excom® remote I/O system - TURCK

excom® remote I/O system
Input module, analog, 4-channel
AI401Ex
The input module AI401Ex is used for the
connection of 2-wire transducers (active input = source mode / transducer passive) or 4wire transducers (passive input = sink mode /
transducer active).
The module features protection class Ex ib IIC
and can be mounted in zone 1 in combination
with excom®. The field circuits feature protection class Ex ia IIC resp. Ex iaD.
■
■
Input module for the connection of passive transmitters (active inputs) or active transmitters (passive inputs).
Complete galvanic isolation
The measuring range is digitized in the scope
of 0…21 mA. For clear reading, the digitized
value is displayed in a range of 0 … 21000
(independent of the parametrized measuring
range) and transmitted to the host system.
Edition • 2014-10-24T20:47:24+02:00
The field circuits are galvanically isolated from
each other.
HART® compatible transducers can be connected to the module. The field device can
thus be parametrized directly at the terminals
on the DIN rail with a licensed modem. An additional impedance in the circuit is not necessary.
1/3
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
excom® remote I/O system
Input module, analog, 4-channel
AI401Ex
AI401Ex
6884204
Supply voltage
Power consumption
Galvanic separation
Number of channels
via the backplanes, central power supply
ð 2.2 W
complete galvanic isolation acc. to EN 60079-11
4-channel
Input circuits
Supply voltage
Overload capability
Low level control
Short-circuit
Wire-break
intrinsically safe acc. to EN 60079-11
0/4…20 mA
15 VDC at 20 mA
> 21 mA
< 3.6 mA
> 24 mA (only in live zero mode)
< 2 mA (only in live zero mode)
Resolution
Linearity deviation
Temperature drift
Rise time/fall time
Max. measurement tolerance under EMC influence
14 Bit
ð 0.05 % full scale
ð 0.005 % / K
ð 50 ms (10 … 90 %)
ð 0.1 %
Ex approval acc. to conformity certificate
Device designation
Device marking
Max. values:
Max. output voltage Uo
Max. output current Io
Max. output power Po
Internal resistance Ri
Characteristic
Internal inductance/capacitance Li/Ci
PTB 03 ATEX 2217
É II 2 (1) G Ex ib [ia] IIC T4
É II (1) D [Ex iaD]
Terminal connection: 1+2
ð 19.1 V
ð 90 mA
ð 615 mW
304 ò
trapezoidal
Li
Ci
External inductance/capacitance Lo/Co
Lo [mH]
Co [nF]
Max. values:
Max. output voltage Uo
Max. output current Io
Max. output power Po
Characteristic
Internal inductance/capacitance Li/Ci
negligibly small
negligibly small
IIC
0.20
170
IIB
1.0
960
Terminal connection: 3+4
ð 6 V
ð 2.5 mA
ð 4 mW
linear
Li
Ci
External inductance/capacitance Lo/Co
Lo [mH]
Co [nF]
Edition • 2014-10-24T20:47:24+02:00
Dimensions
Type code
Ident no.
negligibly small
negligibly small
IIC
10
1900
Indication
Operational readiness
State/ Fault
1 x green / red
4 x red
Housing material
Connection mode
plastic
module, plugged on rack
Protection class
Ambient temperature
Relative humidity
Vibration test
Shock test
EMC
IP20
-20…+70 °C
ð 95 % at 55 °C acc. to EN 60068-2
acc. to IEC 60068-2-6
acc. to IEC 60068-2-27
acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
77 acc. to SN 29500 (Ed. 99) 40 °C
18 x 118 x 103 mm
75 g
MTTF
Dimensions
Weight
2/3
IIB
20
8600
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
excom® remote I/O system
Input module, analog, 4-channel
AI401Ex
ATEX
cFMus
TR CU
CMI
INMETRO
GL
DNV
BV
LR
Edition • 2014-10-24T20:47:24+02:00
Approvals and certificates
3/3