Environmental Monitoring RDU

Total Solutions
for Business-Critical Continuity™
OptimizeIT Manager (RDU-M)
OptimizeIT Manager(RDU-M)
Providing comprehensive monitoring and
management for the new data center
Fully improving the intelligent management level
of the medium data center
The OptimizeIT Manager (RDU-M) can manage multiple monitoring subsystems
at the same time, satisfying the requirements for the intelligent equipment
monitoring, environment monitoring, security monitoring, video monitoring,
access control, etc.
01
System Overview
The OptimizeIT Manager is a management platform for the new data center. With the server as the carrier, it can
realize the real time monitoring and dynamic management on the power environment factors and infrastructures
of the equipment room through the built-in data base and applications. You can easily access the monitoring
functions through the IE browser.
RDU-M
Intelligent
equipment
Environment factors
(Receptacle sensor)
Access control
The third party
and IR
intelligent equipment
Application Scope:
■
Applicable to the medium (and below) and distributed IT
equipment room
Software Platform Consisting of:
ore
on C
icati
Appl
rs
rive
t
n
eme
anag
DB M
ices
n Serv
o
i
t
a
c
Appli
■
■
■
Application Core: Including the database management
module, monitoring equipment management module, data
analysis module, alarm processing module, command module
and data exchange module
nt D
pme
i
Equ
Application Service: composed of the Web service function
modules
Equipment Driver: composed of the data acquisition modules
02
System Features
The OptimizeIT Manager (RDU-M) Has the Following Features:
Modular Design and Expandability
■
■
■
Equipment Integration – Modular, standard port connection, plug-and-play
Function Integration – Integration of the image, access control, environment, power,
equipment and video monitoring
System Integration – Integration of multiple levels of monitoring (equipment room level,
cabinet level and equipment level)
Scientific and Flexible Pre-alarm - prevention of Accidents
■
Multiple Pre-alarm threshold values
■
Multiple Pre-alarm modes
■
Multiple Pre-alarm levels
Security
■
■
■
Linux operating system, stable and not vulnerable to virus
Multilevel authority management (region, equipment type; system management,
operation and view)
RDU-SIC and RDU-A superstratum access authority management
Simple Installation, Use and Maintenance
■
■
■
03
Based on IP network, standard network cable connection, WEB remote access and
centralized management
With the system cloning and backup function, it is simple and convenient for maintenance
Simplified configuration. It can be configured automatically in synchronism with RDU-A/
RDU-SIC, eliminating the trouble of manual configuration
Monitoring Objects and System Parameters
1 Access Control System Management
The access control system has the access control, channel management, real time monitoring, security and
anti-theft alarm functions, and features communication automation, office automation and management
automation.
To ensure the system stability, the hardware of the product adopts the internationally advanced high speed
CPU technology, NV storage technology, accurate clock technology, chip lightning protection design, surge
protection design, anti-interference design, and anti-static design.
The access control equipment of the system is connected to the advanced RDU-M equipment room
monitoring system through IP mode. All the management functions of the access control can be realized
through the equipment room monitoring system.
Access Control Box (ES5010)
Dimensions (Length× Width × Height): 380mm×200mm×69.5mm
Weight: about 2.6Kg
Maximum Connection Distance: 1200m
Display: 6-digit red LED, displaying numbers or simple English characters
Lock Driving Interface: NO/NC contacts
Contact Capacity: DC12V/2A/25Sec, DC24V/2A/25Sec, AC75V/3A/25Sec
Card Reader Port:
Wigan Signal Input Effective Low Level (or OC Door Conduction): -0.7V+0.7V, IOUT MAX =8mA
Wigan Signal Input Effective High Level (or OC Door Shut-off): high
resistance -+4.0V, IOUT MAX =0mA
Wigan 26BIT, 34BIT, 36BIT and 44BIT card number automatic identification
Operating Temperature: -10 ℃ ~+50 ℃
Storage Temperature: -30℃ ~+70℃
Humidity: 5%~95%RH (no condensation)
Communication Converter
Dimensions: 48mm×44mm×24mm
Operating Temperature: -10 ℃ ~+50 ℃
Storage Temperature: -30 ℃ ~+70 ℃
Humidity: 5%RH~95%RH (no condensation)
Interface Standard: conversion between Phoenix
interface and RJ45 interface
04
Electrical Lockset
Outside Button
Rated Operating Voltage: 12V DC
Input Voltage Range: 10.8VDC-13.2VDC
Operating Current: single-opened: 0.48A
Minimum Supply Current: Single-Opened: at
800mA/12V DC input
Rated Power: single-opened: ≤6.2W
Rated Pulling Force: Single-Opened: 270Kg±5Kg
Door Open Mode: 90 degree
Operating Environment:
Temperature: -10~+50℃
Humidity: 20%~90% (no condensation)
Applicable Door Type: applicable to wood door,
glass door without bottom frame (with U support)
and fireproof door
Model: EP67
Maximum Switch Current: 48VDC, 2A
Operating Temperature: -25 ℃ -105 ℃
Button Material: brass with nickel
plating
Panel Material: stainless steel
Mechanical Life: 1,000,000 times
Projecting Button Size: ¢22×2mm
Pane Size: 86×86×6mm
2 Video Monitoring System
DVS Features
■
■
■
05
Adopting the high performance and powerful
high speed video protocol processor
Adopting the optimized H.264 video
compression algorithm to realize smooth
transmission of the HD image at low bandwidth
Built-in Web Server, facilitating the real time
monitoring and settings management of the
front end equipment through standard IE explorer
■
■
■
Supporting remote system upgrade
Supporting dynamic DNS, LAN and Internet (ADSL,
Cable Modem)
Supporting various network protocols: HTTP, TCP/
IP, UDP, STMP, DDNS, DNS, SNTP, DHCP, FTP
■
■
■
■
■
■
Supporting bi-directional voice intercom and voice
broadcasting
Featuring network self-adaptive technology and
automatic adjustment of video frame rate according to
network bandwidth
Alarming functions available for video loss and motion
detection(configurable area and sensitivity)
Various built-in high-speed dome decoder protocol,
supporting the transparent transmission protocol
Supporting video recording / picture capturing
Featuring automatic recovery function upon abnormal
situation and automatic connection upon network
interruption
■
Supporting SD2.0 protocol, supporting up to 32GB
■
Installation method: keeping flat or wall-mounting
Hemisphere Camera Features
■
■
■
■
■
Sony high sensitivity CCD
Automatic white balance tracking and
automatic gain control
DSP digital signal processing and CCD
aperture
Advanced digital back-light compensation
function
Automatic internal/external synchronous
conversion
3 Intelligent System Management
WEB Browser
Hardware Configuration
Network Bandwidth
Power
Voltage
Heat Dissipation
Maximum Surge Current
Height
Width
Thickness
Weight (Maximum Configuration)
Weight (Empty Configuration)
Requirements on Client Operating Environment
IE 6.0 or above version
Hard disk: 1G and above, memory:1G and above;network card:10MB and above
OptimizeIT server bandwidth: 10MB and above
Client bandwidth requirement: 10MB and above
Power Supply
AC power supply equipment (each power supply equipment)
350W(non-redundancy power equipment); 400W(redundancy power equipment)
100-240VAC, 50/60Hz
Maximum: 1571BTU/h (non-redundancy power equipment);
maximum: 1666BTU/h(redundancy power equipment)
Under the typical circuit condition and within the operating range of the overall system environment,
the surge current of every power equipment is likely to reach 25A within 10millisecond or even a
shorter time.
Physical Specification
4.29cm (1.69inch)
43.4cm (17.09inch)
61.26cm (24.12inch)
15kg (33.02 pounds)
5.96kg (13.12 pounds)
4 Environment System Monitoring
Temperature sensor
Alarm LED
Smoke detector
Belt-type flood sensor
IR detector
06
5 RDU-A
The RDU-A intelligent monitoring unit is the acquisition end of the flexible monitoring solutions for the data
center. With the intelligent monitoring platform, it can realize the combined monitoring of the equipment,
environment and safety of the equipment room. Meanwhile, its flexible structural design enables the user to
make flexible and customized configuration according to the specific requirements of various applications.
Software Features:
The user can perform the following operations through Web page:
Browsing detailed status of each equipment, such as environment temperature and humidity, environment
digital values, UPS and precision cooling unit
Sending control commands to the equipment and setting equipment parameter
Viewing the dynamic alarm in case of a new alarm
Inquiring history alarm, history signal data and log
Changing system parameter, such as IP address, time and user information
Changing the site information, equipment name, signal name and alarm level online
Dynamic Equipment Management:
Viewing the type of the installed/removed equipment and dynamically adding, deleting and modifying
equipment
Customizing alarm notice
Downloading/uploading configuration file and system file
Technical Specifications:
Input Voltage
Input Frequency
Total Power
Dimensions (mm)
Weight
Color
Installation Mode
07
100Vac~250Vac
45Hz~65Hz
30W
483(W) ×286(D) × 43 (H)
About 5kg
Black
Rack-mounted
6 Configuration Cases
A customer has the following requirements on the equipment and systems monitored by the power and environment monitoring system:
Integrating the following items into the same system platform: distribution system, UPS system, precision cooling unit, fresh air system,
temperature & humidity / water leakage / early smoke / fire detectors, access control system and security video monitoring system
● The equipment room area is less than 200 sqm
Medium Data Center
SN
1
2
3
4
5
6
7
8
9
10
11
11
12
13
14
15
● The number of server cabinets is more than 15
● The power consumption of the equipment is 25~100KW
Function Requirements
Centralized monitoring and managing platform
Centralized acquisition of the equipment room signals
Monitoring the input distribution box of the equipment room
Monitoring the input distribution box of the equipment room
UPS system monitoring
Precision cooling system monitoring
Fresh air system monitoring
Access control system kits
Sensor expansion module
Temperature & humidity monitoring
Water leakage monitoring
Water leakage monitoring
Smoke monitoring
Video image monitoring
SMS and phone alarm
System networking
Product Name
RDU-M OptimizeIT Manager
RDU-A OptimizeIT acquisition unit
Distribution box monitoring – Smart electricity meter
Distribution box monitoring – AC transformer
SNMP card (for monitoring the intelligent UPS only)
SNMP card (for monitoring the precision cooling system only)
TCP/IP protocol
TCP/IP protocol
4DI 4-way digital signals collector
Temperature and humidity sensor
Cooling unit - belt-type flood sensor
Floor - point-type flood sensor
Smoke detector
45 spherical cameras
G Network SMS Modem
Exchange equipment
08
About Emerson Network Power
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business Critical Continuity? from grid to chip for
telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas
including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls,
infrastructure management, connectivity, solar power, wind power, industrial energy-efficient products and electric vehicle charging stations. All solutions are
supported globally by local Emerson Network Power service technicians. Learn more about Emerson Network Power products and services at:
www.emersonnetwork.com.cn, or call 400-887-6510
About Emerson
Emerson (NYSE: EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering together to provide innovative solutions for
customers in industrial, commercial, and consumer markets through its network power, process management, industrial automation, climate technologies,
and tools and storage businesses. Sales in fiscal 2010 were $21 billion. For more information, visit:
www.emerson.com
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Road, Science & Industry Park,
Nanshan District, 518057 Shenzhen, ChinaTelep
hone: 86-755-86010808
Service Hotline: 4008876510
Postcode: 518057
www.emersonnetwork.com.cn
www.emersonnetworkpower.com
Emerson Network Power
The global leader in enabling Business-Critical Continuity™
AC Power
Embedded Computing
Outside Plant
Racks and Integrated Cabinets
Connectivity
Embedded Power
Power Switching & Controls
Services
DC Power
Infrastructure Management & Monitoring
Precision Cooling
Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2011 Emerson Electric Co.
E-X6216368-0211