- IC Mori

Page 1 / 6
Certificate number: 20125/B0 BV
File number: ACE 02/010/20
Product code: 2633H
This certificate is not valid when presented without the
full attached schedule composed of 7 sections
www.veristar.com
TYPE APPROVAL CERTIFICATE
This certificate is issued to
ABB SpA - ABB Sace Division
Frosinone - ITALY
for the type of product
CIRCUIT BREAKERS (LOW VOLTAGE)
Low voltage moulded-case circuit-breakers Tmax type T1, T2, T3, T4, T5, T6, T7
Requirements:
Bureau Veritas Rules for the Classification of Steel Ships.
IEC 60947-1 (2007), IEC 60947-2 (2006).
This certificate is issued to attest that BUREAU VERITAS did undertake the relevant approval procedures for the product identified above which
was found to comply with the relevant requirements mentioned above.
This certificate will expire on: 04 Dec 2019
For BUREAU VERITAS,
At BV GENOA, on 04 Dec 2014,
Gianni Pirovano
This certificate remains valid until the date stated above, unless cancelled or revoked, provided the conditions indicated in the subsequent page(s) are complied
with and the product remains satisfactory in service. This certificate will not be valid if the applicant makes any changes or modifications to the approved product,
which have not been notified to, and agreed in writing with BUREAU VERITAS. Should the specified regulations or standards be amended during the validity of
this certificate, the product(s) is/are to be re-approved prior to it/they being placed on board vessels to which the amended regulations or standards apply. This
certificate is issued within the scope of the General Conditions of BUREAU VERITAS Marine & Offshore Division available on the internet site www.veristar.com.
Any Person not a party to the contract pursuant to which this document is delivered may not assert a claim against BUREAU VERITAS for any liability arising out
of errors or omissions which may be contained in said document, or for errors of judgement, fault or negligence committed by personnel of the Society or of its
Agents in establishment or issuance of this document, and in connection with any activities for which it may provide.
The electronic version is available at: http://www.veristarnb.com/veristarnb/jsp/viewPublicPdfTypec.jsp?id=8oonhtlszn
BV Mod. Ad.E 530 October 2014
This certificate consists of 6 page(s)
Page 2 / 6
Certificate number: 20125/B0 BV
THE SCHEDULE OF APPROVAL
1. PRODUCT DESCRIPTION:
Technical data of low voltage moulded case circuit-breakers Tmax type: T1, T2, T3, T4, T5, T6, T7.
- Rated insulation voltage, Ui
- Rated impulse withstand voltage, Uimp:
- Rated frequency
- Poles
: 1000V
: 8 kV
: 50 - 60 Hz
: 3/4
Rated uninterrupted current , Iu
(A)
Rated service voltage, Ue (AC)
(V)
(DC)
(V)
Rated ultimate short-circuit breaking capacity, Icu
220/230 V AC
(kA)
380/415 VAC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Rated service short-circuit breaking capacity, Ics
220/230 V AC
(% Icu)
380/415 VAC
(% Icu)
440 V AC
(%Icu)
500 V AC
(% Icu)
690 V AC
(%Icu)
Utilization category
Rated short-circuit making capacity, Icm
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Version
Rated uninterrupted current , Iu
(A)
Rated service voltage, Ue (AC)
(V)
(DC)
(V)
Rated ultimate short-circuit breaking capacity, Icu
220/230 V AC
(kA)
380/415 VAC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Rated service short-circuit breaking capacity, Ics
220/230 V AC
(%Icu)
380/415 VAC
(%Icu)
440 V AC
(%Icu)
500 V AC
(%Icu)
690 V AC
(%Icu)
Utilization category
Rated short-circuit making capacity, Icm
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Version
Tmax T1
B
160
690
500
C
160
690
500
N
160
690
500
25
16
10
8
3
40
25
15
10
4
50
36
22
15
6
100%
100%
100%
100%
100%
A
75%
100%
75%
75%
75%
A
75%
75%
50%
50%
50%
A
52,5
32
17
13,6
4,3
F
84
52,5
30
17
5,9
F
105
75,6
46,2
30
9,2
F
Tmax T2
N
160
690
500
S
160
690
500
H
160
690
500
L
160
690
500
65
36
30
25
6
85
50
45
30
7
100
70
55
36
8
120
85
75
50
10
100%
100%
100%
100%
100%
A
100%
100%
100%
100%
100%
A
100%
100%
100%
100%
100%
A
100%
75% (70 kΑ)
75%
75%
75%
A
143
75,6
63
52,5
9,2
F-P
187
105
94,5
63
11,9
F-P
220
154
121
75,6
13,6
F-P
264
187
165
105
17
F-P
The electronic version is available at: http://www.veristarnb.com/veristarnb/jsp/viewPublicPdfTypec.jsp?id=8oonhtlszn
BV Mod. Ad.E 530 May 2009
This certificate consists of 6 page(s)
Page 3 / 6
Certificate number: 20125/B0 BV
Tmax T3
N
250
690
500
Rated uninterrupted current , Iu
(A)
Rated service voltage, Ue (AC)
(V)
(DC)
(V)
Rated ultimate short-circuit breaking capacity, Icu
220/230 V AC
(kA)
380/415 VAC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Rated service short-circuit breaking capacity, Ics
220/230 V AC
(%Icu)
380/415 VAC
(%Icu)
440 V AC
(%Icu)
500 V AC
(%Icu)
690 V AC
(%Icu)
Utilization category
Rated short-circuit making capacity, Icm
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Version
Rated uninterrupted current , Iu
(A)
Rated service voltage, Ue (AC)
(V)
(DC)
(V)
Rated ultimate short-circuit breaking capacity, Icu
220/230 V AC
(kA)
380/415 VAC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Rated service short-circuit breaking capacity, Ics
220/230 V AC
(%Icu)
380/415 VAC
(%Icu)
440 V AC
(%Icu)
500 V AC
(%Icu)
Utilization category
Rated short-circuit making capacity, Icm
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Version
S
250
690
500
50
36
25
20
5
85
50
40
30
8
75%
75%
75%
75%
75%
A
50%
50% (27kΑ)
50%
50%
50%
A
105
75,6
52,5
40
7,7
F-P
187
105
84
63
13,6
F-P
Tmax T4
N
S
250/320
250/320
690
690
750
750
H
250/320
690
750
L
250/320
690
750
V
250/320
690
750
70
36
30
25
20
85
50
40
30
25
100
70
65
50
40
200
120
100
85
70
200
200
180
150
80
100%
100%
100%
100%
A
100%
100%
100%
100%
A
100%
100%
100%
100%
A
100%
100%
100%
100%
A
100%
100%
100%
100%
A
154
75,6
63
52,5
40
F-P-W
187
105
84
63
52,5
F-P-W
220
154
143
105
84
F-P-W
440
264
220
187
154
F-P-W
660
440
396
330
176
F-P-W
The electronic version is available at: http://www.veristarnb.com/veristarnb/jsp/viewPublicPdfTypec.jsp?id=8oonhtlszn
BV Mod. Ad.E 530 May 2009
This certificate consists of 6 page(s)
Page 4 / 6
Certificate number: 20125/B0 BV
Rated uninterrupted current , Iu
(A)
Rated service voltage, Ue (AC)
(V)
(DC)
(V)
Rated ultimate short-circuit breaking capacity,
Icu
220/230 V AC
(kA)
380/415 VAC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Rated service short-circuit breaking capacity, Ics
220/230 V AC
(%Icu)
380/415 VAC
(%Icu)
440 V AC
(%Icu)
500 V AC
(%Icu)
690 V AC
(%Icu)
Utilization category *)
Rated short-circuit making capacity, Icm
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Version
Tmax T5
N
S
400/630
400/630
690
690
750
750
H
400/630
690
750
L
400/630
690
750
V
400/630
690
750
70
36
30
25
20
85
50
40
30
25
100
70
65
50
40
200
120
100
85
70
200
200
180
150
80
100%
100%
100%
100%
100%
B(400A)
-A(630A)
100%
100%
100%
100%
100%
B(400A)
-A(630A)
100%
100%
100%
100%
100%
B(400A)
-A(630A)
100%
100%
100%
100%
100%
B(400A)
-A(630A)
100%
100%
100%
100%
100%
B(400A)
-A(630A)
154
75,6
63
52,5
40
F-P-W
187
105
84
63
52,5
F-P-W
220
154
143
106
84
F-P-W
440
264
220
187
154
F-P-W
660
440
396
330
176
F-P-W
Tmax T6
Rated current, Iu
(A)
Rated service voltage, Ue (AC)
(V)
(DC)
(V)
Rated ultimate short-circuit breaking capacity,
Icu
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Rated service short-circuit breaking capacity, Ics
220/230 V AC
(%Icu)
380/415 V AC
(%Icu)
440 V AC
(%Icu)
500 V AC
(%Icu)
690 V AC
(%Icu)
Utilization category **)
Rated short-circuit making capacity, Icm
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Version
N
630/800/1000
690
750
S
630/800/1000
690
750
H
630/800/1000
690
750
L
630/800/1000
690
750
70
36
30
25
20
85
50
45
35
22
100
70
50
50
25
200
100
80
65
30
100%
100%
100%
100%
75%
B(630A-800A)
-A(1000A)
100%
100%
100%
100%
75%
B(630A-800A)
-A(1000A)
100%
100%
100%
100%
75%
B(630A-800A)
-A(1000A)
75%
75%
75%
75%
75%
B(630A-800A)
-A(1000A)
154
75,6
63
52.5
40
F-W
187
105
94.5
73.5
46
F-W
220
154
105
105
52.5
F-W
440
220
176
143
63
F-W
The electronic version is available at: http://www.veristarnb.com/veristarnb/jsp/viewPublicPdfTypec.jsp?id=8oonhtlszn
BV Mod. Ad.E 530 May 2009
This certificate consists of 6 page(s)
Page 5 / 6
Certificate number: 20125/B0 BV
Tmax T7
Rated current, Iu
(A)
Rated service voltage, Ue (AC)
(V)
(DC)
(V)
Rated ultimate short-circuit breaking capacity, Icu
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Rated service short-circuit breaking capacity, Ics
220/230 V AC
(%Icu)
380/415 V AC
(%Icu)
440 V AC
(%Icu)
500 V AC
(%Icu)
690 V AC
(%Icu)
Utilization category ***)
Rated short-circuit making capacity, Icm
220/230 V AC
(kA)
380/415 V AC
(kA)
440 V AC
(kA)
500 V AC
(kA)
690 V AC
(kA)
Version
S
800/1000/
1250/1600
690
-
H
800/1000/
1250/1600
690
-
L
800/1000/
1250/1600
690
-
V (7)
800/1000/
1250/1600
690
-
85
50
50
40
30
100
70
65
50
42
200
120
100
85
50
200
150
130
100
60
100%
100%
100%
100%
100%
B
100%
100%
100%
100%
75%
B
100%
100%
100%
75%
75%
B
100%
100%
100%
100%
75%
B
187
105
105
84
63
F-W
220
154
143
105
88,2
F-W
440
264
220
187
105
F-W
440
330
286
220
132
F-W
*) Icw = 5 kA,
**) Icw = 7,6 kA (630 A) - 10 kA (800 A),
***) Icw = 20 kA (S, H, L version) - 15 kA (V version).
F = Front,
P = Plug-in circuit-breakers,
W = Withdrawable circuit-brakers.
Trip units:
Thermomagnetic:
T adjustable, M fixed
T adjustable, M adjustable (5..!0 x In)
T adjustable, M fixed (3..5 x In)
T adjustable, M adjustable (2,5..5 x In)
Magnetic only
Electronic:
PR221DS
PR222DS
PR223DS
PR231/P
PR232/P
PR331/P
PR332/P
TMD
TMA
TMG
TMG
T1
T2
T3
T4
T5
T6
T7
X
-
X
X
X(1)
X
X
X
X(2)
X(3)
X
X(4)
X(5)
-
X(6)
-
-
X
-
-
X
X
X
-
X
X
X
-
X
X
X
-
X
X
X
X
-
(1) - MF up to In 12,5 A,
(2) - up to 50 A,
(3) - up to 250 A,
(4) - up to 500 A,
(5) - up to 500 A,
(6) - up to 800 A (W version is not available on T6 1000 A),
(7) - only for T7 800/1000/1250 A.
The electronic version is available at: http://www.veristarnb.com/veristarnb/jsp/viewPublicPdfTypec.jsp?id=8oonhtlszn
BV Mod. Ad.E 530 May 2009
This certificate consists of 6 page(s)
Page 6 / 6
Certificate number: 20125/B0 BV
2. DOCUMENTS AND DRAWINGS:
As per Manufacturer's technical catalogue N° 1SDC210015D0202.
3. TEST REPORTS:
ABB SACE test reports Nos LBRP 8013/00 issued on 08.09.2008 and LBRP 7876/01 issued on 20.12.2007.
Intertek test reports Nos E 133S220765_25a, E 133S220765_25aR, E 133S220765_25b and E 133S220765_25bR
issued on 28.06.2007.
CESI test report No A7027438 issued on 26.02.2008.
LOVAG Certificates of Conformity Nos: IT 07.001 to IT 07.014, IT 07.040 ; IT 07.062, IT 07.075 to IT 07.078,
IT 08.009, IT 08.010, IT 08.018 to IT 08.020, IT 08.051 to IT 08.054, IT 08.074, IT 08.075, IT 08.078 and
IT 08.079 including performance test reports.
4. APPLICATION / LIMITATION:
4.1 - Approval also valid for ships to be granted with the notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS.
4.2 - According to BV Rules for the Classification of Steel Ships and IEC 60947-2.
5. PRODUCTION SURVEY REQUIREMENTS:
5.1 - The above products are to be supplied by ABB SACE S.p.A. in compliance with the type described in this certificate.
5.2 - This type of product is within the category HBV of Bureau Veritas Rule Note NR320.
5.3 - ABB SACE S.p.A. has to make the necessary arrangements to have its works recognised by Bureau Veritas in compliance
with the requirements of NR320 for HBV products :
ABB SACE S.p.A.
ABB Xinhui Low Voltage Switchgear CO., Ltd
Via Baloni 35
Jinguzhou Industrial Development Zone, Xinhui District,
I-24123 Bergamo, Italy
Jiangmen City,
Guangdong Province, P.R. China
6. MARKING OF PRODUCT:
According to IEC 60947-2 specifications.
7. OTHERS:
7.1 - This approval is given on the understanding that the Society reserves the right to require check tests to be carried out on the
units at any time and that ABB SACE S.p.A. - Bergamo - Italy will accept full responsibility for informing shipbuilders,
shipowners or their sub-contractors of the proper methods of use and general maintenance of the units and the conditions of this
approval.
7.2 - This Certificate supersedes the Type Approval Certificate No.20125/A1 BV issued on 14 Apr 2012 by the Society.
*** END OF CERTIFICATE ***
The electronic version is available at: http://www.veristarnb.com/veristarnb/jsp/viewPublicPdfTypec.jsp?id=8oonhtlszn
BV Mod. Ad.E 530 May 2009
This certificate consists of 6 page(s)