UNIT
NC-60
50
NC-50
1.5m
(5ft)
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
GROUND
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-37
11. STANDARD OPERATION RANGE
MXZ-2C20NAHZMXZ-3C24NAHZMXZ-3C30NAHZ
Model
MXZ-2C20NAHZ
Outdoor unit MXZ-3C24NAHZ
MXZ-3C30NAHZ
Rating
208/230 V 60 Hz 1
Guaranteed Voltage
Min. 198 V 208 V 230 V Max. 253 V
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-38
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
12. ACCESSORIES
Part Number
Descriptions
Applicable model
BV12FFSI2
Refrigeration Ball Valve-Flare/Schrader/Insulated - 1/2" size
BV14FFSI2
Refrigeration Ball Valve-Flare/Schrader/Insulated - 1/4" size
BV38FFSI2
Refrigeration Ball Valve-Flare/Schrader/Insulated - 3/8" size
BV58FFSI2
Refrigeration Ball Valve-Flare/Schrader/Insulated - 5/8" size
CWMB1
4 piece ( 1 pair) condensing unit wall mounting brackets painted steel
DSD-400P
Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic
MSDD-50AR-E
Flared Connections for connecting two branch boxes
4C36, 5C42, 8C48NAHZ
and branch boxes
All Models
4C36, 5C42, 8C48NAHZ
MSDD-50BR-E
Brazed Connections for connecting two branch boxes
MAC-A454JP-E
Port Adapter size: 3/8" X 1/2"
MAC-A455JP-E
Port Adapter size: 1/2" X 3/8"
2C20, 3C24, 3C30, 4C36,
5C42, 8C48NAHZ
3C24, 3C30, 4C36, 5C42,
8C48NAHZ
MAC-A456JP-E
Port Adapter size: 1/2" X 5/8"
PAC-493PI
Port Adapter size: 1/4" x 3/8"
PAC-IF01MNT-E
M-NET Adapter
3C30, 4C36, 5C42,
8C48NAHZ
All Models
ULTRILITE2
Condensing Unit Mounting Pad 24" x 42" x 3"
Due to continuing improvement, above specification may be subject to change without notice.
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.
H2i-MXZ-39
12. ACCESSORIES
Part Number
Descriptions
PAC-MKA30BC
Three Port Branch Box
Applicable model
4C36, 5C42, 8C48NAHZ
PAC-MKA50BC
Five Port Branch Box
PAC-SG76RJ
3/8” x 5/8” Port Adapter
3C30, 4C36, 5C42,
8C48NAHZ
PAC-SG60DS-E
Drain Socket
2C20, 3C24, 3C30NAHZ
PAC-SH71DS-E
Drain Socket
4C36, 5C42, 8C48NAHZ
PAC-SH96SG-E
Airflow Guide
All Models
Due to continuing improvement, above specification may be subject to change without notice.
H2i-MXZ-40
M-Series - H2i® MXZ Outdoor Units (November 2014)
© 2014 Mitsubishi Electric US, Inc.