HVFS terminal units with fan
CONTENTS
Description
Versions and dimensions
Technical data
2
3
8
2
Series HVFS
HVFS terminal units with fan
Description
The HVFS terminal unit is a solution that fully adapts to
installations in which it is desirable to retain the flexibility of a
variable air volume (VAV) system, while also providing a constant
air volume to specific areas (VAC).
When the thermal demands in the conditioned space are highest,
the flow rate supplied by the HVFS air terminal is 100% primary air,
an action that is controlled by the volume control damper.
The HVFS boxes include the following:
- Double-inlet fan with built-in single-phase
motor, with adjustable speed drive.
- Differential pressure sensor at the primary
air inlet.
- Actuator-Belimo NMV-D2M volume control
damper, at the primary air inlet.
- Airtight
volume
control
damper,
manufactured of galvanized steel sheet, that
runs at low pressure.
- Return air inlet with acoustic silencer at
inlet.
- Fiberglass insulation with a thickness of 50
mm on the inner surface of the box enclosure.
As the thermal needs of the conditioned space gradually decrease,
the primary air intake to the air terminal also gradually decreases
and the secondary air intake increases proportionally. The air flow
supplied by the fan to the diffusers remains constant, whereas the
temperature changes according to thermal demand.
The HVFS boxes control the supply air temperature by varying the
primary air intake (characteristic of a VAV system), while the
supply flow to the rooms remain constant (characteristic of a VAC
system).
The HVFSW and HVFSE air terminals include a hot-water or
electric coil, respectively, when necessary to combat negative
loads (winter), e.g., perimeter loads or in the cases of prolonged
shutdown of the installation. In these cases, the primary air intake
is low, ensuring a minimal ventilation air supply.
The HVFS terminal unit comes in 7 sizes, covering an air flow
range of 300 to 6200 m3/h.
The HVFS terminal units are serviced from the outside, with no need to remove the unit; the fan motor assembly may be
removed through the lower panel, and the control elements from one side of the unit.
Series HVFS
Versions. Dimensions
HVFS BOX 300 to 1500
3
4
Versions. Dimensions
HVFS BOX 2000 to 3000
Series HVFS
Series HVFS
Versions. Dimensions
HVFSW BOX 300 to 1500
5
6
Versions. Dimensions
HVFSW BOX 2000 to 3000
Series HVFS
Series HVFS
7
Versions. Dimensions
Dimension table - HVFS 300 to 1500 boxes
MODEL
A
B
C
D
E
F
G
H
I
J
K
HVFS-300
HVFS-500
HVFS-750
HVFS-1000
HVFS-1500
277
379
442
Ø 158
Ø 198
198
198
198
325
390
390
425
475
104
260
260
260
289
605
790
790
915
1100
250
250
250
250
250
250
300
300
350
500
215
232
300
300
333
320
480
480
480
560
255
415
415
415
455
1150
1150
1150
1150
1180
3
MODEL
DAMP.
FAN
FLOW RATE m /h
HVFS-300
HVFS-500
HVFS-750
HVFS-1000
HVFS-1500
400
800
1200
1600
2000
D2E-133-DM47
DA 9/7 RE
DA 9/9 RE
DA 9/9 RE
DA 10/10 RE
510
850
1270
1700
2500
Dimension table - HVFS 2000-3000 boxes
MODEL
B
C
D
E
F
G
H
I
J
K
HVFS-2000
HVFS-3000
Ø 348
Ø 400
262
262
260
289
1200
1220
250
300
475
800
300
333
480
560
415
455
1180
1180
MODEL
DAMP.
FAN
POL.
W
FLOW RATE m /h
HVFS-2000
HVFS-3000
450
575
2xDA 9/9 RE
2xDA 10/10 RE
6
6
240
370
-
3
Dimension table - HVFSW 300 to 1500 boxes
MODEL
A
B
C
D
E
F
G
H
I
J
K
HVFSW-300
HVFSW-500
HVFSW-750
HVFSW-1000
HVFSW-1500
277
379
442
Ø 158
Ø 198
198
198
198
325
390
390
425
475
104
260
260
260
289
605
790
790
915
1100
250
250
250
250
250
250
300
300
350
500
215
232
300
300
333
320
480
480
480
480
255
415
415
415
455
1350
1450
1450
1450
1450
MODEL
DAMP.
POLES
POT.
MODEL
HVFSW-300
HVFSW-500
HVFSW-750
HVFSW-750
HVFSW-1000
HVFSW-1500
400
800
1200
1200
1600
2000
6
6
6
6
6
175 W
130 W
240 W
240 W
240 W
370 W
D2E-133-D47
DA 9/7 RE
DA 9/9 RE
DA 10/10 RE
DA 10/10 RE
DA 10/10 RE
FAN
3
REHEAT COIL
FLOW RATE m /h
BC-3T-3F-360
BC-6T-3F-545
BC-6T-3F-545
BC-6T-3F-545
BC-6T-3F-670
BC-6T-3F-805
510
850
1200
1200
1600
2500
Dimension table - HVFSW 2000-3000 boxes
MODEL
A
C
D
E
F
G
H
I
J
K
HVFSW-2000
HVFSW-3000
Ø 348
Ø 400
262
262
260
289
1140
1220
250
300
475
800
300
333
480
480
415
455
1450
1450
MODEL
DAMP.
HVFSW-2000
HVFSW-3000
L=450
L=575
POLES
6
6
FAN
POT.
240 W
370 W
MODEL
2xDA 10/10 RE
2xDA 10/10 RE
3
REHEAT COIL
FLOW RATE m /h
BC-6T-3F-845
BC-6T-3F-925
3400
5000
Series HVFS
8
Technical data
Radiated noise. Sound power level dB(A). Minimum pressure (air inlet)
Size
3000
3000
3000
3000
3000
3000
3000
3
Q [l/s]
Q [m /h]
63
125
250
500
1k
2k
4k
8k
86,1
113,9
141,7
169,4
141,7
188,9
236,1
283,3
211,1
283,3
352,8
425
283,3
377,8
472,2
566,7
425
566,7
708,3
850
566,7
755,6
944,4
1133,3
850
1133,3
1416,7
1700
310
410
510
610
510
680
850
1020
760
1020
1270
1530
1020
1360
1700
2040
1530
2040
2550
3060
2040
2720
3400
4080
3060
4080
5100
6120
<
<
<
<
<
<
<
<
7
<
<
<
<
<
<
<
<
<
<
21
<
<
<
22
<
<
23
26
<
22
26
29
<
23
27
30
<
23
27
30
<
23
27
30
21
25
29
32
22
26
30
33
25
30
34
37
21
26
30
33
22
27
30
33
22
27
31
34
22
27
30
34
24
29
33
36
25
30
34
37
29
34
38
41
20
24
28
31
20
25
28
31
20
25
29
32
20
25
29
32
22
27
31
34
24
28
32
35
27
32
36
39
<
<
22
25
<
<
23
26
<
20
23
26
<
<
23
26
<
22
25
29
<
23
27
30
21
26
30
33
<
<
20
23
<
<
20
24
<
<
21
24
<
<
21
24
<
<
23
26
<
20
24
27
<
24
28
31
<
<
<
21
<
<
<
21
<
<
<
22
<
<
<
21
<
<
21
24
<
<
22
25
<
22
25
28
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
22
<
<
<
23
<
<
23
26
Regenerated noise. Sound power level dB(A). Minimum pressure (air inlet)
Octave bands [Hz]
Size
300
500
750
1000
1500
2000
3000
Q [l/s]
3
Q [m /h]
63
125
250
500
1k
2k
4k
8k
86,1
113,9
141,7
169,4
141,7
188,9
236,1
283,3
211,1
283,3
352,8
425
283,3
377,8
472,2
566,7
425
566,7
708,3
850
566,7
755,6
944,4
1133,3
850
1133,3
1416,7
1700
310
410
510
610
510
680
850
1020
760
1020
1270
1530
1020
1360
1700
2040
1530
2040
2550
3060
2040
2720
3400
4080
3060
4080
5100
6120
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
20
<
21
24
27
<
21
25
28
<
22
25
28
<
21
25
28
<
24
28
31
20
25
29
32
24
28
32
35
27
32
35
38
27
32
36
39
27
32
36
39
27
32
36
39
30
35
38
41
31
36
39
43
34
39
43
46
26
30
34
37
26
31
35
38
26
31
35
38
26
31
35
38
29
33
37
40
30
35
38
41
33
38
42
45
<
<
22
25
<
<
22
25
<
<
23
26
<
<
23
26
<
21
25
28
<
22
26
29
21
26
30
33
<
<
<
<
<
<
<
20
<
<
<
20
<
<
<
20
<
<
<
22
<
<
20
23
<
20
24
27
<
20
24
27
<
20
24
27
<
21
25
28
<
21
24
27
<
23
27
30
<
24
28
31
23
28
31
34
<
23
27
30
<
23
27
30
<
24
28
31
<
23
27
30
21
26
30
33
22
27
31
34
26
31
34
37
<: Sound power level <20 dB(A)
Series HVFS
9
Technical data
Overall radiated and regenerated sound levels.
For minimal air inlet pressure
Sound pressure level in dB(A)
Size
300
500
750
1000
1500
2000
3000
Q [l/s]
Q [m3/h]
Radiated noise
(dB(A))
Regenerated noise
(dB(A))
86,1
113,9
141,7
169,4
141,7
188,9
236,1
283,3
211,1
283,3
352,8
425
283,3
377,8
472,2
566,7
425
566,7
708,3
850
566,7
755,6
944,4
1133,3
850
1133,3
1416,7
1700
310
410
510
610
510
680
850
1020
760
1020
1270
1530
1020
1360
1700
2040
1530
2040
2550
3060
2040
2720
3400
4080
3060
4080
5100
6120
25
30
34
37
26
30
34
37
26
31
35
38
26
31
34
38
28
33
37
40
29
34
38
41
33
38
41
45
30
35
39
42
30
35
39
42
31
36
39
43
31
35
39
42
33
38
42
45
34
39
43
46
38
42
46
49
10
Series HVFS