and Accessories - Control Panels USA Inc.

Instrumentation &
Control Panel
Submittal
Olympia Force Main
Submittal # 14-7271-01A
Nelson Lewis, Inc.
December 2014
16310 Bratton Lane
Building 1, Suite 100
Austin, TX 78728
Phone: (512) 863-3224
Fax: (512) 868-5446
www.controlpanelsusa.net
CP USA Project # 14-7271
CP USA Project Manager: Brandon Friemel
Submittal Clarification
14-7271-01A
ATTN:
Patrick N. Moseley, P.E.
Engineer for Moeller & Associates
c/o Mark Bray
Nelson Lewis, Inc.
PROJECT:
DATE:
Item #
1)
Olympia Force Main Project
December 11, 2014
Comment
CP USA is submitting our Instrument Panel schematics without the Power Insulator shown on
Contract Drawing Sheet E-006, as we are uncertain about the requirements for the Power Insulator for
this application. CP USA would ask the engineer to provide more information in the form of a
specification for the type of Power Insulator required.
Regards,
Brandon Friemel
Project Manager
16310 Bratton Lane, Suite 100 * Austin, Texas 78728 * Phone: (512) 863-3224 * Fax: (512) 868-5446 * www.controlpanelsusa.net
Nelson Lewis, Inc.
December 2014
Olympia Force Main
CP USA
Submittal # 14-7271-01A
SCHEDULE OF EQUIPMENT
ITEM #
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
DESCRIPTION
Instrument Panel
Enclosure, NEMA 4, Carbon Steel, Free
Standing, 3-Point Latching
Back Panel, Full
Folding Shelf
LED Panel Light, Door Switch, 120VAC, 18"
Circuit Breaker, UL489, 1-Pole, 5 Amp
Circuit Breaker, UL489, 1-Pole,10 Amp
Surge Suppressor, 120VAC
24VDC Power Supply, 5A
UPS, 24VDC, 5A
Universal DIN rail adapter
Relay, 4PDT, 10A, 120VAC
Relay, DPDT, 10A, 120VAC
Relay, DPDT, 10A, 24VDC
Relay Base, 2-pole
Relay Base, 4-pole
Push-To-Test Pilot Light, LED, Full Voltage,
30.5mm, NEMA 4/4X/13, 12-130V AC/DC,
Amber
Pushbutton, 30.5mm, NEMA 4/4X/13, Flush,
Black
Contact Block, 10Amp, 1 N.O. - 1 N.C.
Alarm Horn, 120VAC, Nema 4X, with weather
proof box
Alarm Strobe Light, Red Lense, 120VAC, 1/2"
conduit mount
DC Signal Line Surge Protector, 4-20mA w/
Shield, 20 kA Max Discharge Current
Terminal Block, Feed Through, Finger Safe, 2610awg, 41 Amp, 800Volt, Type UT4
Ground Terminal Block, Finger Safe, 26-10awg,
41 Amp, 800Volt, Type UT4-PE
Ground Bus Bar
Wire Way
Prepared by Control Panels USA Inc.
MANUFACTURER
PART NUMBER
Hoffman
A72H3124FS3PT
1
each
Hoffman
Hoffman
Saginaw
Siemens
Siemens
Phoenix Contact
Phoenix Contact
Phoenix Contact
Phoenix Contact
Idec
Idec
Idec
Idec
Idec
A72P30F1
ACSHELF1818SS
SCE-LF18NO
5SJ4111-7HG40
5SJ4110-7HG40
2856812
2866734
2320254
2320089
RH4B-UL-AC120
RH2B-UL-AC120
RH2B-UL-DC24
SH2B-05
SH4B-05
1
1
1
2
1
1
1
1
2
7
15
5
20
7
each
each
each
each
each
each
each
each
each
each
each
each
each
each
Allen-Bradley
800H-QRTH2A
4
each
Allen-Bradley
800H-AR2
2
each
Allen-Bradley
800T-XA
2
each
Federal Signal
350-120VAC-WB
1
each
Federal Signal
LP3P-Red
1
each
Citel
DLA-24D3
1
each
Phoenix Contact
3044102
A/R
each
Phoenix Contact
3044128
A/R
each
Square D
Thomas & Betts
PK7GTA
TY series
A/R
A/R
each
ft
Page 1 of 1
QUANTITY
UNIT
12/11/2014
Nelson Lewis, Inc.
December 2014
Olympia Force Main
CP USA
Submittal # 14-7271-01A
SCHEDULE OF EQUIPMENT
ITEM #
DESCRIPTION
26
Field Instruments
Combustible Gas Detector
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Existing/Owner Provided Field Instruments & Equipment
Low Level Lockout Float Switch, N.C. Contacts
High Level Float Switch, N.O. Contacts
High High Level Float Switch, N.O. Contacts
Auto-Dialer
Radio Unit
Pump Controller
Submersible Level Transmitter
Prepared by Control Panels USA Inc.
MANUFACTURER
PART NUMBER
QUANTITY
UNIT
ATI
C12-17-0100-2-1-00-0261
1
each
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
1
1
1
1
1
1
1
each
each
each
each
each
each
each
Page 1 of 1
12/11/2014
Nelson Lewis, Inc.
November 2014
Olympia Force Main
CP USA
Submittal # 14-7271-01A
SCHEDULE OF EQUIPMENT
ITEM #
7
8
11
12
13
14
15
21
DESCRIPTION
Spare Equipment
Surge Suppressor, 120VAC
24VDC Power Supply, 5A
Relay, 4PDT, 10A, 120VAC
Relay, DPDT, 10A, 120VAC
Relay, DPDT, 10A, 24VDC
Relay Base, 2-pole
Relay Base, 4-pole
DC Signal Line Surge Protector, 4-20mA w/
Shield, 20 kA Max Discharge Current
Prepared by Control Panels USA Inc.
MANUFACTURER
PART NUMBER
QUANTITY
UNIT
Phoenix Contact
Phoenix Contact
Idec
Idec
Idec
Idec
Idec
2856812
2866734
RH4B-ULAC120
RH2B-UL-AC120
RH2B-UL-DC24
SH2B-05
SH4B-05
2
2
5
5
1
6
5
each
each
each
each
each
each
each
Citel
DLA-24D3
3
each
Page 1 of 1
12/11/2014
Item # 01
Free-Stand Enclosures Type 4 Free-Stand Enclosures and Accessories
Mild Steel
Free-Stand Enclosures
Type 4 Free-Stand Enclosures and Accessories
Spec-00156
F
763.422.2211
763.422.2600
Free-Stand with 3-Point Latch, Type 4
APPLICATION
These enclosures are ideal for mounting equipment on panels
or racks in indoor or outdoor applications where it is necessary
to protect controls and instrumentation from wet, non-corrosive
environments. The design features Hoffman’s exclusive
POWERGLIDE™ Handle with 3-point latching for secure closure.
FEATURES
•
•
•
•
•
-point latch for security and ease of use
3
Mounting channels accommodate panel or rack-mount
equipment
P anels and rack mount angles can be mounted anywhere along
channels
Rolled flange around door opening excludes liquids and
contaminants
L ifting eyes for easy handling
SPECIFICATIONS
•
•
•
•
•
•
•
•
•
•
2 gauge steel
1
3-point latch system with POWERGLIDE® handle
S eams continuously welded and ground smooth; no holes or
knockouts
Mounting channels welded horizontally to interior body sides at
top, bottom and center
Heavy-gauge continuous hinge with stainless steel hinge pin
Data pocket is high-impact thermoplastic
L ifting eyes
Oil-resistant door gasket
Bonding provision on door
Provision for mounting fluorescent light
FINISH
ANSI 61 gray polyester powder paint inside and out over pretreated
surfaces. Optional panels have either a white or a conductive finish.
ACCESSORIES
INDUSTRY STANDARDS
UL 508A Listed; Type 4, 12; File No. E61997
cUL Listed per CSA C22.2 No. 94; Type 4, 12; File No. E61997
NEMA Type 3, 4, 12, 13
E.I.A. RS310D
IEC 60529, IP66
See also Accessories.
Drawers
INTERSAFE™ Data Interface Ports, Type 4/4X/12
PANELITE™ Enclosure Lights Overview
Pull-Out Shelves
Rack Mounting Angles - U Style (Type RA)
Swing-Out Panels for Free-Stand Type 4, 4X and 12 Enclosures with
Mounting Channel
MODIFICATION AND CUSTOMIZATION
Hoffman excels at modifying and customizing products to
your specifications. Contact your local Hoffman sales office or
distributor for complete information.
Bulletin: A4L3
Standard Product Catalog Number
A72H2518FS3PT
A72H3124FS3PT
A72H3724FS3PT
1
Mild Steel
AxBxC in./mm
72.06 x 25.06 x 18.06
1830 x 637 x 459
72.06 x 31.06 x 24.06
1830 x 789 x 611
72.06 x 37.06 x 24.06
1830 x 941 x 611
SUBJECT TO CHANGE WITHOUT NOTICE
Rack Units
35
35
35
EQUIPMENT PROTECTION SOLUTIONS
Spec-00156 F
Free-Stand Enclosures Type 4 Free-Stand Enclosures and Accessories
EQUIPMENT PROTECTION SOLUTIONS
Spec-00156 F
PH 763.422.2211 • FAX 763.422.2600 • HOFFMANONLINE.COM
Mild Steel
2
Item # 02
Panels and Panel Accessories Panels for Enclosures
Panels for Free-Stand Type 4, 4X and 12 Single- and Dual-Access One-Door Enclosures with
Mounting Channel
Panels for one-door, single-access and one-door, dual-access Free-Stand Type 12 Enclosures, Free-Stand Type 4 Enclosures and OneDoor Type 4X Free-Stand Fiberglass Enclosures. Panels are 12 gauge steel and can be positioned anywhere along horizontal mounting
channels (see dimension drawing Sections B-B for limitations). Half-length panels can be located in the upper or lower portion of the
enclosure. Panels are finished with white polyester powder paint or a conductive, corrosion-resistant coating and furnished with plated
mounting hardware.
Bulletin: PNL30, PNLFS
Catalog Number
A60P24F1
A60P24F1G
A60P24F2
A60P24F2G
A72P24F1
A72P24F1G
A72P24F2
A72P24F2G
A90P24F1
A90P24F1G
A90P24F2
A90P24F2G
A72P30F1
A72P30F1G
A72P30F2
A72P30F2G
A60P36F1
A60P36F1G
A60P36F2
A60P36F2G
A72P36F1
A72P36F1G
A72P36F2
A72P36F2G
A90P36F1
A90P36F1G
A90P36F2
A90P36F2G
Description
Full Panel
Full Panel
Half Panel
Half Panel
Full Panel
Full Panel
Half Panel
Half Panel
Full Panel
Full Panel
Half Panel
Half Panel
Full Panel
Full Panel
Half Panel
Half Panel
Full Panel
Full Panel
Half Panel
Half Panel
Full Panel
Full Panel
Half Panel
Half Panel
Full Panel
Full Panel
Half Panel
Half Panel
Finish
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Painted steel
Conductive
Panel Size (in.)
48.00 x 20.00
48.00 x 20.00
24.88 x 20.00
24.88 x 20.00
60.00 x 20.00
60.00 x 20.00
30.88 x 20.00
30.88 x 20.00
78.00 x 20.00
78.00 x 20.00
39.88 x 20.00
39.88 x 20.00
60.00 x 26.00
60.00 x 26.00
30.88 x 26.00
30.88 x 26.00
48.00 x 32.00
48.00 x 32.00
24.88 x 32.00
24.88 x 32.00
60.00 x 32.00
60.00 x 32.00
30.88 x 32.00
30.88 x 32.00
78.00 x 32.00
78.00 x 32.00
39.88 x 32.00
39.88 x 32.00
Panel Size (mm)
1218 x 508
1218 x 508
632 x 508
632 x 508
1524 x 508
1524 x 508
784 x 508
784 x 508
1981 x 508
1981 x 508
1013 x 508
1013 x 508
1524 x 660
1524 x 660
784 x 660
784 x 660
1219 x 813
1219 x 813
632 x 813
632 x 813
1524 x 813
1524 x 813
784 x 813
784 x 813
1981 x 813
1981 x 813
1013 x 813
1013 x 813
Fits Enclosure
A x B (in.)
60.00 x 24.00
60.00 x 24.00
60.00 x 24.00
60.00 x 24.00
72.00 x 24.00
72.00 x 24.00
72.00 x 24.00
72.00 x 24.00
90.00 x 24.00
90.00 x 24.00
90.00 x 24.00
90.00 x 24.00
72.00 x 30.00
72.00 x 30.00
72.00 x 30.00
72.00 x 30.00
60.00 x 36.00
60.00 x 36.00
60.00 x 36.00
60.00 x 36.00
72.00 x 36.00
72.00 x 36.00
72.00 x 36.00
72.00 x 36.00
90.00 x 36.00
90.00 x 36.00
90.00 x 36.00
90.00 x 36.00
Fits Enclosure
A x B (mm)
1524 x 610
1524 x 610
1524 x 610
1524 x 610
1829 x 610
1829 x 610
1829 x 610
1829 x 610
2286 x 610
2286 x 610
2286 x 610
2286 x 610
1829 x 762
1829 x 762
1829 x 762
1829 x 762
1524 x 914
1524 x 914
1524 x 914
1524 x 914
1829 x 914
1829 x 914
1829 x 914
1829 x 914
2286 x 914
2286 x 914
2286 x 914
2286 x 914
Use combinations of panels for 3-5 door A 28 enclosures.
11
Accessories
SUBJECT TO CHANGE WITHOUT NOTICE
EQUIPMENT PROTECTION
Spec-00310 P
Item # 03
Shelves, Keyboard Trays and Gland Plates Folding Shelves
Accessories
Shelves, Keyboard Trays and Gland Plates
Folding Shelves
Spec-00035
N63.422.2211
7
763.422.2600
Stainless Steel Folding Shelf
Catalog Number
ACSHELF12
ACSHELF1212SS
ACSHELF1818SS
ACSHELF2424SS
Size AxB
in./mm
12.00 x 12.00
305 x 305
12.00 x 12.00
305 x 305
18.00 x 18.00
457 x 457
24.00 x 24.00
610 x 610
Maximum
Distributed
Load Rating (lb.)
150
Maximum
Distributed
Load Rating (kg)
68
150
68
150
68
150
68
Supports instruments and test equipment used to install and
maintain electrical components in an enclosure. Also ideally
suited for supporting laptop computers, monitoring units and
other equipment used with programmable controllers. The shelf
can be installed on the inside or outside surface of larger Hoffman
industrial enclosures (except PROLINE™ ). Automatically locks in
the horizontal position when raised. When not in use, the shelf folds
down and projects only 1 in. (25 mm) from the mounting surface.
Constructed of 304 stainless steel with a brushed finish. Maintains
UL/CSA Type 4, 4X and 12 rating when properly installed on a
Hoffman enclosure.
Bulletin: A80
Large Folding Shelf
Catalog Number
AASHLF1218
AA61SHLF1218
AA35SHLF1218
AASHLF1818
AA61SHLF1818
Supports instruments and test equipment used to install and
maintain electrical components in an enclosure. Also ideally
suited for supporting laptop computers, monitoring units and
other equipment used with programmable controllers. The shelf
can be installed on the inside or outside surface of larger Hoffman
industrial enclosures (except PROLINE™ ). Automatically locks in
the horizontal position when raised. When not in use, the shelf folds
to 1.73 in. (44 mm) from the mounting surface. All parts are heavy
gauge steel. Maintains UL/CSA Type 4 and 12 when properly intalled
on a Hoffman enclosure.
Bulletin: A34Y, A80
1
Accessories
AA35SHLF1818
AASHLF2424
AA61SHLF2424
AA35SHLF2424
Size AxB
in./mm
18.00 x 12.00
457 x 305
18.00 x 12.00
457 x 305
18.00 x 12.00
457 x 305
18.00 x 18.00
457 x 457
18.00 x 18.00
457 x 457
18.00 x 18.00
457 x 457
24.00 x 24.00
610 x 610
24.00 x 24.00
610 x 610
24.00 x 24.00
610 x 610
Maximum
Distributed
Load Rating (lb.)
150
Maximum
Distributed
Load Rating (kg)
68
Finish
White
150
68
Gray
150
68
Light gray
150
68
White
150
68
Gray
150
68
Light gray
150
68
White
150
68
Gray
150
68
Light gray
Catalog numbers ACSHELF12 and ACSHELF18 have been obsoleted. Please use
the shelves above as replacements.
SUBJECT TO CHANGE WITHOUT NOTICE
EQUIPMENT PROTECTION
Spec-00035 N
Item # 04
300
SAGINAW CONTROL & ENGINEERING • STOCK PRICE LIST
GENERAL
ACCESSORIES
LED Light Fixture
Application -
LED light fixture is designed to provide
interior lighting for an enclosure. Can be
mounted to light channels in the top of an
enclosure or on the front flange of most
enclosures. Door activated adjustable
switch, switch can be removed and
relocated. Terminal block on each end of
fixture, making it easy to wire and daisy
chain multiple lights continuously. LED
bulb with PVC frosted white protective light
diffuser included. Housing made from steel
and powder coated white epoxy polyester.
Units with convenience receptacle outlet
are 120 VAC with ground 50/60 HZ. Without
convenience receptacle outlet 100 to 277
VAC 50/60 HZ.
Catalog No.
Height
Width Depth
Product
List
(A) (B) (C)AMPVACHz Code Price
SCE-LF18
2.75
18.18
4.00
0.53
100-125
50/60
P2
206.55
SCE-LF24
2.75
24.18
4.00
0.53
100-125
50/60
P2
218.03
2.75
18.18
4.00
0.53
100-240
50/60
P2
185.90
2.75
24.18
4.00
0.53
100-240
50/60
P2
196.72
Product
Code
List
Price
SCE-LF18NO
SCE-LF24NO
No
(Outlet
)
No
(Outlet )
Construction -
• 4000K Frosted White
• 18 inch 850 Lumens
• 24 inch 900 Lumens
IS10 - Industry Standards UL Component Recognized
Light Switch Mounting Bracket
Catalog No.
SCE-LSMB
Height
Width
Depth
(A)(B) (C)
2.00
2.68
1.00
P2
25.56
9 General Accessories
Designed to remote mount the door
activated light switch when space is limited.
Light Switch Mounting Bracket may be used
with SCE-LF18, SCE-LF18NO, SCE-LF24 &
SCE-LF24NO. For installation information,
consult our Installation Manual at www.
saginawcontrol.com.
Full Light Switch Assembly
Designed to remote mount the light switch
when space is limited.
Catalog No.
SCE-LSA
Product
List
CodePrice
P2
Phone (989) 799-6871
Fax (989) 799-4524
38.34
Item # 05, 06
Product Selection – 5SJ41..-.HG40
Type HSJ: Interrupting rating:
240 VAC: 14,000 Maximum RMS Symmetrical Amps
60 VDC: 10,000 Amps
Type NSJ: Interrupting rating:
240 VAC: 10,000 Maximum RMS Symmetrical Amps
60 VDC (1-pole) / 125 VDC (2- & 3-pole): 10,000 Amps
TYPE 
No. of
In
(A)
Poles
1
0.3
1
0.5
1
1
1
1.6
1
2
1
3
1
4
1
5
1
6
1
8
1
10
1
13
1
15
1
16
1
20
1
25
1
30
1
32
1
35
1
40
1
45
1
50
1
60
1
63
HSJ
Characteristic B
Order No.
----------------5SJ4106-6HG40
--5SJ4110-6HG40
5SJ4113-6HG40
5SJ4118-6HG40
5SJ4116-6HG40
5SJ4120-6HG40
5SJ4125-6HG40
5SJ4130-6HG40
5SJ4132-6HG40
5SJ4135-6HG40
5SJ4140-6HG40
5SJ4145-6HG40
5SJ4150-6HG40
5SJ4160-6HG40
5SJ4163-6HG40
5SJ4...-.HG4. Product Profile 090121.doc
HSJ
Characteristic C
Order No.
5SJ4114-7HG40
5SJ4105-7HG40
5SJ4101-7HG40
5SJ4115-7HG40
5SJ4102-7HG40
5SJ4103-7HG40
5SJ4104-7HG40
5SJ4111-7HG40
5SJ4106-7HG40
5SJ4108-7HG40
5SJ4110-7HG40
5SJ4113-7HG40
5SJ4118-7HG40
5SJ4116-7HG40
5SJ4120-7HG40
5SJ4125-7HG40
5SJ4130-7HG40
5SJ4132-7HG40
5SJ4135-7HG40
5SJ4140-7HG40
NSJ
Characteristic C
Order No.
HSJ
Characteristic
D Order No.
5SJ4114-8HG40
5SJ4105-8HG40
5SJ4101-8HG40
5SJ4115-8HG40
5SJ4102-8HG40
5SJ4103-8HG40
5SJ4104-8HG40
5SJ4111-8HG40
5SJ4106-8HG40
5SJ4108-8HG40
5SJ4110-8HG40
5SJ4113-8HG40
5SJ4118-8HG40
5SJ4116-8HG40
5SJ4120-8HG40
5SJ4125-8HG40
5SJ4130-8HG40
5SJ4132-8HG40
5SJ4135-8HG40
5SJ4140-8HG40
5SJ4145-8HG40
5SJ4150-8HG40
5SJ4160-8HG40
5SJ4163-8HG40
5SJ4145-7HG40
5SJ4150-7HG40
5SJ4160-7HG40
5SJ4163-7HG40
6 of 19
NSJ
Characteristic D
Order No.
January 2009
Product Selection – 5SJ4…-.HG41
Type HSJ: Interrupting rating:
240 VAC: 14 kA Maximum RMS Symmetrical
60 VDC (1-pole) / 125 VDC (2- & 3-pole): 10kA
Type NSJ: Interrupting rating:
240 VAC: 10kA Maximum RMS Symmetrical
60 VDC (1-pole)/125 VDC (2- & 3-pole): 10 kA
HSJ
TYPE 
No. of
In
Characteristic C
(A)
Order No.
Poles
*
0.3
5SJ4*14-7HG41
*
0.5
5SJ4*05-7HG41
*
1
5SJ4*01-7HG41
*
1.6
5SJ4*15-7HG41
*
2
5SJ4*02-7HG41
*
3
5SJ4*03-7HG41
*
4
5SJ4*04-7HG41
*
5
5SJ4*11-7HG41
*
6
5SJ4*06-7HG41
*
8
5SJ4*08-7HG41
*
10
5SJ4*10-7HG41
*
13
5SJ4*13-7HG41
*
15
5SJ4*18-7HG41
*
16
5SJ4*16-7HG41
*
20
5SJ4*20-7HG41
*
25
5SJ4*25-7HG41
*
30
5SJ4*30-7HG41
*
32
5SJ4*32-7HG41
*
35
5SJ4*35-7HG41
*
40
5SJ4*40-7HG41
*
45
*
50
*
60
*
63
1Substitute the “*” with:
1
for 1-pole mCBs
2
for 2-pole mCBs
3
for 3-pole mCBs
5SJ4...-.HG4. Product Profile 090121.doc
NSJ
Characteristic C
Order No.
5SJ4*45-7HG41
5SJ4*50-7HG41
5SJ4*60-7HG41
5SJ4*63-7HG41
7 of 19
HSJ
Characteristic D
Order No.
5SJ4*14-8HG41
5SJ4*05-8HG41
5SJ4*01-8HG41
5SJ4*15-8HG41
5SJ4*02-8HG41
5SJ4*03-8HG41
5SJ4*04-8HG41
5SJ4*11-8HG41
5SJ4*06-8HG41
5SJ4*08-8HG41
5SJ4*10-8HG41
5SJ4*13-8HG41
5SJ4*18-8HG41
5SJ4*16-8HG41
5SJ4*20-8HG41
NSJ
Characteristic D
Order No.
5SJ4*25-8HG41
5SJ4*30-8HG41
5SJ4*32-8HG41
5SJ4*35-8HG41
5SJ4*40-8HG41
5SJ4*45-8HG41
5SJ4*50-8HG41
5SJ4*60-8HG41
5SJ4*63-8HG41
January 2009
Product Selection – 5SJ4…-.HG42
Type NSJ: Interrupting rating:
 480Y/277 VAC 10,000 Maximum RMS Symmetrical Amps
 60 VDC (1-pole) / 125 VDC (2- & 3-pole) 10,000 Amps
HSJ
TYPE 
No. of
In
Characteristic C
(A)
Order No.
Poles
*
0.3
--*
0.5
--*
1
--*
1.6
--*
2
--*
3
--*
4
--*
5
--*
6
--*
8
--*
10
--*
13
--*
15
--*
16
--*
20
--*
25
--*
30
--*
32
--*
35
--*
40
--*
45
--*
50
--*
60
--*
63
--1Substitute the “*” with:
1
for 1-pole mCBs
2
for 2-pole mCBs
3
for 3-pole mCBs
5SJ4...-.HG4. Product Profile 090121.doc
NSJ
Characteristic C
Order No.
5SJ4*14-7HG42
5SJ4*05-7HG42
5SJ4*01-7HG42
5SJ4*15-7HG42
5SJ4*02-7HG42
5SJ4*03-7HG42
5SJ4*04-7HG42
5SJ4*11-7HG42
5SJ4*06-7HG42
5SJ4*08-7HG42
5SJ4*10-7HG42
5SJ4*13-7HG42
5SJ4*18-7HG42
5SJ4*16-7HG42
5SJ4*20-7HG42
5SJ4*25-7HG42
5SJ4*30-7HG42
5SJ4*32-7HG42
5SJ4*35-7HG42
5SJ4*40-7HG42
---------
8 of 19
HSJ
Characteristic D
Order No.
-------------------------------------------------
NSJ
Characteristic D
Order No.
5SJ4*14-8HG42
5SJ4*05-8HG42
5SJ4*01-8HG42
5SJ4*15-8HG42
5SJ4*02-8HG42
5SJ4*03-8HG42
5SJ4*04-8HG42
5SJ4*11-8HG42
5SJ4*06-8HG42
5SJ4*08-8HG42
5SJ4*10-8HG42
5SJ4*13-8HG42
5SJ4*18-8HG42
5SJ4*16-8HG42
5SJ4*20-8HG42
5SJ4*25-8HG42
5SJ4*30-8HG42
5SJ4*32-8HG42
-------------
January 2009
Control Circuit Protection
Supplementary Protectors
Dimensions
5SX2 supplementary protectors
5SX2,
5SY4, 5SY5 supplementary protectors
5SJ4, single pole branch circuit protector
5SX9 auxiliary switch, 5SX9 fault signal
Additional component for 5SX2; can be retrofitted 5SX9 1.., 5SX9 2..
5ST3 auxiliary switch
5ST3 fault signal contact
can be retrofitted to 5SY4, 5SY5, 5SP4
5SP4 supplementary protectors
5ST3 shunt trip
5ST3 undervoltage release
can be retrofitted
to 5SY4, 5SY5, 5SP4
Siemens Energy & Automation, Inc.
Industrial Controls Catalog
16/23
Control Circuit Protection
General Data
5SJ4 Branch Circuit Protector
Technical Data
Specification
Tripping characteristic
Number of poles
Rated voltage (UL 489)
Operating voltage, min.
Rated current
Interrupting Rating (UL 489)
AC: Max. RMS Symmetrical
Standards
Certifications
Degree of protection
Device depth
Mounting technique
Terminals
Terminal tightening torque
Wire Size
Recommended Wire Strip Length
Mounting
Position
Ambient temperature
Calibration temperature
Storage temperature
Resistance to vibration
Dimensions
Siemens Energy & Automation, Inc.
Industrial Controls Catalog
5SJ41 Mini-Breaker
C
D
1
V AC: 240 max.
V DC: 60 max.
24 VAC/DC
6 to 63 A
0.3 to 63 A
0.3 to 63 A
V AC 240: 14 kA
V AC 240: 14 kA
(0.3 - 40 A)
(0.3 - 20 A)
V AC 240: 5 kA
V AC 240: 5 kA
(45 - 63 A)
(25 - 63 A)
V AC 240: 14 kA;
V DC 60: 10 kA
V DC 60: 10 kA
V DC 60: 10 kA
(0.3 - 63 A)
(0.3 - 63 A)
UL 489, CSA 22.2 No. 5-02, IEC/EN 60 898
UL, cUL, File No. E 243414
IP 10 acc. to DIN EN 60 529; IP 40 when panel mounted
70 mm
Standard 35 mm DIN rail
Identical screw terminals on both line and load sides
31 lbs. in. (3.5 Nm)
14-4 AWG (1.5 - 25 mm2)
60/75˚C, Cu only
0.59 in. (15 mm)
B
As Required
-13˚ to +113˚F (-25˚ to +45˚C)
temporary: +131˚F (+55˚C); max. humidity: 95%
25˚C (77˚F) acc. to UL 489
30˚C (86˚F) acc. to EN 60 898
-40˚ to +167˚F (-40˚ to +75˚C)
60 m/s2 at 10 Hz up to 150 Hz acc. to IEC 60 068-2-6
see catalog page 16/23
16/5
Control Circuit Protection
General Data
Trip characteristics
Tripping characteristics acc. to EN 60 898
Tripping characteristic B, -6
Type B characteristic designed for European residential circuit protection.
This characteristic can also
be used for protection of
computers and electronic
equipment. Magnetic trip
point - 3 to 5 times In rating.
Thermal trip point - 1.13 to
1.45 protector rating.
Tripping characteristic C, -7
Type C characteristic is for
general device protection in
control circuits. Magnetic
trip point - 5 to10 times In rating. Thermal trip point - 1.13
to 1.45 protector rating.
Tripping characteristic D, -8
Type D characteristic is designed for high inrush loads.
Magnetic trip point - 10 to 20
times In rating. Thermal trip
point - 1.13 to 1.45 protector
rating.
1,13 1,45
120
A I2_06353c
20
10
6
4
1,13 1,45
120
2
1
40
20
2
20
2
Seconds
Seconds
10
6
4
10
6
4
1
0,6
0,4
2
1
0,6
0,4
0,2
0,2
0,1
0,06
0,04
0,1
0,06
0,04
0,02
For different ambient temperatures, the current values of the
delayed tripping operation
change by approximately 5%
per 10°K temperature difference. Specifically they increase
for temperatures below 25°C
(5SJ41), 30°C (5SP, 5SX, 5SY)
and decrease for temperatures
above 25°C (5SJ41), 30°C (5SP,
5SX, 5SY).
20
1
40
10
6
4
0,01
A I2_06354c
60
40
Tripping time
Tripping time
Minutes
60
40
Minutes
Tripping characteristic A, -5
Type A characteristic is designed to protect very sensitive circuits such as
semiconductors. Magnetic
trip point - 2 to 3 times In rating. Thermal trip point - 1.13
to 1.45 protector rating.
0,02
1 1,5 2
3 4 5 6 8 10 15 20
Multiple of rated current
0,01
1
30
If more that one electrical circuit
is loaded in a series of miniature
circuit breakers or supplementary protectors, the resulting increase in ambient temperature
affects the characteristic curve.
In this case an additional correction factor found in the following table must be used.
1,5 2
3 4 5 6 8 10 15 20
Multiple of rated current
Number
1
2-3
4-6
>7
Correction factor K
1.00
0.90
0.88
0.85
30
For DC voltages the maximum
current values of the instantaneous tripping operation increase by a factor of 1.2.
16/2
Siemens Energy & Automation, Inc.
Industrial Controls Catalog
Item # 07
https://www.phoenixcontact.com/us/products/2856812
Type 3 surge protection device - PT 2-PE/S-120AC/FM - 2856812
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Pluggable type 3 arrester (device protection) for single-phase power supply networks with separate N and PE (3conductor system: L1, N, PE) with remote indication contact.
The figure shows the PT 2-PE/
S-230AC/FM version
Product Features
Plugs can be checked with CHECKMASTER
Tool-free plug replacement
With floating remote indication contact
Consists of base element and plug
Optical signaling of disconnection via LED
DIN rail module
For single and multi-phase power supply units
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
79.5 GRM
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
90 mm
Width
17.7 mm
Depth
65.5 mm
Horizontal pitch
1 Div.
12/11/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2856812
Type 3 surge protection device - PT 2-PE/S-120AC/FM - 2856812
Technical data
Dimensions
Complete module height
90 mm
Complete module width
17.7 mm
Complete module depth
65.5 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 85 °C
General
Housing material
PA
Inflammability class according to UL 94
V0
Color
black
Standards for air and creepage distances
DIN VDE 0110-1
IEC 60664-1
DIN VDE 0675-6
IEC 61643-1
Surge voltage category
III
Pollution degree
2
Type
DIN rail module, two-section, divisible
Mounting type
DIN rail: 35 mm
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.00
Direction of action
1L-N & N-PE
Protective circuit
IEC test classification
III
EN type
T3
Nominal voltage UN
120 V AC
Arrester rated voltage UC
150 V AC
Nominal frequency fN
50 Hz
60 Hz
Nominal current IN
26 A (30 °C)
Operating effective current IC at UC
≤ 1.1 mA
Standby power consumption PC
≤ 200 mVA
Residual current IPE
≤ 1.5 µA
Nominal discharge current In (8/20) µs
2.5 kA
3 kA (in acc. with UL 1449)
Combination wave UOC
6 kV
Voltage protection level Up (L-N)
≤ 620 V
12/11/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2856812
Type 3 surge protection device - PT 2-PE/S-120AC/FM - 2856812
Technical data
Protective circuit
Voltage protection level Up (L-PE)
≤ 850 V
Voltage protection level Up (N-PE)
≤ 850 V
Response time tA (L-N)
≤ 25 ns
Response time tA (L-PE)
≤ 100 ns
Max. required back-up fuse
25 A (gL/C)
Surge protection fault message
Optical, remote indicator contact
Non-heating apparatus connection, power supply
Connection method
Screw connection
Connection type IN
Screw terminal blocks
Connection type OUT
Screw terminal blocks
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Remote indicator contact
Connection name
Remote fault indicator contact
Switching function
N/C contact
Connection method
Screw connection
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Maximum operating voltage Umax. AC
250 V
Maximum operating voltage Umax DC
50 V
Max. operating current Imax
3 A AC
Standards and Regulations
12/11/2014 Page 3 / 5
https://www.phoenixcontact.com/us/products/2856812
Type 3 surge protection device - PT 2-PE/S-120AC/FM - 2856812
Technical data
Standards and Regulations
Standards/specifications
IEC 61643-1 2005
EN 61643-11/A11 2007
UL 1449
NF C61-740
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130806
eCl@ss 7.0
27130806
ETIM
ETIM 2.0
EC000942
ETIM 3.0
EC000942
ETIM 4.0
EC000942
ETIM 5.0
EC001473
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Drawings
12/11/2014 Page 4 / 5
https://www.phoenixcontact.com/us/products/2856812
Type 3 surge protection device - PT 2-PE/S-120AC/FM - 2856812
Dimensioned drawing
Circuit diagram
90
L
5
6
L
44,8
11
J
12
OUT
51,5
65,5
IN
N
N
1
2
PE
3
4 PE
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
12/11/2014 Page 5 / 5
Item # 08
https://www.phoenixcontact.com/us/products/2866734
Power supply unit - QUINT-PS/ 3AC/24DC/ 5 - 2866734
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking)
Technology, input: 3-phase, output: 24 V DC/5 A
Product description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system
protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states
before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V
DC ... 56 V DC are covered. Product Features
High level of system availability even in the event of permanent phase failure
Reliable starting of difficult loads
Preventive function monitoring
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
1038.0 GRM
Custom tariff number
85044030
Country of origin
Thailand
Technical data
Dimensions
Width
40 mm
Height
130 mm
Depth
125 mm
Width with alternative assembly
122 mm
Height with alternative assembly
130 mm
Depth with alternative assembly
43 mm
12/11/2014 Page 1 / 6
https://www.phoenixcontact.com/us/products/2866734
Power supply unit - QUINT-PS/ 3AC/24DC/ 5 - 2866734
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage range
3x 400 V AC ... 500 V AC
Input voltage range
3x 320 V AC ... 575 V AC
2x 360 V AC ... 575 V AC
450 V DC ... 800 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
3x 0.8 A (400 V AC)
3x 0.7 A (500 V AC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 20 ms (400 V AC)
> 30 ms (500 V AC)
Choice of suitable fuses
6 A ... 16 A (AC: Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor, gas-filled surge arrester
Output data
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
5 A (-25°C ... 60°C, UOUT = 24 V DC)
7.5 A (with POWER BOOST, -25°C ... 40°C permanently, UOUT = 24 V DC)
30 A (SFB technology, 12 ms)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Residual ripple
< 20 mVPP (with nominal values)
Peak switching voltages nominal load
< 20 mVPP (at nominal values, 20 MHz)
Maximum power dissipation NO-Load
4W
Power loss nominal load max.
14 W
General
Net weight
0.7 kg
Operating voltage display
Green LED
12/11/2014 Page 2 / 6
https://www.phoenixcontact.com/us/products/2866734
Power supply unit - QUINT-PS/ 3AC/24DC/ 5 - 2866734
Technical data
General
Efficiency
> 89 % (at 400 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
2 kV AC (routine test)
Protection class
I
> 635000 h (40°C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
vertically
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Shipbuilding approval
Germanischer Lloyd (EMC 2), ABS, LR, RINA, NK, DNV, BV
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
DIN VDE 0106-1010
Standard – Protection against electric shock
DIN 57100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Equipment safety
GS (tested safety)
Approval - requirement of the semiconductor industry with regard to mains
SEMI F47-0706 Compliance Certificate
voltage dips
Information technology equipment - safety (CB scheme)
CB Scheme
UL approvals
UL Listed UL 508
UL/C-UL Recognized UL 60950-1 (3-wire + PE, star net)
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
Surge voltage category
III
Connection data, input
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
20
12/11/2014 Page 3 / 6
https://www.phoenixcontact.com/us/products/2866734
Power supply unit - QUINT-PS/ 3AC/24DC/ 5 - 2866734
Technical data
Connection data, input
Conductor cross section AWG/kcmil max
12
Stripping length
7 mm
Screw thread
M3
Connection data, output
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
12
Stripping length
7 mm
Signaling
Output name
DC OK active
Output description
UOUT > 0.9 x UN: High signal
Maximum switching voltage
+ 24 V DC
Output voltage
+ 24 V DC
Maximum inrush current
min. 20 mA (short-circuit resistant)
Continuous load current
≤ 20 mA
Status display
UOUT > 0.9 x UN: "DC OK" LED green
Note on status display
UOUT < 0.9 x UN: Flashing "DC OK" LED
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
12
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Screw thread
M3
Output name
DC OK floating
Output description
Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage
≤ 30 V AC/DC
Maximum inrush current
≤1A
Continuous load current
≤1A
Status display
UOUT > 0.9 x UN: "DC OK" LED green
12/11/2014 Page 4 / 6
https://www.phoenixcontact.com/us/products/2866734
Power supply unit - QUINT-PS/ 3AC/24DC/ 5 - 2866734
Technical data
Signaling
Note on status display
UOUT < 0.9 x UN: Flashing "DC OK" LED
Output name
POWER BOOST, active
Output description
IOUT < IN: High signal
Maximum switching voltage
+ 24 V DC
Output voltage
+ 24 V DC
Maximum inrush current
min. 20 mA (short-circuit resistant)
Continuous load current
≤ 20 mA
Status display
IOUT > IN: LED "BOOST" yellow
Classifications
eCl@ss
eCl@ss 4.0
27040702
eCl@ss 4.1
27040702
eCl@ss 5.0
27049002
eCl@ss 5.1
27049002
eCl@ss 6.0
27049002
eCl@ss 7.0
27049002
eCl@ss 8.0
27049002
ETIM
ETIM 2.0
EC001039
ETIM 3.0
EC001039
ETIM 4.0
EC000599
ETIM 5.0
EC002540
UNSPSC
UNSPSC 6.01
30211502
UNSPSC 7.0901
39121004
UNSPSC 11
39121004
UNSPSC 12.01
39121004
UNSPSC 13.2
39121004
Drawings
12/11/2014 Page 5 / 6
https://www.phoenixcontact.com/us/products/2866734
Power supply unit - QUINT-PS/ 3AC/24DC/ 5 - 2866734
Block diagram
L1 (+)
L2
L3 (-)
DC OK
I < IN
13
14
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
12/11/2014 Page 6 / 6
Item # 09
https://www.phoenixcontact.com/us/products/2320254
Uninterruptible power supply - QUINT-UPS/ 24DC/ 24DC/
5/1.3AH - 2320254
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Uninterruptible power supply with IQ technology and integrated power storage for DIN rail mounting, input 24 V
DC, output: 24 V DC/5 A, power storage: lead AGM 1.3 Ah, incl. mounted UTA 107/30 universal DIN rail adapter
Product Features
Easy handling thanks to automatic battery detection, tool-free battery replacement during operation, and communication via the IFS interface
Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
Fast tripping of standard circuit breakers with SFB (selective fuse breaking) technology
Device suitable for universal use thanks to comprehensive license package and extensive parameterization and diagnostics options
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
2420.0 GRM
Custom tariff number
85371091
Country of origin
China
Technical data
Dimensions
Width
88 mm
Height
138 mm
Depth
125 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
0 °C ... 40 °C
Ambient temperature (storage/transport)
-15 °C ... 40 °C
Max. permissible relative humidity (operation)
≤ 95 % (25°C, non-condensing)
12/11/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2320254
Uninterruptible power supply - QUINT-UPS/ 24DC/ 24DC/
5/1.3AH - 2320254
Technical data
Ambient conditions
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage
24 V DC
Input voltage range
18 V DC ... 30 V DC
Current consumption
9.3 A (24 V DC)
9.7 mA
1.7 A
7A
Buffer period
50 min (1 A)
5 min (5 A)
Output data
Nominal output voltage
24 V DC
Output voltage range
18 V DC ... 30 V DC
Output current
5 A (-25 °C ... 60 °C)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in series
No
Output fuse
1x 15 A
General
IQ technology
Yes
Disposal
Used batteries must not be thrown away with household waste, they
should instead be disposed of in accordance with applicable national
regulations. They can also be returned to Phoenix Contact or the
manufacturer.
Net weight
2.2 kg
Memory medium
Lead rechargeable battery module 1.3 Ah
Efficiency
> 97.1 % (Mains operation, with charged power storage)
97.31 %
Protection class
III
> 806000 h (40°C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: horizontal 5 mm, vertical 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
EN 61558-2-17
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
12/11/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2320254
Uninterruptible power supply - QUINT-UPS/ 24DC/ 24DC/
5/1.3AH - 2320254
Technical data
General
UL approvals
UL/C-UL Recognized UL 60950
UL Listed UL 508
Connection data, input
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
12
Stripping length
7 mm
Screw thread
M4
Connection data, output
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
12
Stripping length
7 mm
Signaling
Signalization designation
Power In OK
Status display
LED
Note on status display
Static to
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Screw thread
M4
Signalization designation
Alarm
12/11/2014 Page 3 / 5
https://www.phoenixcontact.com/us/products/2320254
Uninterruptible power supply - QUINT-UPS/ 24DC/ 24DC/
5/1.3AH - 2320254
Technical data
Signaling
Output name
Switching output
Output description
Relay
Output voltage
≤ 30 V AC/DC
Continuous load current
≤ 100 mA
Status display
LED
Note on status display
Static to
Signalization designation
Battery charge
Output name
Switching output
Output description
Relay
Output voltage
≤ 30 V AC/DC
Continuous load current
≤ 100 mA
Status display
LED bar graph
Note on status display
dynamic
Signalization designation
Battery mode
Output name
Switching output
Output description
Relay
Type of signaling
Battery mode
Output voltage
≤ 30 V AC/DC
Continuous load current
≤ 100 mA
Status display
LED
Note on status display
Static to
Classifications
eCl@ss
eCl@ss 4.0
27040702
eCl@ss 4.1
27040702
eCl@ss 5.0
27242213
eCl@ss 5.1
27040603
eCl@ss 6.0
27040603
eCl@ss 7.0
27040603
eCl@ss 8.0
27049201
ETIM
ETIM 3.0
EC001039
ETIM 4.0
EC000382
12/11/2014 Page 4 / 5
https://www.phoenixcontact.com/us/products/2320254
Uninterruptible power supply - QUINT-UPS/ 24DC/ 24DC/
5/1.3AH - 2320254
Classifications
ETIM
ETIM 5.0
EC000382
UNSPSC
UNSPSC 6.01
30211510
UNSPSC 7.0901
39121011
UNSPSC 11
39121011
UNSPSC 12.01
39121011
UNSPSC 13.2
39121011
Drawings
Block diagram
Input
DC 24V
Output
DC 24V
Data-Port
13
Confirm
14
23
mC
tmax[min]
I < IN
Battery
DC 24V
J
J
24
33
34
R1
24V 0.2A
Alarm
Bat.Mode
Bat.Charge
Remote
R2
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
12/11/2014 Page 5 / 5
Item # 10
https://www.phoenixcontact.com/us/products/2320089
Assembly adapters - UTA 107/30 - 2320089
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Universal DIN rail adapter
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
77.0 GRM
Custom tariff number
79070000
Country of origin
Thailand
Technical data
Dimensions
Width
30 mm
Height
107 mm
Depth
9.6 mm
General
Housing material
Steel
Classifications
eCl@ss
eCl@ss 4.0
27040801
eCl@ss 4.1
27040801
eCl@ss 5.0
27049090
eCl@ss 5.1
27049090
eCl@ss 6.0
27049090
eCl@ss 7.0
27049090
eCl@ss 8.0
27049290
12/11/2014 Page 1 / 2
https://www.phoenixcontact.com/us/products/2320089
Assembly adapters - UTA 107/30 - 2320089
Classifications
ETIM
ETIM 3.0
EC001039
ETIM 4.0
EC001597
ETIM 5.0
EC002625
UNSPSC
UNSPSC 6.01
30211502
UNSPSC 7.0901
39121004
UNSPSC 11
39121004
UNSPSC 12.01
39121004
UNSPSC 13.2
39121004
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
12/11/2014 Page 2 / 2
Item # 11, 12, 13, 14, 15
Relays
Selection Guide
Selection Guides
General Purpose Relays
RU Series
RR Series
RH Series
RM Series
RY Series
Appearance
Page
E-3
E-10
E-16
E-19
2, 4 Form C
1, 2, 3 Form C
1, 2, 3, 4 Form C
2 Form C
2, 4 Form C
Contact Rating
(resistive)
DPDT: 10A, 30V DC
10A, 250V AC
4PDT: 6A, 30V DC
6A, 250V AC
10A, 30V DC
10A, 120V, 240V AC
1/3HP, 240V AC
1/4HP, 120V AC
10A, 30V DC
10A, 120V, 240V AC
1/3HP, 240V AC
1/6HP, 120V AC
5A, 30V DC
5A, 120V AC, 240V AC
DPDT: 3A, 30V DC;
3A, 120V AC, 240V AC
4PDT: 5A, 30V DC;
5A, 120V AC, 240V AC
Silver
Silver-cadmium
oxide
Silver
DPDT
E
E-6
Contact Configuration
Contact Material
4PDT
AuSnOIn (silver tin
oxide indium)
AuAg/Ag (goldsilver alloy on silver)
General Purpose Latching Relays
RR2KP Series
Standard
Silver, gold-plated
Bifurcated
Silver-paladium
alloy (Ag-PD Alloy)
RH2L Series
RY2KS Series
RY2L Series
E-26
E-29
E-32
Appearance
Page
Contact Configuration
E-23
2 Form C
2 Form C
2 Form C
2 Form C
Contact Rating
(resistive)
10A, 30V DC
10A, 120V AC
10A, 30V DC
7.5A, 240V AC
10A, 120V AC
3A, 30V DC
3A, 120V AC
3A, 30V DC
3A, 120V AC
3A, 240V AC
Contact Material
Silver
Silver-cadmium oxide
Silver, gold-plated
Silver, gold-flashed
Solid State Relays
RSS Series
Appearance
Page
E-35
Contact Configuration
1 Form A (SPST-NO)
Contact Rating
10, 25, 50, 75, 90A
48V AC to 660V AC Output Ratings
Output
Dual SCR (zero crossing)
E-2
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
Relays
RH Series
RH Series — General Purpose Midget Relays
Key features of the RH series include:
• Compact midget size saves space
• High switching capacity (10A)
• Choice of blade or PCB style terminals
• Relay options include indicator light, check button, and top
mounting bracket
• DIN rail, surface, panel, and PCB type sockets
available for a wide range of mounting applications
Specifications
E
E-10
Contact Material
Silver cadmium oxide
Contact Resistance
50mΩ maximum (initial value)
Minimum Applicable
Load
24V DC/30mA, 5V DC/100mA
(reference value)
Operating Time
SPDT (RH1), DPDT (RH2): 20ms maximum
3PDT (RH3), 4PDT (RH4): 25ms maximum
Release Time
SPDT (RH1), DPDT (RH2): 20ms maximum
3PDT (RH3), 4PDT (RH4): 25ms maximum
Maximum Continuous
Applied Voltage
(AC/DC) at 20°C
110% of the rated voltage
Minimum Operating
Voltage (AC/DC) at 20°C
80% of the rated voltage
Drop-Out Voltage (AC)
30% or more of the rated voltage
Drop-Out Voltage (DC)
10% or more of the rated voltage
Power
Consumption
SPDT (RH1): DC: 0.8W
AC: 1.1VA (50Hz), 1VA (60Hz)
DPDT (RH2): DC: 0.9W
AC: 1.4VA (50Hz), 1.2VA (60Hz)
3PDT (RH3): DC: 1.5W
AC: 2VA (50Hz), 1.7VA (60Hz)
4PDT (RH4): DC: 1.5W
AC: 2.5VA (50Hz), 2VA (60Hz)
Insulation Resistance
UL Recognized
Files No. E67770
E59804
CSA Certified
File No.LR35144
File No. BL951113332319
Ordering Information
Order standard voltages for fastest delivery. Allow extra delivery time for
non-standard voltages.
Basic Part No.
RH2B-U
Coil Voltage:
–
AC110-120V
100MΩ min (measured with a 500V DC megger)
SPDT (RH1)
Between live and dead parts: 2,000V AC, 1
minute; Between contact circuit and operating coil: 2,000V AC, 1 minute;
Between contacts of the same pole: 1,000V
AC, 1 minute
Dielectric Strength
DPDT (RH2), 3PDT (RH3), 4PDT (RH4)
Between live and dead parts: 2,000V AC, 1
minute; Between contact circuit and operating coil: 2,000V AC, 1 minute;
Between contact circuits: 2,000V AC,
1 minute; Between contacts of the same
pole: 1,000V AC, 1 minute
Frequency Response
1,800 operations/hour
Temperature Rise
Coil: 85°C maximum
Contact: 65°C maximum
Vibration Resistance
0 to 6G (55Hz maximum)
Shock Resistance
SPDT/DPDT: 200N (approximately 20G)
3PDT/4PDT: 100N (approximately 10G)
Life Expectancy
Electrical: over 500,000 operations at 120V
AC, 10A; (over 200,000 operations at 120V
AC, 10A for SPDT [RH1], 3PDT [RH3], 4PDT
[RH4])
Mechanical: 50,000,000 operations
Operating Temperature
–30 to +70°C
Weight
SPDT: 24g, DPDT: 37g (approximately)
3PDT: 50g, 4PDT: 74g (approximately)
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
Relays
RH Series
Part Numbers
Part Numbers: RH Series with Options
Termination
B
(blade)
V2
(PCB 0.078"
[2mm] wide)
Contact Configuration
Indicator Light
Check Button
Indicator Light and Check Button Top Bracket
SPDT
Basic Part No.
RH1B-U
RH1B-L*
—
—
RH1B-UT
DPDT
RH2B-U
RH2B-UL
RH2B-UC
RH2B-ULC
RH2B-UT
3PDT
RH3B-U
RH3B-UL
RH3B-UC
RH3B-ULC
RH3B-UT
4PDT
RH4B-U
RH4B-UL
RH4B-UC
RH4B-ULC
RH4B-UT
SPDT
RH1V2-U
RH1V2-L*
—
—
—
DPDT
RH2V2-U
RH2V2-UL
RH2V2-UC
RH2V2-ULC
—
3PDT
RH3V2-U
RH3V2-UL
RH3V2-UC
RH3V2-ULC
—
4PDT
RH4V2-U
RH4V2-UL
RH4V2-UC
RH4V2-ULC
—
* RH1B(V2)-L is not UL recognized.
Ratings
E
Coil Ratings
Rated Current ±15% at 20°C
Rated Voltage
AC
6V
12V
24V
120V*
240V†
DC
6V
12V
24V
48V
110V‡
60Hz
Coil Resistance ±15% at 20°C
50Hz
SPDT
DPDT
3PDT
4PDT
SPDT
DPDT
3PDT
4PDT
SPDT
DPDT
3PDT
150mA
75mA
37mA
7.5mA
3.2mA
200mA
100mA
50mA
11mA
5.5mA
280mA
140mA
70mA
14.2mA
7.1mA
330mA
165mA
83mA
16.5mA
8.3mA
170mA
86mA
42mA
8.6mA
3.7mA
238mA
118mA
59.7mA
12.9mA
6.5mA
330mA
165mA
81mA
16.4mA
8.2mA
387mA
196mA
98mA
19.5mA
9.8mA
18.8Ω
76.8Ω
300Ω
7,680Ω
3,1200Ω
9.4Ω
39.3Ω
153Ω
4,170Ω
15,210Ω
6.0Ω
25.3Ω
103Ω
2770Ω
12,100Ω
4PDT
5.4Ω
21.2Ω
84.5Ω
2220Ω
9120Ω
SPDT
DPDT
3PDT
4PDT
SPDT
DPDT
3PDT
4PDT
128mA
64mA
32mA
18mA
8mA
150mA
75mA
36.9mA
18.5mA
9.1mA
240mA
120mA
60mA
30mA
12.8mA
250mA
125mA
62mA
31mA
15mA
47Ω
188Ω
750Ω
2,660Ω
13,800Ω
40Ω
160Ω
650Ω
2,600Ω
12,100Ω
25Ω
100Ω
400Ω
1,600Ω
8,600Ω
24Ω
96Ω
388Ω
1550Ω
7,340Ω
* For RH2 relays = 110/120V AC.
† For RH2 relays = 220/240V AC.
‡ For RH2 relays = 100/110V DC.
AC
6V
12V
24V
120V*
240V†
DC
6V
12V
24V
48V
110V‡
Coil Inductance
Coil Inrush
Rated Voltage
SPDT
DPDT
3PDT
4PDT
SPDT
250mA
120mA
56mA
12mA
7mA
340mA
170mA
85mA
16mA
8mA
520mA
260mA
130mA
26mA
12mA
620mA
310mA
165mA
33mA
16mA
0.09H
0.037H
1.5H
37H
130H
Energizing
DPDT
3PDT
0.08H
0.30H
1.2H
33H
130H
0.05H
0.22H
0.9H
21H
84H
4PDT
0.05H
0.18H
0.73H
18H
73H
SPDT
0.06H
0.22H
0.9H
22H
77H
De-Energizing
DPDT
3PDT
0.04H
0.16H
0.63H
15H
62H
0.03H
0.12H
0.5H
12H
47H
4PDT
0.02H
0.10H
0.36H
9H
36H
SPDT
DPDT
3PDT
4PDT
SPDT
DPDT
3PDT
4PDT
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
* For RH2 relays = 110/120V AC.
† For RH2 relays = 220/240V AC.
‡ For RH2 relays = 100/110V DC.
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
E-11
Relays
RH Series
Ratings con’t
Contact Ratings
SPDT
Resistive
DPDT 3PDT
4PDT
SPDT
Inductive
DPDT 3PDT
4PDT
Motor Load
SPDT DPDT 3PDT
10A
10A
10A
7.5A
—
7.5A
—
—
—
—
—
—
—
—
—
Voltage
Rating
28V DC
UL
30V DC
UL
CSA
Nominal
10A
Nominal
0.5A
110V DC
UL
CSA
Nominal
UL
CSA
Nominal
120V AC
240V AC
10A
—
10A
10A
0.5A
10A
10A
10A
0.5A
0.5A
10A
10A
7A
7A
7.5A
0.3A
7.5A
0.3A
—
7.5A
7A
10A
10A
—
7.5A
7A
7A
7A
7.5A
7.5A
4.5A
5A
5A
—
—
—
7.5A
7.5A
—
—
—
0.3A
0.3A
—
—
—
1/6
1/6
1/6
—
—
—
1/3
1/3
1/3
—
—
—
—
7.5A
7.5A
*
7A
5A
5A
1. * 6.5A/pole, 20A total.
2. Inductive load cos ø = 0.3, L/R = 7ms.
E
Applicable Sockets
Part Numbers: Sockets
Standard DIN Finger-Safe DIN
Surface Mount
Rail Mount
Rail Mount
Relay
Panel
Mount
—
RH1B
SH1B-05
RH2B
SH2B-05
RH3B
SH3B-05
SH1B-05C
SH1B-51
SH2B-05C
SH2B-02
SH3B-05C
SH1B-62
SH2B-51
SH2B-62
SH3B-51
SH3B-62
—
RH4B
SH4B-05
SH4B-05C
Spring & Clips (optional)
PCB Mount
SH4B-51
SH4B-62
Part Number
Use With
SY2S-02F1
SFA-101
SFA-202
SH1B-05, 05C
SY4S-51F1
SFA-301
SFA-302
SH1B-51, 62
SY4S-02F1
SFA-101
SFA-202
SH2B-05, 05C
SY4S-51F1
SFA-301
SFA-302
SH2B-51, 62
SH3B-05F1
SFA-101, -202
SH3B-05, 05C
SY4S-51F1
SFA-301
SFA-302
SH3B-51, 62
SH4B-02F1
SFA-101, -202
SH4B-05, 05C
SY4S-51F1
SFA-301
SFA-302
SH4B-51, 62
See Section F for details on sockets. All DIN rail mount sockets shown above can be mounted using
DIN rail BNDN1000.
Internal Circuits
1
1
4
1
2
4
1
2
3
5
5
8
5
6
8
5
6
7
4
8
9
9
12
9
10
12
9
10
11
12
13
14
13
14
13
14
13
14
(-)
(+)
(-)
(+)
(-)
(+)
(-)
(+)
RH1
E-12
RH2
www.idec.com
RH3
RH4
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
Relays
RH Series
Electrical Life Curves
RH1
1000
1000
AC 110V Resistive
500
Life (x 10,000) Operations
Life (x 10,000) Operations
500
100
50
DC 30V Resistive
100
50
DC 100V Resistive
DC 30V Inductive
20
20
AC 220V Inductive AC 110V Inductive
10
1
2
3
4
5
6
Load Current (A)
AC 220V Resistive
7
8
9
DC 100V Inductive
10
10
1
2
3
AC 220V Resistive
4
5
6
7
8
9
10
Load Current (A)
E
RH2
1000
1000
AC 110V Resistive
DC 30V Resistive
500
Life (x 10,000) Operations
Life (x 10,000) Operations
500
100
50
50
AC 220V Resistive
AC 110V Inductive
AC 220V Inductive
DC 30V
Inductive
DC 100V Resistive
DC 100V Inductive
20
20
10
100
1
2
3
4
5
6
7
Load Current (A)
8
9
10
10
1
2
3
4
5
6
7
Load Current (A)
8
9
10
8
9
10
RH3 and 4
1000
1000
AC 110V Resistive
100
50
20
DC 30V Inductive
100
50
20
AC 220V Inductive AC 220V Resistive
AC 110V Inductive
10
DC 30V Resistive
500
Life (x 10,000) Operations
Life (x 10,000) Operations
500
1
2
www.idec.com
3
4
5
6
7
Load Current (A)
8
9
10
DC 100V Resistive
DC 100V Inductive
10
1
2
3
4
5
6
7
Load Current (A)
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
E-13
Relays
RH Series
Dimensions
Top Bracket Mounting
Blade Terminal
RH1B-UT
0.39"
RH2B-UT
(10mm)
0.183"
(4.7mm)
Ø 0.101" (2.6mm)
0.257"
0.566"
(14.5mm)
1.39" (35.6mm)
or Less
0.183"
(2mm)
(3.5mm)
0.211"
(5.4mm)
0.25"
0.839"
(21.5mm)
1.39" (35.6mm)
or Less
1.07" (27.5mm)
1.48" (38mm)
0.293"
(7.5mm)
(4.7mm)
0.137"
0.25"
(6.4mm)
(6.4mm)
Plug-in
Blade Terminal
RH1B
RH2B
Total length from panel surface including socket:
SH1B-05: 2.40" (61.5mm) maximum; SH1B-51: 1.54" (39mm) maximum
Total length from panel surface including hold-down spring:
SH1B-05: 2.48" (63.5mm) maximum; SH1B-51: 1.62" (41.6mm) maximum
E
(5.9mm)
0.078"
(2mm)
(3.5mm)
0.23"
(6.6mm)
0.078"
0.137"
(4.7mm)
(0.5mm)
1.68" (43.2mm)
0.23"
(5.9mm)
0.185"
0.019"
1.07" (27.5mm)
(4.7mm)
(0.5mm)
1.48" (38mm)
1.68" (43.2mm)
0.019"
Ø 0.101" (2.6mm)
0.185"
Total length from panel surface including socket:
SH2B-05: 2.40" (61.5mm) maximum; SH2B-51: 1.54" (39.6mm)
Total length from panel surface including hold-down spring:
SH2B-05: 2.48" (63.5mm) maximum; SH2B-51: 1.62" (41.6mm)
0.183"
(4.7mm)
(0.5mm)
0.211"
(5.4mm)
1.39" (35.6mm)
or less
0.019"
(0.5mm)
1.07" (27.5mm)
0.019"
0.25"
0.183"
(4.7mm)
0.819" (21mm)
0.546"
(6.4mm)
1.07" (27.5mm)
Ø 0.101" (2.6mm)
Ø 0.101" (2.6mm)
(14mm)
Plug-in
Blade Terminal
RH3B
Total length from panel surface including socket:
SH3B-05: 2.57" (66mm) maximum
Total length from panel surface including hold-down spring:
SH3B-05: 2.65" (68mm) maximum
1.39" (35.6mm) 0.25"
or less
(6.4mm)
RH4B
Total length from panel surface including socket:
SH4B-05: 2.40" (61.5mm) or less; SH4B-51: 1.54" (39.6mm)
Total length from panel surface including hold-down spring:
SH4B-05: 2.48" (63.5mm) or less; SH4B-51: 1.62" (41.6mm)
0.183"
0.183"
(4.7mm)
(4.7mm)
1.39" (35.6mm) or Less
Ø 0.101" (2.6mm)
0.019" (0.5mm)
1.21" (31mm)
0.25"
(6.4mm)
1.39" (35.6mm) or less
E-14
www.idec.com
1.07" (27.5mm)
0.25"
(6.4mm)
1.07" (27.5mm)
Ø 0.101" (2.6mm)
0.019" (0.5mm)
1.60" (41mm)
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
Item # 16
Bulletin 800T/H
30.5 mm Push Buttons
Pilot Lights
Pilot Light Devices1
0
Transformer Type Pilot Light
Cat. No. 800T-P16R
Push-to-Test Pilot Light
Cat. No. 800T-PT16R
1
Type
2
Lamp Type
Volts
Operator Only
Full Voltage‡
Color
Incandescent
24V AC/DC
No Lamp
0…250V AC/DC
LED
12…130 V AC/DC
Universal‡
3
Incandescent
4
120V AC,
50/60 Hz
Transformer‡
LED
No Lamp
5
Type 4/13
Pilot Light
Push-to-Test1
Cat. No.
Cat. No.
800T-SB00XX
800T-S00
800T-Q24R
800T-QT24R
800T-Q24G
800T-QT24G
800T-Q24A
800T-QT24A
800T-QN25
800T-QTN25
800T-QH2R
800T-QTH2R
800T-QH2G
800T-QTH2G
800T-QH2A
800T-QTH2A
800T-P16R
800T-PT16R
800T-P16G
800T-PT16G
800T-P16A
800T-PT16A
800T-PH16R
800T-PTH16R
800T-PH16G
800T-PTH16G
800T-PH16A
800T-PTH16A
800T-PN16
800T-PTN16
Red
Green
Amber
No Lens
Red
Green
Amber
Red
Green
Amber
Red
Green
Amber
No Lens
1 Includes one standard Cat. No. 800T-XA (1 N.O. - 1 N.C.) contact block. For typical pilot light wiring diagrams, see page 10-65.
Operator only supplied without power module, lamp, lens cap, or contact blocks.
‡ All pilot lights except push-to-test without sealed contacts and dual input transformer relay, are rated for Class 1, Division 2 applications.
6
(Push-to-Test)
800
T
a
7
8
9
– P
T
c
d
b
Code
T
H
Protection Rating
Description
Metal, Type 4/13
Plastic, Type 4/4X/13
b
Code
Blank
C
Finger-Safe Guards
Description
No guards
Guards on terminals
Power Module Type
800T
Type
4/13
Code
P
11
Q
Description
Transformer
(or dual input)
Full voltage/
Universal
e
16
G
f
g
d
a
c
10
800H
Type
4/4X/13
Code
AR
h
f
Lamp Test Options
Code
Description
Blank
No test option
T
Push-to-test
D
Dual input — diode♣
Dual input — transformer
DT
relay
Note: Push-to-test supplied with
factory jumpered contact block.
e
Illumination Options
Code
Description
Blank
Incandescent
H
LED1
PR
QR
Voltage
Transformer
Code
Description
16
120V AC 50/60 Hz
26
240V AC 50/60 Hz
46
480V AC 50/60 Hz
56
600V AC 50/60 Hz
Full Voltage — Incandescent
12
12V AC/DC
24
24V AC/DC
48
48V AC/DC
10
120V AC/DC
20
240V AC/DC
Universal — LED
2
12…130V AC/DC
Dual Input
16
120V AC
24V AC/DC
24
(Dual input diode only)
1 LED illumination option is not available with diode type dual input.
12
Type 4/4X/13
Pilot Light
Push-to-Test1
Cat. No.
Cat. No.
800H-SR00
800H-SRB00XX
800H-QR24R
800H-QRT24R
800H-QR24G
800H-QRT24G
800H-QR24A
800H-QRT24A
—
—
800H-QRH2R
800H-QRTH2R
800H-QRH2G
800H-QRTH2G
800H-QRH2A
800H-QRTH2A
800H-PR16R
800H-PRT16R
800H-PR16G
800H-PRT16G
800H-PR16A
800H-PRT16A
800H-PRH16R
800H-PRTH16R
800H-PRH16G
800H-PRTH16G
800H-PRH16A
800H-PRTH16A
—
—
♣ Diode type dual input provides circuit isolation via opposing diodes. Not
recommended for use with solid-state outputs.
♠ Glass lens available on 800T pilot lights only. Not available on push-to-test
units.
13
www.ab.com/catalogs
10-20
Preferred availability cat. nos. are bold.
Publication A117-CA001A-EN-P
g
Lens Color
Code
Color
Blank
A
B
C
G
R
W
No lens
Amber
Blue
Clear
Green
Red
White
Glass
Code
♠
Blank
D
E
F
H
J
K
h
Contact Blocks
(Push-to-test units only)
Code
Description
Standard
Blank
1 N.O. - 1 N.C.
PenTUFF (Low Voltage)
AV
1 N.O. - 1 N.C.
Class 1, Div. 2/Zone 2
Logic Reed
AR
1 N.O. - 1 N.C.
Sealed Switch
AP
1 N.O. - 1 N.C.
Stackable Sealed Switch
AY
1 N.O. - 1 N.C.
Bulletin 800T/H
30.5 mm Push Buttons
Specifications
Specifications1
Electrical Ratings
Refer to the contact ratings tables on page 10-4.
2200V for one minute, 1300V for one minute (Logic Reed)
1 000 000 at max. rated load, 200 000 at max. rated load (Logic Reed)
Contact ratings
Dielectric strength
Electrical design life cycles
Mechanical Ratings
10…2000 Hz, 1.52 mm displacement (peak-to-peak) max./
10 G max. (except Logic Reed)
1/2 cycle sine wave for 11 ms ≥ 25 G (contact fragility) and no damage at 100 G
Type 1/4/12/13 (800T); Type 1/4/4X/12/13 (800H); EN/IEC 60529 IP66/65
Vibration
Shock
Degree of protection
Mechanical design life cycles
Push buttons
Selector switches
0
(Momentary, non-illuminated)
(Momentary, illuminated)
(Push-pull/twist-to-release)
(Non-illuminated)
(Illuminated, key-operated)
1
10 000 000 min.
250 000 min.
250 000 min.
1 000 000 min.
200 000 min.
25 000 min.
200 000 min.
Shallow, mini, and low-voltage contact blocks: Slow, double make and break
Logic Reed and sealed switch contact blocks: Single break magnetic
#18…14 AWG (#18…10 Max Duty) / 6…8 lb•in
Potentiometers
All other devices
Contact operation
Wire gauge/Terminal screw torque
Typical operating forces
2
3
Flush, extended button, standard mushroom, jumbo plastic mushroom: 2 lbs max.
Jumbo and extended aluminum mushroom head: 3.95 lbs max.
Maintained selector switch: 3.6 in•lb max.
3.6 in•lb to stop, 0.2 in•lb to return
5 lb max.
8.0 lb max. push or pull
8 lb max. push to in position or pull to center position (15 lb max. pull to out position)
9 lbs max. push or pull 30 in•oz max. twist, 6 in•oz minimum return
Rotational torque 3…12 in•oz; stopping torque 12 in•lb (minimum)
1 lb
1 lb max.
3 lb max. at 0.205 in. plunger travel
1 lb max.
1.4 lb max.
1.4 lb max.
1.6 lb
Environment
-40…+131 °F (-40…+55 °C)
-40…+185 °F (-40…+85 °C)
Operators without contact blocks
Spring return selector switches
Illuminated push buttons and push-to-test pilot lights
2-position push-pull
3-position push-pull
Twist-to-release or push-pull
Potentiometer
Standard
Logic Reed
Sealed switch
Contact blocks
Stackable sealed switch
MaxDuty
PenTUFF
Self Monitoring
Operating
Storage
Note: Operating temperatures below freezing are based on
the absence of moisture and liquids. Consult your local
Rockwell Automation sales office or Allen-Bradley
distributor for use in lower temperature applications.
Temperature range
50…95% RH from 77…140 °F (25…60 °C) per Procedure IV of MIL-STD-810C,
Method 507.1 cycling test
Humidity
4
5
6
7
8
9
1 Performance Data — See Important- 3.
10
11
12
13
www.ab.com/catalogs
Preferred availability cat. nos. are bold.
Publication A117-CA001A-EN-P
10-3
01_800TH.qxd
4/23/2008
1:48 PM
Page 10-7
Item # 17
Bulletin 800T/H
30.5 mm Push Buttons
Push Button Operators
Momentary Contact Push Button Units, Non-Illuminated
!
Flush Head Unit
Cat. No. 800T-A1A
Extended Head Unit
Cat. No. 800T-B6A
Booted Unit
Cat. No. 800H-R2A
Bootless Flush Head Unit
Cat. No. 800H-AR1A
Type 4/13
Contact Type
No Contact
1 N.O.
1 N.C.
1 N.O. - 1 N.C.
1
Type 4/4X/13
Booted9
Bootless
Flush Head
Button
Color
Flush Head
Extended Head
Cat. No.
Cat. No.
Cat. No.
Cat. No.
Green
800T-A1
800T-B1
800H-R1
800H-AR1
Black
800T-A2
800T-B2
800H-R2
800H-AR2
Red
800T-A6
800T-B6
800H-R6
800H-AR6
Green
800T-A1D1
800T-B1D1
800H-R1D1
800H-AR1D1
Black
800T-A2D1
800T-B2D1
800H-R2D1
800H-AR2D1
Red
800T-A6D1
800T-B6D1
800H-R6D1
800H-AR6D1
Green
800T-A1D2
800T-B1D2
800H-R1D2
800H-AR1D2
Black
800T-A2D2
800T-B2D2
800H-R2D2
800H-AR2D2
Red
800T-A6D2
800T-B6D2
800H-R6D2
800H-AR6D2
Green
800T-A1A
800T-B1A
800H-R1A
800H-AR1A
Black
800T-A2A
800T-B2A
800H-R2A
800H-AR2A
Red
800T-A6A
800T-B6A
800H-R6A
800H-AR6A
2
3
4
5
800
T
a
a
Code
T
H
Protection Rating
Description
Metal, Type 4/13
Plastic, Type 4/4X/13
b
Code
Blank
C
Finger-Safe Guards
Description
No Guards
Guards on Terminals
c
Operator Type
800T
800H
Type
Type
Description
4/13
4/4X/13
Code
Code
A
Flush Head
AR
B
Extended Head
BR
D
Mushroom Head
DR
Mushroom Head
DX
DRX
less Color Cap
Bootless
—
Guarded
GR
Head
—
Booted Head
R9
d
Code
Blank
1
2
3
Color Cap
Description
Used only when ordering
Operator Type DX/DRX
Green
Black
Orange7
– A
1
c
d
b
d (cont'd)
Code
4
5
6
7
9
Color Cap
Description
Gray7
White7
Red
Blue
Yellow
e
Special Mushroom Head
Code
Description
Jumbo Mushroom Head —
J§
Plastic
Jumbo Mushroom Head —
L§
Metal
Note: Special Mushroom Head
options only apply to
Mushroom Head operator
Type Code D/DR.
f
Code
Blank
D1
D2
D3
D4
D5
D6
A1
A2
A4
A7
A
B
Contact Block(s)
Description
No Contacts
Standard
1 N.O.
1 N.C.
1 N.O.E.M.
1 N.C.L.B.
1 N.O. (Mini)
1 N.C. (Mini)
1 N.C.L.B. - 1 N.O.
2 N.O.‡
2 N.C.
1 N.C.L.B. - 1 N.C.
1 N.O. - 1 N.C.
2 N.O. - 2 N.C.
A
e
f (cont'd)
Contact Block(s)
Code
Description
PenTUFF (Low Voltage)
D1V
1 N.O.
D2V
1 N.C.
D3V
1 N.O.E.M.
D4V
1 N.C.L.B.
AV
1 N.O. - 1 N.C.
BV
2 N.O. - 2 N.C.
Time Delay
1 N.O.
T
Depress close, delayed
opening
1 N.C.
S
Depress open, delayed
closure
Snap Action
M
1 N.O. - 1 N.C.
N
2 N.O. - 2 N.C.
Class 1, Div. 2/Zone 2
Logic Reed
D1R
1 N.O.
D2R
1 N.C.
A2R
2 N.O.‡
A4R
2 N.C.
AR
1 N.O. - 1 N.C.
BR
2 N.O. - 2 N.C.
f
6
f (cont'd)
Contact Block(s)
Code
Description
Class 1, Div. 2/Zone 2
Sealed Switch
D1P
1 N.O.
D2P
1 N.C.
A2P
2 N.O.
A4P
2 N.C.
AP
1 N.O. - 1 N.C.
BP
2 N.O. - 2 N.C
Stackable Sealed Switch
D1Y
1 N.O.
D2Y
1 N.C.
A2Y
2 N.O.
A4Y
2 N.C.
AY
1 N.O. - 1 N.C.
BY
2 N.O. - 2 N.C
Time Delay Contacts
Series C field installable kits can
only be used with Series T or later
operators. Adjustable range of 0.5
to 15 s + 25%. Maximum
continuous current Ith 5 A.
Snap Action Contacts
Snap action contacts feature a
quick make, quick break snapaction mechanism that is only
available on factory assembled
units. Maximum continuous current
Ith 10 A.
7
8
9
10
11
12
9 Underlying operators are "flush head" type, except red which are "extended
head". Boot material is hyplon with brass threaded insert.
7 Not available for booted operators.
‡ A2 and A2R contact blocks cannot be stacked upon, but can stack on
other contact blocks.
§ Jumbo mushroom heads not available in white color.
Visit our website: www.ab.com/catalogs
Preferred availability cat. nos. are printed in bold
10-7
13
Bulletin_800T_800H_d.qxd
30/01/2004
15:00
Page 10-79
Item # 18
Bulletin 800T/800H
30.5 mm Push Buttons
Accessories
Αχχεσσοριεσ
Contact Blocks
Packaged in kit form for field installation. All necessary mounting hardware is provided with each contact block kit. Contact ratings are
listed on page 10-52.
Note: It is not recommended to mount more than four contact blocks on any one non-illuminated operator, (maximum two blocks deep).
Contact blocks cannot be stacked onto power modules, so illuminated operators are limited to two contact blocks. Sealed switch
contact blocks are not stackable, and are limited to two blocks per operator. Time delay contacts are only available as one circuit per
operator.
Shallow Block
Contact Type
1 N.O.
1 N.C.
1 N.O.E.M.
1 N.C.L.B.
1 N.O. - N.C.
2 N.O.
2 N.C.
1 N.C.L.B. - 1 N.O.
1 N.C.L.B. - 1 N.C.
PenTUFF (Low Voltage)
Contact Block
Shallow Block✶†
Cat. No.
800T-XD1
800T-XD2
800T-XD3
800T-XD4
800T-XA
800T-XA2§
800T-XA4
800T-XA1
800T-XA7
PenTUFF
(Low Voltage) Block✶†
Cat. No.
800T-XD1V
800T-XD2V
800T-XD3V
800T-XD4V
800T-XAV
—
—
—
—
Logic Reed
Block‡
Cat. No.
800T-XD1R
800T-XD2R
—
—
800T-XAR
800T-XA2R§
800T-XA4R
—
—
Mini Block
Self Monitoring Contact Block
Contact Type
1 N.C.L.B.
(wired in series with 1 N.O. monitoring contact)
Sealed Switch Block
Logic Reed Block
S.M.C.B.✶➤
Cat. No.
800TC-XD4S
Contact Type
1 N.O.
1 N.C.
1 N.C.L.B.
Stackable Sealed Switch
Block
Sealed
Switch Block‡
Cat. No.
800T-XD1P
800T-XD2P
—
—
800T-XAP
—
—
—
—
Time Delay Block
Mini Block✶
Cat. No.
800T-XD5
800T-XD6
—
Time Delay
Block♣
Cat. No.
800T-XT
800T-XS
—
Stackable Sealed
Switch Block‡
Cat. No.
800T-XD1Y
800T-XD2Y
—
—
800T-XAY
800T-XA2Y
800T-XA4Y
—
—
MaxDuty Block
MaxDuty Block
Cat. No.
800T-XD1M
800T-XD2M
800T-XD4M
✶ Contact blocks with normally closed contacts meet direct drive positive opening standard requirements when properly fused to IEC 269-1 and 269-2.
Shallow/mini contacts: 10 A gl or N type cartridge fuse. PenTUFF contacts: 6 A gl or N type cartridge fuse.
† Specify Bulletin 800TC for finger-safe contact blocks. Example: Cat. No. 800T-XA becomes Cat. No. 800TC-XA.
‡ 800T operator using sealed switch and logic reed contact blocks and installed in a suitable enclosure are UL Listed as suitable for use in Class I, Division
2/Zone 2 hazardous locations.
§ Additional contacts cannot be stacked on XA2 and XA2R contact blocks.
♣ For contact ratings, see page 10-51.
➤ For use with 2-position push-pull or push-pull/twist operators only. Must be mounted on the first level of the operator. The N.O. monitoring contact
automatically closes when the S.M.C.B. is properly installed onto the operator. If the S.M.C.B. is separated from the operator, the N.O. monitoring contact
automatically opens.
Shallow Contact Block Hardware
Cat. No.
800T-N335
800T-N336
800T-N337
Description
Contact Block Mounting Screw
Screw Retainer
Actuator Extender
Visit our website: www.ab.com/catalogs
10-79
Item # 19
FEDERAL SIGNAL CORPORATION
Vibratone ® Horns
Models 350 and 450
The Models 350 and 450 Vibratone Horns produce a very loud
horn tone by the electro-mechanical vibration of a diaphragm.
Capable of reproducing coded blasts or sustained tones, Federal
Signal’s Vibratone horn is excellent for general alarm, start and dismissal, coded paging, and process control signaling in areas of
high ambient noise levels.
DESIGNED FOR ROUTINE
SIGNALING
•
Range of up to 200 feet (61m)
•
Coded or sustained tones
•
Model 350 – 12, 24, 120 and
240VAC; Model 450 – 12, 24, 125
and 250VDC
•
Model 350 produces 100dB at 10’
(110dB at 1 m); Model 450 produces 99dB at 10’ (109dB at 1 m)
•
UL and cUL Listed, CSA Certified,
FM Approved
•
Type 4X when installed with Panel
Mount Gasket Kit or Weatherproof
Backbox (Model WB); Type 4X and
Type 12 when installed with
Surface Mount Trim Ring (Model
TR)
The Vibratone Model 350 is available in AC voltages; 12VAC,
24VAC, 120VAC and 240VAC. The Model 350 produces 100dB @
10’, except the 12VAC model, which produces 94dB @ 10’.
The Model 450 is available in DC voltages; 12VDC, 24VDC,
125VDC and 250VDC. The Model 450 produces 99dB @ 10’.
Vibratone mounting options provide for surface, flush or semiflush mounting on walls, panels, in cabinets, on 4-inch square outlet boxes, or in concrete and deep wall constructions.
Installed on the front of a Vibratone Horn, the optional Model PR
Projector or Model PR2 Double Projector direct sound output
straight ahead or to the sides, optimizing sound output for long,
narrow rooms or corridors.
Vibratone horns are UL Listed, cUL Listed, CSA Certified and FM
Approved. They are designed and approved for use in Type 4X
applications when installed with the Panel Mount Gasket Kit or
Weatherproof Backbox (Model WB). They are approved for Type
4X and Type 12 applications when installed with the Surface Mount
Trim Ring (Model TR, illustrated on page 124).
Each Vibratone horn is enclosed in a zinc die-cast housing and
sealed with grey powder-coat paint. The Model 350 features a
stainless steel diaphragm. The Model 450 utilizes an aluminum
diaphragm and heavy duty contacts. The rugged construction of
the Vibratone horns resists vandalism and the effects of harsh
industrial environments.
Compact size, loud output and heavy-duty construction make the
VibraTone horns ideal for industrial and institutional signaling
applications.
Model
Voltage
Operating
Current
Decibels @
10'
1m
350
350
350
350
450
450
450
450
12VAC 50/60Hz
24VAC 50/60Hz
120VAC 50/60Hz
240VAC 50/60Hz
12VDC
24VDC
125VDC
250VDC
0.90 amps
0.90 amps
0.18 amps
0.09 amps
0.50 amps
0.25 amps
0.05 amps
0.03 amps
94
100
100
100
99
99
99
99
104
110
110
110
109
109
109
109
FB
VIBRATONE ® HORNS (350/450)
PR
FG
FB
350
SF
350
350
PR
FG
350
N
B
350
2
TR
PR
350
PR2
NB
350
290A2450-02
WB
HOW TO ORDER
OPTIONS
®
FB
Wall box for flush mounting the Vibratone horn in stud, 4" block, or
other shallow wall construction; 43/8" square box; 27/8" deep; shipping weight 2 lbs.
(0.91 kg)
FBL
Same as FB, but 313/16" deep for 6" x 8" concrete block, cinder block or other deep
wall construction; shipping wt. 3 lbs. (1.36 kg)
FG
Flush grille which attaches to the basic unit and serves as the cover of the plastered-in FB flush box; 6" H x 6" W x 1/8" D; shipping wt. 1 lb. (0.45 kg)
K8435666A
Optional Panel Mounting Gasket Kit includes a gasket and hardware for surface or
flush mounting the horn for NEMA Type 4 applications.
1
NB
4" square box with / " & / " knockouts for interior mountings; 1 / " deep; shipping
weight 1 lb. (0.45 kg)
PR
Projector which concentrates sound into a basic area when attached to the basic
model 350/450 units; 4" H x 4" W x 6" D; shipping weight 1 lb. (0.45 kg)
PR2
Double projector directs sounds to both sides when attached to the basic model
350/450 units; ideal for use in hallways; 4" H x 111/2" W x 4" D; shipping weight 2
lbs. (0,91 kg)
SF
Stamped surface plate used for installations on plastered-in 4" outlet switch boxes
for semi-flush mountings; 6"H x 6" W x 1/2" D; shipping
weight 1 lb. (0.45 kg)
TR
Gasketed trim ring allowing surface mount installations of 350/450 units while
maintaining Type12 and Type4X rating of enclosure.
WB
Cast aluminum neoprene-gasketed weatherproof housing for outside use, complete with mounting lugs; tapped for 1/2", 3⁄4” conduit; 43/8" square box; 2" deep
mounting lugs on 41/2" centers; shipping weight 1 lb. (0.45 kg)
S P E C I F I C AT I O N S
Operating Temp.:
Net Weight:
Shipping Weight:
Height:
Width:
Depth:
2
3
1
4
-65°F to 150°F
1.4 lbs.
1.5 lbs.
4.0"
4.0"
2.5"
2
• Specify model and voltage
• Specify options from list
• Please refer to Model Number Index
350/450 beginning on page 378
R E P L A C E M E N T PA RT S
Description
Panel Mount Gasket Kit
Coil (120VAC only)
Volume Control Kit
Part Number
K8435666A
KFC1516C
K8435663B
-54°C to 66°C
0.6 kg
0.7 kg
102 mm
102 mm
64 mm
2645 Federal Signal Dr., University Park, IL 60466 Tel: 708.534.4756
Fax: 708.534.4852
www.federalsignal-indust.com
113
Item # 20
FEDERAL SIGNAL CORPORATION
StreamLine ®
Low Profile
Strobe Light
Models LP3P, LP3S, LP3T
Federal Signal introduces the Model LP3 low profile strobe light.
This Type 4X strobe is available in five colors: amber, blue, clear,
green and red.
PERFECT SIZE MEETS
SUPERIOR PERFORMANCE!
•
Surface mount, T-mount, or
integrated 1/2-inch pipe mount
•
Five dome colors
•
Screw-on lens
•
Low profile — Model LP3S
is only 5" high
•
The LP3 is offered in three mounting configurations. LP3P features an integrated 1/2-inch NPT pipe mount. LP3S features a
three-hole surface mount — ideal for control panels and other flat
or flush surfaces. The “T-mount” LP3T has a popular 2-hole
design for wall or flush mounting.
Both the LP3S and LP3T include a surface gasket to complete the
Type 4X installation. An optional dome guard is available for use
with the LP3S and LP3T. All LP3 units feature a threaded screwon lens that provides tool-free wiring and strobe tube replacement. The strobe tube is rated for 7,000 hours.
The LP3 comes in three voltage variations: 12-48VDC, 120VAC
and 240VAC. The state-of-the-art strobe mechanism produces 2.2
joules of energy, while drawing relatively low level amperage.
Available in 12-48VDC, 120VAC
and 240VAC
•
Type 4X, IP66 enclosure
•
PLC and triac compatible
•
UL and cUL Listed, CSA Certified,
CE pending
1
2
StreamLine® strobes feature high-quality, long-life strobe lamps
which are designed to reduce tungsten build-up for longer lamp
maintenance cycles. Careful consideration is given to the relationship between lamp shape and lens design for maximum light output. StreamLine products make use of surface mount technology,
which provides a more powerful light in a much smaller package.
The dry-electrolyte capacitor used in StreamLine products runs
cooler than those used in many competitive strobes, resulting in a
more reliable product that won’t fail due to overheating.
Model
Voltage
Operating
Current
Flash Rate/
Minute
Joule
Output
Candlepower
ECP2
Peak1
LP3
12-48VDC
0.44-0.10 amps
65-95
2.2
175,000
51.5
LP3
120VAC
0.10 amps
65-95
2.2
175,000
51.5
LP3
240VAC
0.07 amps
65-95
2.2
175,000
51.5
Peak candlepower is the maximum light intensity generated by a flashing light during its light pulse
ECP (Effective Candlepower) is the intensity that would appear to an observer if the light were burning steadily
VISUAL
STREAMLINE ® LOW PROFILE STROBE LIGHT (LP3S, LP3P, LP3T)
LP3S
Dome
Housing
Lens
Gasket
Set Screw
"
)
.25 4mm
(6.
1
/2"
Pipe Mount
Custom
Strobe Tube
LP3P
Snap-in Printed
Circuit Board
Assembly
Power
Connection
Schematic
Housing
Surface
Mount
Housing
T-mount
Gasket
Gasket
Mounting
Surface
Mounting
Surface
HOW TO ORDER
S P E C I F I C AT I O N S
Lamp Life:*
Lamp Style:
Operating Temperature
Net Weight:
Shipping Weight:
Diameter:
Height (from bottom):
LP3P
LP3S
LP3T
*Optimal hours under ideal conditions.
LP3T**
7,000 hours
Strobe
-31°F to 150°F
7.3 oz.
8.5 oz.
3.125"
7,000 hours
Strobe
-35°C to 66°C
206.96 g
240.98 g
7.94 cm
5.7"
5.0"
5.1"
14.48 cm
12.7 cm
12.95 cm
• Specify model, voltage and color
• Specify options
Dome guard for LP3S and LP3T
(LP3G)
**LP3T-120 & 240VAC shown
R E P L A C E M E N T PA RT S
Description
Dome, Amber
Dome, Blue
Dome, Clear
Dome, Green
Dome, Red
Strobe Tube
Part Number
K8589006A
K8589006A-01
K8589006A-02
K8589006A-03
K8589006A-04
K149130A
2645 Federal Signal Dr., University Park, IL 60466 Tel: 708.534.4756
Description
PC Assembly, 12-48VDC
PC Assembly, 120VAC
PC Assembly, 240VAC
Gasket, Lens
Gasket, LP3S
Gasket, LP3T
Fax: 708.534.4852
Part Number
K2001316A
K2001317A
K2001317A-01
K8589013A
K8589011A
K8589012A
www.federalsignal-indust.com
63
Item # 21
Item # 22
Extract from the online
catalog
UT 4
Order No.: 3044102
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044102
Universal terminal block with screw connection, cross section: 0,14 - 4
mm², AWG: 26 - 10, width: 6.2 mm, color: Gray
Product notes
WEEE/RoHS-compliant since:
01/01/2003
Commercial data
EAN
4017918960391
Pack
50 Pcs.
Customs tariff
85369010
Weight/Piece
0.009424 KG
Catalog page information
Page 27 (CL-2007)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
General
Number of levels
1
Number of connections
2
Color
gray
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 6
Apr 29, 2008
UT 4 Order No.: 3044102
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044102
Insulating material
PA
Inflammability class acc. to UL 94
V0
Dimensions
Width
6.2 mm
Length
47.7 mm
Height NS 35/7,5
47.5 mm
Height NS 35/15
55 mm
Technical data
Maximum load current
41 A (with 6 mm conductor cross section)
Rated surge voltage
8 kV
Pollution degree
3
Surge voltage category
III
Insulating material group
I
Connection in acc. with standard
IEC 60947-7-1
Nominal current IN
32 A (with 4 mm conductor cross section)
Nominal voltage UN
1000 V
Open side panel
ja
2
2
Connection data
Conductor cross section solid min.
0.14 mm
Conductor cross section solid max.
6 mm
Conductor cross section stranded min.
0.14 mm
Conductor cross section stranded max.
6 mm
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
10
Conductor cross section stranded, with ferrule
without plastic sleeve min.
0.25 mm
Conductor cross section stranded, with ferrule
without plastic sleeve max.
4 mm
Conductor cross section stranded, with ferrule
with plastic sleeve min.
0.25 mm
Conductor cross section stranded, with ferrule
with plastic sleeve max.
4 mm
2 conductors with same cross section, solid min.
0.14 mm
2 conductors with same cross section, solid max.
1.5 mm
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
2
2
2
2
2
2
2
2
2
2
Page 2 / 6
Apr 29, 2008
UT 4 Order No.: 3044102
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044102
2 conductors with same cross section, stranded
min.
0.14 mm
2 conductors with same cross section, stranded
max.
1.5 mm
2 conductors with same cross section, stranded,
TWIN ferrules with plastic sleeve, min.
0.5 mm
2 conductors with same cross section, stranded,
TWIN ferrules with plastic sleeve, max.
2.5 mm
2 conductors with same cross section, stranded,
ferrules without plastic sleeve, min.
0.25 mm
2 conductors with same cross section, stranded,
ferrules without plastic sleeve, max.
1.5 mm
Type of connection
Screw connection
Stripping length
9 mm
Internal cylindrical gage
A4
Screw thread
M3
Tightening torque, min
0.6 Nm
Tightening torque max
0.8 Nm
2
2
2
2
2
2
Certificates / Approvals
CSA
Nominal voltage UN
600 V
Nominal current IN
30 A
AWG/kcmil
26-10
CUL
Nominal voltage UN
600 V
Nominal current IN
30 A
AWG/kcmil
26-10
UL
Nominal voltage UN
600 V
Nominal current IN
30 A
AWG/kcmil
26-10
Certification
CB, CSA, CUL, DNV, GL, LR, UL, VDE-PZI
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 6
Apr 29, 2008
Item # 23
Extract from the online
catalog
UT 4-PE
Order No.: 3044128
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044128
Universal terminal block with screw connection, cross section: 0.14 - 4
mm², AWG: 26 - 10, width: 6.2 mm, color: Green-yellow
Product notes
WEEE/RoHS-compliant since:
01/01/2003
Commercial data
EAN
4017918960407
Pack
50 Pcs.
Customs tariff
85369010
Weight/Piece
0.01325 KG
Catalog page information
Page 33 (CL-2007)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
General
Number of levels
1
Number of connections
2
Color
green-yellow
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 7
Apr 29, 2008
UT 4-PE Order No.: 3044128
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044128
Insulating material
PA
Inflammability class acc. to UL 94
V0
Dimensions
Width
6.2 mm
Length
47.7 mm
Height NS 35/7,5
47.5 mm
Height NS 35/15
55 mm
Technical data
Rated surge voltage
8 kV
Pollution degree
3
Surge voltage category
III
Insulating material group
I
Connection in acc. with standard
IEC 60947-7-2
Open side panel
ja
Connection data
Conductor cross section solid min.
0.14 mm
Conductor cross section solid max.
6 mm
Conductor cross section stranded min.
0.14 mm
Conductor cross section stranded max.
6 mm
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
10
Conductor cross section stranded, with ferrule
without plastic sleeve min.
0.25 mm
Conductor cross section stranded, with ferrule
without plastic sleeve max.
4 mm
Conductor cross section stranded, with ferrule
with plastic sleeve min.
0.25 mm
Conductor cross section stranded, with ferrule
with plastic sleeve max.
4 mm
2 conductors with same cross section, solid min.
0.14 mm
2 conductors with same cross section, solid max.
1.5 mm
2 conductors with same cross section, stranded
min.
0.14 mm
2 conductors with same cross section, stranded
max.
1.5 mm
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
2
2
2
2
2
2
2
2
2
2
2
2
Page 2 / 7
Apr 29, 2008
UT 4-PE Order No.: 3044128
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044128
2 conductors with same cross section, stranded,
TWIN ferrules with plastic sleeve, min.
0.5 mm
2 conductors with same cross section, stranded,
TWIN ferrules with plastic sleeve, max.
2.5 mm
2 conductors with same cross section, stranded,
ferrules without plastic sleeve, min.
0.25 mm
2 conductors with same cross section, stranded,
ferrules without plastic sleeve, max.
1.5 mm
Type of connection
Screw connection
Stripping length
9 mm
Internal cylindrical gage
A4
Screw thread
M3
Tightening torque, min
0.6 Nm
Tightening torque max
0.8 Nm
2
2
2
2
Certificates / Approvals
CSA
AWG/kcmil
26-10
CUL
AWG/kcmil
26-10
UL
AWG/kcmil
26-10
Certification
CB, CSA, CUL, DNV, GL, LR, UL, VDE-PZI
requested approbations
Certification Ex:
IECEx, KEMA-EX
Accessories
Item
Designation
Description
ATP-UT
Partition plate, for visual and electrical separation of terminal
groups, width: 2 mm, color: gray
Assembly
3047167
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 7
Apr 29, 2008
UT 4-PE Order No.: 3044128
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044128
3047028
D-UT 2,5/10
Cover, for terminal block UT and UT...-PE, width 2.2 mm, color:
Gray
0801762
NS 35/ 7,5 CU UNPERF
2000MM
DIN rail, material: Copper, unperforated, height 7.5 mm, width 35
mm, length: 2 m
1207640
NS 35/ 7,5 PERF 755MM
NS 35 DIN rail, height 7.5 mm, length 755 mm
1207653
NS 35/ 7,5 PERF 955MM
NS35 DIN rail, height 7.5 mm, length 955 mm
1207666
NS 35/ 7,5 PERF 1155MM
NS 35 DIN rail, height 7.5 mm, length 1155 mm
0801733
NS 35/ 7,5 PERF 2000MM
DIN rail, material: Steel, perforated, height 7.5 mm, width 35 mm,
length: 2 m
0801681
NS 35/ 7,5 UNPERF 2000MM
DIN rail, material: Steel, unperforated, height 7.5 mm, width 35
mm, length: 2 m
1201756
NS 35/15 AL UNPERF 2000MM
DIN rail, deep-drawn, high profile, unperforated, 1.5 mm thick,
material: Aluminum, height 15 mm, width 35 mm, length 2 m
1201895
NS 35/15 CU UNPERF 2000MM
DIN rail, material: Copper, unperforated, 1.5 mm thick, height 15
mm, width 35 mm, length: 2 m
1207679
NS 35/15 PERF 755MM
NS 35 DIN rail, perforated, height 15 mm, length 755 mm
1207682
NS 35/15 PERF 955MM
NS 35 DIN rail, perforated, height 15 mm, length 955 mm
1207695
NS 35/15 PERF 1155MM
NS 35 DIN rail, perforated, height 15 mm, length 1155 mm
1201730
NS 35/15 PERF 2000MM
DIN rail, material: Steel, perforated, height 15 mm, width 35 mm,
length: 2 m
1201714
NS 35/15 UNPERF 2000MM
DIN rail, material: Steel, unperforated, height 15 mm, width 35
mm, length: 2 m
1201798
NS 35/15-2,3 UNPERF 2000MM
DIN rail, material: Steel, unperforated, 2.3 mm thick, height 15
mm, width 35 mm, length: 2 m
3030336
FBS 2-6
Plug-in bridge for cross-connections in the terminal center, 2-pos.,
color: Red
3030242
FBS 3-6
Plug-in bridge for cross-connections in the terminal center, 3-pos.,
color: Red
3030255
FBS 4-6
Plug-in bridge for cross-connections in the terminal center, 4-pos.,
color: Red
3030349
FBS 5-6
Plug-in bridge for cross-connections in the terminal center, 5-pos.,
color: Red
3030271
FBS 10-6
Plug-in bridge for cross-connections in the terminal center, 10pos., color: Red
3030365
FBS 20-6
Plug-in bridge for cross-connections in the terminal center, 20pos., color: Red
3032224
FBS 50-6
Plug-in bridge for cross-connections in the terminal center, 50pos., color: Red
Bridges
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 7
Apr 29, 2008
UT 4-PE Order No.: 3044128
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044128
General
3022276
CLIPFIX 35-5
Snap-on end bracket, for NS 35/7.5 or NS 35/15 DIN rail, can be
fitted with Zack strip ZB 5 and ZBF 5, terminal strip marker KLM
2 and KLM, parking facility for FBS...5, FBS...6, KSS 5, KSS 6,
width: 5,15 mm, color: gray
0811228
X-PEN 0,35
Marker pen without ink cartridge, for manual labeling of markers,
labeling extremely wipe-proof, line thickness 0.35 mm
1051016
ZB 6,LGS:FORTL.ZAHLEN
Zack strip, 10-section, printed horizontally: with the numbers,
1-10, 11-20 etc. up to 991-1000, color: white
5060935
ZB 6/WH-100:UNBEDRUCKT
Zack strip, unprinted: For individual labeling with M-PEN, ZB-T
or CMS system, large batch, sufficient for labeling 1000 terminal
blocks, for a terminal width of 6.2 mm, color: White
1050499
ZB 6:SO/CMS
Zack strip, 10-section, divisible, special printing, marking
according to customer requirements
0201689
MPS-IH BU
Insulating sleeve (blue), for MPS metal part to be ordered
separately (0201744)
0201676
MPS-IH RD
Insulating sleeve (red), for MPS metal part to be ordered
separately (0201744)
0201663
MPS-IH WH
Insulating sleeve (white), for MPS metal part to be ordered
separately (0201744)
0201744
MPS-MT
Test plug, consisting of: Metal part for 2.3 mm diameter socket
hole
3030925
PAI-4
Test adapter, for 4 mm diameter test plug PS and safety test plug,
makes contact in the bridge shaft
3030996
PS-6
Modular test plug, for individual assembly of test plug strips, for
UT, ST, DT and QT terminal blocks, can be labeled with ZBF 6,
color: Red
SZS 0,6X3,5
Screwdriver, bladed, matches all screw terminal blocks up to 4.0
mm² connection cross section, blade: 0.6 x 3.5 mm, without VDE
approval
Marking
Plug/Adapter
Tools
1205053
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 7
Apr 29, 2008
UT 4-PE Order No.: 3044128
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044128
Drawings
Circuit diagram
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 6 / 7
Apr 29, 2008
UT 4-PE Order No.: 3044128
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3044128
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2008 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 7 / 7
Apr 29, 2008
Item # 24
tnb06_wrtrm_sece_p04_05
8/9/07
1:07 PM
Page E-5
Item # 25
and Accessories
How to Order Ty-Duct ®
Ordering the Ty-Duct® products you need is as easy as 1, 2, 3!
After selecting the appropriate Ty-Duct solutions for your application,
make sure you complete the following checklist.
and Accessories
For Ty-Duct Wiring Duct and Covers:
1 Specify color
[ _ ] = space for color identifier:
2 Indicate if you want the
duct without mounting holes
W = White
3 Indicate if you want an
adhesive-backed duct
(not available in Wide Slot
Duct — Halogen Free)
2
G = Gray
B = Black
I
= Intrinsic Blue
To order duct without mounting holes, add suffix NM to catalog number. Example: TY75X1WPG6NM is a .75" x 1" wide slot gray duct with no mounting holes.
3 To order Adhesive-Backed
Duct, add suffix A to Catalog
Number.
Example: TY75x15WPB6A
is a .75" x 1.5" wide slot
black duct with adhesive
backing.
Shelf life for adhesive
is 1 year.
Nominal Width x Nominal Height
CAT. NO.
SIZE (W x H)
IN.
MM
DESCRIPTION
TY75X1WP[ G ]6NM .75 x 1 Wide Slot Duct
TY75X15WP[B ]6A .75 x 1.5 Wide Slot Duct
TY75X2WP[ I ]6
.75 x 2 Wide Slot Duct
SP = Solid
WP = Wide Slot
NP = Narrow Slot
RP = Round Hole
1
0.94 x 1.09
0.94 x 1.56
0.94 x 2.07
TY2D[ SP ][ G ]6
2" High Wall Divider
TY75CP[ _ ]6
DUCT STD. COVER STD. LENGTH
CTN. QTY.
CTN. QTY.
(FT.)
120
120
120
LENGTH STD.
(FT.) CTN. QTY
6
6
Standard lengths are 6 feet.
120
Corner Strip sample shown below.
Joining Strips are ordered the
same way.
LENGTH STD.
(FT.) CTN. QTY
CAT. NO.
DESCRIPTION
TYCS[ G ]6
Corner Strip
6
120
TYJS[ G ]6
Joining Strip
6
120
Catalog Number must be completed by adding suffix G for Gray, W for White, I for
Intrinsic Blue, B for Black. Example: TY2DSPG6 is a 2" high solid wall gray divider.
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
120
For Ty-Duct Corner
& Joining Strips:
Catalog Number must be completed by adding suffix
SP for Solid or WP for Wide Slot.
Example: TY2DSPG6 is a 2" high solid wall gray divider.
DESCRIPTION
COVER
CAT. NO.
Catalog Number must be completed by adding suffix G for Gray, W for White, I for Intrinsic Blue, B for Black.
Example: TY75x2WPI6 is a .75" x 2" wide slot intrinsic blue duct. Cover color must be specified also.
For Ty-Duct Dividers:
CAT. NO.
23.9 x 27.7
23.9 x 39.6
23.9 x 52.6
Standard Carton Quantity
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Catalog Number must be completed by adding suffix G for Gray, W for White, I for
Intrinsic Blue, B for Black. Example: TYCSG6 is a gray corner strip.
Technical Services
Tel: 888.862.3289
www.tnb.com
E-5
tnb06_wrtrm_sece_p08_09
8/9/07
1:06 PM
Page E-8
and Accessories
Wide Slot Wiring Duct
and Accessories
Greater sidewall rigidity
with increased versatility!
Two-Point
Contact Design
Wide Slot Wiring
Duct — PVC
• Wide fingers and slots increase rigidity
and enable insertion of bundles
• Non-slip cover does not slide easily
and resists vibration
• Rounded edges keep hands and wires
free of abrasion
• V-shaped slot lead-in enables easier
and faster wire installation
Flush Cover
Design
• Dual score lines are designed to yield clean
breakoffs at the base of the slot and the duct
• Restricted slot design makes sure that wires
are held with or without the cover inserted
• Flush cover attaches flush with sidewall
for finished look
Dual Score
Lines
• Improved flush sidewall and cover style for greater wire capacity
• Versatile North American and DIN Standard mounting holes
enables same duct for multiple applications
• Constructed of flame-retardant PVC
• Integrated mounting holes — larger sizes include staggered
holes for mounting flexibility (see page E-23 for illustration)
• Lead-free construction
Wide Fingers
& Slots
Grooved
Cover
V-Shaped
Slot Lead-In
Embossed
Holes
E-8
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
tnb06_wrtrm_sece_p08_09
8/9/07
1:06 PM
Page E-9
and Accessories
Wide Slot Wiring Duct
W
For a complete listing of Wide Slot
dimensional details see page E-23.
H
Bottom View
CAT. NO.
DESCRIPTION
TY75X1WP[ _ ]6
TY75X15WP[ _ ]6
TY75X2WP[ _ ]6
TY1X1WP[ _ ]6
TY1X15WP[ _ ]6
TY1X2WP[ _ ]6
TY1X3WP[ _ ]6
TY1X4WP[ _ ]6
TY15X1WP[ _ ]6
TY15X15WP[ _ ]6
TY15X2WP[ _ ]6
TY15X3WP[ _ ]6
TY15X4WP[ _ ]6
TY2X1WP[ _ ]6
TY2X15WP[ _ ]6
TY2X2WP[ _ ]6
TY2X3WP[ _ ]6
TY2X4WP[ _ ]6
TY2X5WP[ _ ]6
TY25X2WP[ _ ]6
TY25X3WP[ _ ]6
TY25X4WP[ _ ]6
TY3X1WP[ _ ]6
TY3X2WP[ _ ]6
TY3X3WP[ _ ]6
TY3X4WP[ _ ]6
TY3X5WP[ _ ]6
TY4X15WP[ _ ]6
TY4X2WP[ _ ]6
TY4X3WP[ _ ]6
TY4X4WP[ _ ]6
TY4X5WP[ _ ]6
TY6X4WP[ _ ]6
.75 x 1 Wide Slot Duct
.75 x 1.5 Wide Slot Duct
.75 x 2 Wide Slot Duct
1 x 1 Wide Slot Duct
1 x 1.5 Wide Slot Duct
1 x 2 Wide Slot Duct
1 x 3 Wide Slot Duct
1 x 4 Wide Slot Duct
1.5 x 1 Wide Slot Duct
1.5 x 1.5 Wide Slot Duct
1.5 x 2 Wide SlotDuct
1.5 x 3 Wide Slot Duct
1.5 x 4 Wide Slot Duct
2 x 1 Wide Slot Duct
2 x 1.5 Wide Slot Duct
2 x 2 Wide Slot Duct
2 x 3 Wide Slot Duct
2 x 4 Wide Slot Duct
2 x 5 Wide Slot Duct
2.5 x 2 Wide Slot Duct
2.5 x 3 Wide Slot Duct
2.5 x 4 Wide Slot Duct
3 x 1 Wide SlotDuct
3 x 2 Wide Slot Duct
3 x 3 Wide Slot Duct
3 x 4 Wide Slot Duct
3 x 5 Wide Slot Duct
4 x 1.5 Wide Slot Duct
4 x 2 Wide Slot Duct
4 x 3 Wide Slot Duct
4 x 4 Wide Slot Duct
4 x 5 Wide Slot Duct
6 x 4 Wide Slot Duct
SIZE (W x H)
IN.
MM
0.94 x 1.14 23.9 x 27.7
0.94 x 1.60 23.9 x 39.6
0.94 x 2.10 23.9 x 52.6
1.25 x 1.14 31.8 x 27.7
1.25 x 1.60 31.8 x 39.9
1.25 x 2.10 31.8 x 52.8
1.25 x 3.05 31.8 x 77.7
1.25 x 4.37 31.8 x 111.3
1.75 x 1.14 44.5 x 27.7
1.75 x 1.60 44.5 x 39.9
1.75 x 2.10 44.5 x 52.8
1.75 x 3.05 44.5 x 77.7
1.75 x 4.37 44.5 x 111.3
2.25 x 1.24 57.2 x 28.4
2.25 x 1.70 57.2 x 40.4
2.25 x 2.19 57.2 x 53.3
2.25 x 3.14 57.2 x 78.2
2.25 x 4.46 57.2 x 111.8
2.25 x 5.15 57.2 x 129.3
2.75 x 2.19 69.9 x 53.6
2.75 x 3.14 69.9 x 78.2
2.75 x 4.46 69.9 x 111.8
3.25 x 1.24 82.6 x 29.0
3.25 x 2.19 82.6 x 54.9
3.25 x 3.14 82.6 x 79.8
3.25 x 4.46 82.6 x 113.5
3.25 x 5.15 82.6 x 130.6
4.25 x 1.70 108.0 x 42.4
4.25 x 2.19 108.0 x 55.1
4.25 x 3.14 108.0 x 80.0
4.25 x 4.46 108.0 x 113.8
4.25 x 5.15 108.0 x 130.8
6.25 x 4.46 158.8 x 114.0
COVER
CAT. NO.
DUCT STD. COVER STD. LENGTH
CTN. QTY
CTN. QTY
(FT.)
TY75CP[ _ ]6
TY1CP[ _ ]6
TY15CP[ _ ]6
TY2CP[ _ ]6
TY25CP[ _ ]6
TY3CP[ _ ]6
TY4CP[ _ ]6
TY6CP[ _ ]6
120
120
120
120
120
120
120
60
120
120
120
120
60
120
120
120
60
60
60
120
60
60
120
60
60
60
60
60
60
60
30
30
30
120
6
120
6
120
6
120
6
120
6
120
6
120
6
60
6
and Accessories
Side View
Front View w/Cover
• Standard lengths are 6 feet.
[ _ ] = space for color identifier:
G = Gray
W = White
B = Black
+ Catalog Number must be completed by adding suffix G for Gray, W for White, I for Intrinsic Blue, B for Black.
Example: TY75X1WPG6 is a .75" x 1" wide slot gray duct.
To order duct without mounting holes, add suffix NM to catalog number.
Example: TY75X1WPG6NM is a .75" x 1" wide slot gray duct with no mounting holes.
To order Adhesive-Backed Duct, add suffix A to Catalog Number.
Example: TY75X1WPG6A is a .75" x 1" wide slot gray duct with adhesive backing. Shelf life for adhesive is 1 year.
PVC vinyl duct is UL Recognized
, CSA Certified and CE Compliant.
I = Intrinsic Blue
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
E-9
tnb06_wrtrm_sece_p10_11
8/9/07
1:05 PM
Page E-10
and Accessories
Narrow Slot Wiring Duct
and Accessories
Designed to fit the spacing of
high-density terminal blocks!
Two-Point
Contact Design
Narrow Slot Wiring Duct
• Smaller, higher number of fingers
for more concise harnessing
• Non-slip cover does not slide
easily and resists vibration
• Rounded edges keep hands
and wires free of abrasion
• V-shaped slot lead-in enables
easier and faster wire installation
• Restricted slot design makes sure that wires
are held with or without the cover inserted
Flush Cover
Design
• Flush cover attaches flush with sidewall
for finished look
Two Levels
of Wire Service
• Versatile North American and DIN Standard mounting
holes enable same duct for multiple applications
• Dual score lines are designed to yield clean
breakoffs at the base of the slot and the duct
Dual Score
Lines
Three Levels
of Wire Service
• Finger design restricts wire from slipping
along the edge; creates two or three levels
of wire service (see page E-24 for
illustration)
• Lead-free construction
• Constructed of flame-retardant PVC
V-Shaped
Slot Lead-In
Narrow Fingers
& Slots
Grooved
Cover
Restricted Slot
Design
Embossed
Holes
E-10
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
tnb06_wrtrm_sece_p10_11
8/9/07
1:05 PM
Page E-11
and Accessories
Narrow Slot Wiring Duct
W
For a complete listing of Narrow Slot
dimensional details see page E-24.
H
Side View
CAT. NO.
DESCRIPTION
TY75X15NP[ _ ]6
TY1X1NP[ _ ]6
TY1X15NP[ _ ]6
TY1X2NP[ _ ]6
TY1X3NP[ _ ]6
TY1X4NP[ _ ]6
TY15X1NP[ _ ]6
TY15X15NP[ _ ]6
TY15X2NP[ _ ]6
TY15X3NP[ _ ]6
TY15X4NP[ _ ]6
TY2X1NP[ _ ]6
TY2X15NP[ _ ]6
TY2X2NP[ _ ]6
TY2X3NP[ _ ]6
TY2X4NP[ _ ]6
TY2X5NP[ _ ]6
TY25X2NP[ _ ]6
TY25X3NP[ _ ]6
TY25X4NP[ _ ]6
TY3X1NP[ _ ]6
TY3X2NP[ _ ]6
TY3X3NP[ _ ]6
TY3X4NP[ _ ]6
TY3X5NP[ _ ]6
TY4X2NP[ _ ]6
TY4X3NP[ _ ]6
TY4X4NP[ _ ]6
TY4X5NP[ _ ]6
.75 x 1.5 Narrow Slot Duct
1 x 1 Narrow Slot Duct
1 x 1.5 Narrow Slot Duct
1 x 2 Narrow Slot Duct
1 x 3 Narrow Slot Duct
1 x 4 Narrow Slot Duct
1.5 x 1 Narrow Slot Duct
1.5 x 1.5 Narrow Slot Duct
1.5 x 2 Narrow Slot Duct
1.5 x 3 Narrow Slot Duct
1.5 x 4 Narrow Slot Duct
2 x 1 Narrow Slot Duct
2 x 1.5 Narrow Slot Duct
2 x 2 Narrow Slot Duct
2 x 3 Narrow Slot Duct
2 x 4 Narrow Slot Duct
2 x 5 Narrow Slot Duct
2.5 x 2 Narrow Slot Duct
2.5 x 3 Narrow Slot Duct
2.5 x 4 Narrow Slot Duct
3 x 1 Narrow Slot Duct
3 x 2 Narrow Slot Duct
3 x 3 Narrow Slot Duct
3 x 4 Narrow Slot Duct
3 x 5 Narrow Slot Duct
4 x 2 Narrow Slot Duct
4 x 3 Narrow Slot Duct
4 x 4 Narrow Slot Duct
4 x 5 Narrow Slot Duct
SIZE (W x H)
IN.
MM
0.94 x 1.60 23.9 x 39.6
1.25 x 1.14 31.8 x 27.7
1.25 x 1.60 31.8 x 39.9
1.25 x 2.10 31.8 x 52.8
1.25 x 3.05 31.8 x 77.7
1.25 x 4.37 31.8 x 111.3
1.75 x 1.14 44.5 x 27.7
1.75 x 1.60 44.5 x 39.9
1.75 x 2.10 44.5 x 52.8
1.75 x 3.05 44.5 x 77.7
1.75 x 4.37 44.5 x 111.3
2.25 x 1.24 57.2 x 28.4
2.25 x 1.70 57.2 x 40.4
2.25 x 2.19 57.2 x 53.3
2.25 x 3.14 57.2 x 78.2
2.25 x 4.46 57.2 x 111.8
2.25 x 5.15 57.2 x 129.3
2.75 x 2.19 69.9 x 53.6
2.75 x 3.14 69.9 x 78.2
2.75 x 4.46 69.9 x 111.8
3.25 x 1.24 82.6 x 29.0
3.25 x 2.19 82.6 x 54.9
3.25 x 3.14 82.6 x 79.8
3.25 x 4.46 82.6 x 113.5
3.25 x 5.15 82.6 x 130.6
4.25 x 2.19 108.0 x 55.1
4.25 x 3.14 108.0 x 80.0
4.25 x 4.46 108.0 x 113.8
4.25 x 5.15 108.0 x 130.8
COVER
CAT. NO.
DUCT STD. COVER STD. LENGTH
CTN. QTY
CTN. QTY
(FT.)
TY75CP[ _ ]6
TY1CP[ _ ]6
TY15CP[ _ ]6
TY2CP[ _ ]6
TY25CP[ _ ]6
TY3CP[ _ ]6
TY4CP[ _ ]6
120
120
120
120
120
60
120
120
120
120
60
120
120
120
60
60
60
120
60
60
120
60
60
60
60
60
60
30
30
120
6
120
6
120
6
120
6
120
6
120
6
120
6
and Accessories
Front View w/Cover
Bottom View
• Standard lengths are 6 feet.
[ _ ] = space for color identifier:
G = Gray
W = White
B = Black
+ Catalog Number must be completed by adding suffix G for Gray, W for White, I for Intrinsic Blue, B for Black.
Example: TY75X15NPB6 is a .75" x 1.5" narrow slot black duct.
To order duct without mounting holes, add suffix NM to catalog number.
Example: TY75X15NPB6NM is a .75" x 1.5" narrow slot black duct with no mounting holes.
To order Adhesive-Backed Duct, add suffix A to Catalog Number.
Example: TY75X15NPB6A is a .75" x 1.5" narrow slot black duct with adhesive backing. Shelf life for adhesive is 1 year.
PVC vinyl duct is UL Recognized
, CSA Certified and CE Compliant.
I = Intrinsic Blue
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
www.tnb.com
E-11
tnb06_wrtrm_sece_p26
8/9/07
1:06 PM
Page E-26
and Accessories
Technical Information
and Accessories
Ty-Duct ® meets all of the prominent agency approvals and standards.
Agency Approvals:
Thomas & Betts Ty-Duct wiring duct is UL recognized for all requirements set forth
in UL standard 1565 “Positioning Device.”
The Ty-Duct wiring duct meets all applicable requirements of the Canadian Standard
Association as described in CSA C22.2 No. 18.5.
All Ty-Duct wiring duct components comply with the European Directives
for CE (Conformite European) Marking.
All materials used in the making of the Ty-Duct wiring duct comply with the European Directives 2002/95/EC (RoHS),
2002/96/EC (WEEE), and 2003/11/EC.
Standards:
NFPA-79-2002
Thomas & Betts Ty-Duct wiring duct is compliant with the National Fire Protection Agency NFPA-79-2002. All materials used in the
manufacturing of the Ty-Duct components are selected from flame-retardant material and comply with IEC 60332-1. The testing is
required in order to comply with NFPA-79-2002, Section 13.3.1.
UL 508/UL 508A
As required in UL508/UL508A a factory-installed conductor shall be separated from a conductor used in a different circuit when the
conductors are not insulated for the maximum voltage of either circuit. The Ty-Duct wiring duct with a divider wall creates the required
separation to meet this requirement.
DIN 43 659
This European standard specifies dimensions for slotted trunkings installed in electrical switchgear assemblies.
The standard defines the following dimensions:
• The mounting hole pattern
• The mounting hole slot dimensions
• The mounting hole pitch and location
• The minimum overall product length
E-26
www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Canada
Tel: 450.347.5318
Fax: 450.347.1976
Technical Services
Tel: 888.862.3289
Item # 26
Model C12-17
Combustible Gas Transmitter.......
Units supplied with the integral display also contain a
single alarm setpoint and relay for local alarm purposes. This
integral relay is a latching alarm that can be reset with a
magnetic tool without opening the enclosure.
C12-17 transmitters can be connected directly to PLC,
DCS, or computer based alarm systems without additional
hardware. If complete alarm systems are needed, ATI can
supply Series B14 modular alarm receivers or Series C14
Multi-point scanning alarm units to provide all required
alarm functions.
Sensor Operation
Transmitter with display
The Model C12-17 is a stand-alone gas transmitter designed
to detect potentially hazardous concentrations of
combustible gases in ambient air. Gases and hydrocarbon
vapors such as methane, propane, butane, gasoline, toluene,
hydrogen, and many others can be reliably monitored in
process buildings, analyzer enclosures, pump stations, and
gas compressor stations. In fact, anywhere gases or vapors
may build up to explosive levels can be readily monitored
using this transmitter.
C12-17 Combustible Gas Transmitters are three-wire
transmitters, operating from 24 VDC power supplies and
transmitting a 4-20 mA signal proportional to 0-100% LEL
(Lower Explosive Limit) of a particular gas or vapor. The
transmitter is available either as a blind transmitter or with
integral LCD display that provides local indication of gas
concentration, visible through the glass window in the
explosion-proof housing.
Combustible gas sensors are made up of two matched
sensing elements, one active and one passive. Both are
electrically heated and form two legs of a Wheatstone bridge
circuit. When combustible gas contacts the sensor, the
active element catalyzes the oxidation of gas, heating the
active element and changing it's resistance. The passive
element remains unchanged, resulting in a change in the
bridge circuit that is proportional to the gas concentration.
Explosion-proof sensor assemblies are made of 316
stainless steel for maximum corrosion protection. A sinter
bonded flame arrestor provides the gas diffusion path to the
sensing elements while maintaining the flame-proof
integrity of the assembly. Sensing elements are specially
designed for maximum poison resistance and long life in
harsh industrial environments, with sensor life typically 2
years or more.
Model
C12-17
Combustible Gas Transmitter... ....
Specifications
Gas Type:
Display:
Range:
Response
Time (T90):
Accuracy:
Electronic
Repeatability:
Electronic
Linearity:
Zero Drift:
Span Drift:
Output:
Calibrated for methane unless otherwise
ordered.
3-digit LCD optional
0-100% LEL
10 seconds
Power:
Enclosure:
Generally ±5% of value, but limited by
available calibration gas accuracy.
±1%
Sensor:
Controls:
Alarm:
Alarm Relay:
±0.5%
Less than 2% full scale per month
Less than 3% per month
Powered 4-20 mA, 675 ohms maximum at
24 VDC
Operating
Temperature:
Weight:
12-30 VDC, 100 mA maximum
Explosion-proof, Class 1, Div 1, Groups B, C,
&D
Optional single alarm available
SPDT, 5 Amp @ 220 VAC non-inductive,
latching
316 stainless steel
Potentiometer zero and span adjustment
Potentiometer alarm setpoint adjustment
Magnetic reset switch for latching alarm
relay
-40° to +70°C
3 lbs (1.3 kg)
Ordering Information:
Model C12-17-DDDD-E-F
Suffix DDDD - Range
0100 - 0-100% LEL
0050 - 0-50% LEL
Suffix C - Sensor Style
1 - Standard
2 - Remote sensor with junction box
Suffix E - Units of Measurement
1 - No display
2 - Integral display & alarm relay
Accessories
00-0258 - Calibration adapter
00-0261 - Splash guard/remote calibration adapter
00-0298 - Sensor flow assembly
Transmitter without display
Represented By:
Analytical Technology, Inc.
6 Iron Bridge Drive • Collegeville, PA 19426
Phone: 610/917-0991• Toll-Free: 800/959-0299
Fax: 610/917-0992
E-Mail: [email protected]
Web: www.analyticaltechnology.com
ATI (UK) Limited
Bank Chambers, 33 Stamford Street
Mossley, Aston-u-Lyne OL5 0LL
Phone: +44 (0) 1457 832800
Fax: +44 (0) 1457 83950
E-Mail: [email protected]