General Technical Specifications

Basic Technical Specifications for
Tokyo-Chubu HVDC Interconnection Project
[General Technical Specifications]
Note)The terms of this [General Technical Specifications] are subject to change according to the further study in future.
Basic technical specifications for the Tokyo-Chubu HVDC Interconnection Project
(expected to be brought into operation in FY 2020) are as follows at this point.
 AC/DC conversion:Line-commutated type
 Rated capacity:900MW (450MW 2units)
 DC voltage:±200kV
 Frequency:(Tokyo side) 50Hz / (Chubu side) 60Hz
 Telecommunication:Microwave link×2route
Tokyo Electric Power Co., Inc.
Chubu Electric Power Co., Inc.
1
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved
1. Outline of Tokyo-Chubu HVDC Interconnection Project
【Increase power interchange capacity between 50Hz/60Hz areas by 900MW】
 Install HVDC interconnection 900MW to be brought into operation in FY 2020.
Azumi Shin-Takasegawa
MinamiFukumitsu
Midono
Hokuriku EPCO
BTB
300MW
500kV
Etsumi trunk line
(T-branch)
Etsumi
trunk line
Gifu
Add 900MW
converter
(Tokyo side)
Chubu EPCO
Chubu EPCO
Pumped-storage power plant
generator mode:2150MW
pumping mode :1850MW
500kV transmission line
Azumi trunk line (partially upgraded)
Tokyo EPCO
Shin-Shinano
HVDC line 90km
Construct a new
converter station
(Chubu side)
Tokyo EPCO
FC
600MW
Chubu EPCO
Chushin
500kV substation
275kV substation
500kV transmission line
275kV transmission line
Hokubu
Takane #1
Mazegawa #1
FC・BTB
AC/DC converter
Hydropower station
Switching station
Constructed by Tokyo EPCO
Constructed by Chubu EPCO
2
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved
2-1. Equipment(at Tokyo EPCO's Shin-Shinano substation)
◇ List of Equipment
Name of equipment
・Thyristor valve
450MW 2units
・Converter transformer
560MVA,154kV/87kV 2units
・DC smoothing reactor
AC/DC converter
・AC harmonic filter
equipment
・DC harmonic filter
AC equipment
Quantity
1H 2units
5th・7th 2banks,11th・13th・HP 2banks
12th(HP) 2banks
・Phase modifying equipment
Leading 300Mvar,Lagging 300MVar
・DC switchgear
1set
・Step-down transformer
500MVA,500kV/154kV/66kV 2units
・500kV・154kV・66kV AC switchgear
500kV 2bays,154kV 9bays,66kV 2bays
◇ Circuit Configuration
154kV
AC switchgear
CB
AC harmonic filter
(5th, 7th)
CB
Phase modifying
equipment
CB
DC switchgear
DC
smoothing
reactor
AC harmonic filter
(11th, 13th, HP)
LS
CB
CB
DC
harmonic
filter
CB
500kV
AC switchgear
Step-down transformer
CB
Converter transformer
To 60Hz side
Thyristor valve
LS
Converter transformer
DC
harmonic
filter
CB
Step-down transformer
CB
LS
CB
AC harmonic filter
(11th, 13th, HP)
CB
CB
CB
DC
smoothing
reactor
AC harmonic filter
(5th, 7th)
Phase modifying
equipment
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved
3
2-2. Equipment(at Chubu EPCO's new converter station)
◇ List of Equipment
Name of equipment
Quantity
・Thyristor valve
450MW 2units
・Converter transformer
560MVA, 154kV/87kV 2units
・DC smoothing reactor
AC/DC converter
・AC harmonic filter
equipment
・DC harmonic filter
5th・7th 2banks, 11th・13th・HP 2banks
12th(HP) 2banks
・Phase modifying equipment
SC 60MVA 6banks,ShR 80MVA 4units
・DC switchgear
1set
・Step-down transformer
500MVA, 500kV/154kV/77kV 2units
・500kV・154kV・77kV AC switchgear
500kV 5bays, 154kV 9bays, 77kV 2bays
◇ Circuit Configuration
Phase modifying
equipment
500kV
AC switchgear
CB
CB
AC harmonic filter
(11th, 13th, HP)
CB
AC harmonic filter
(5th, 7th)
DC
smoothing
reactor
DC switchgear
DS
CB
Transmission line #1
154kV
AC switchgear
CB
AC equipment
1H 2units
CB
DC
harmonic
filter
CB
Step-down transformer
CB
CB
Converter transformer
Step-down transformer
DS
To 50Hz side
DC
harmonic
filter
CB
CB
CB
CB
Transmission line #2
CB
Thyristor valve
Converter transformer
Phase modifying
equipment
CB
AC harmonic filter
(5th, 7th)
CB
AC harmonic filter
(11th, 13th, HP)
DS
DC
smoothing
reactor
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved
4
3-1. Tentative Layout(of Tokyo EPCO's Shin-Shinano substation)
5
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved
3-2. Tentative Layout(of Chubu EPCO's new converter station)
250m
AC 500kV
Etsumi
trunk line
Main
building
AC equipment
(Switchgear・Transformer)
AC500/154/77kV
Space for temporary works
and future replacement
AC equipment
(Switchgear)
AC154kV
to Tokyo EPCO's
Shin-Shinano S/S
Entrance of
converter station
AC77kV
AC equipment
Phase
modifying
equipment
DC equipment
AC154kV
Transformer
Thyristor valve
Switchgear
DC smoothing reactor
DC harmonic filter
AC equipment
(AC harmonic filter)
DC 200kV
AC154/87kV
DC200kV
N
6
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved
4-1. Scope of Work (for Tokyo EPCO's Shin-Shinano substation)
◎At this stage we haven't decided how to combine and order the items.
Item
AC/DC converter
System design
Specification
Rated capacity
900MW(450MW 2units)
Rated voltage/
Rated current
±200kV/2250A
Frequency
50Hz
Control method
Target availability
Thyristor valve
Converter
transformer
DC
smoothing
reactor
AC
harmonic
filter
12 phase
collective control
More than 97%
at equivalent bipolar
outage time※
Insulation
Indoor air insulated
Rated voltage/
Rated current
200kV/2250A
Capacity
560MVA
(280MVA 2stages)
Rated voltage
154kV/87kV
Connection
Y-Y, Y-D
Inductance
1H
Rated voltage/
Rated current
200kV/2250A
Rated voltage
154kV
Branch
configuration
5th,7th,11th,13th,HP
Item
DC
harmonic
filter
Phase modifying
equipment
Specification
Rated voltage
200kV
Branch
configuration
12th(HP)
Leading Capacity
300MVar
Lagging Capacity
300MVar
Insulation
(outdoor) air insulated
Rated voltage
200kV
Capacity
500MVA
Rated voltage
500kV/154kV/66kV
Connection
Y-Y-D
Insulation
SF6 gas insulated
Insulation
SF6 gas insulated
Insulation
SF6 gas insulated
DC switchgear
Step-down
transformer
AC switchgear
(500kV)
AC switchgear
(154kV)
AC switchgear
(66kV)
※Note)Equivalent bipolar outage time:Interrupted capacity and outage time
are converted to equivalent outage time for bipolar capacity
(ex. Monopole 450MW×2days ⇒ Bipolar 900MW×1day)
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved
7
4-2. Scope of Work (for Chubu EPCO's new converter station)
◎At this stage we haven't decided how to combine and order the items.
Item
AC/DC converter
System design
Specification
Rated capacity
900MW(450MW 2units)
Rated voltage/
Rated current
±200kV/2250A
Frequency
60Hz
Control method
Target availability
Insulation
Thyristor valve
Converter
transformer
AC
harmonic
filter
Indoor air insulated
Rated voltage/
Rated current
200kV/2250A
Capacity
560MVA
(280MVA 2stages)
Rated voltage
Connection
DC
smoothing
reactor
12 phase
collective control
More than 97%
at equivalent bipolar
outage time※
Inductance
Item
DC
harmonic
filter
Phase modifying
equipment
(77kVSC)
Phase modifying
equipment
(77kVShR)
Specification
Rated voltage
200kV
Branch
configuration
12th(HP)
Capacity
60MVA 6banks
Capacity
80MVA 4units
Insulation
SF6 gas insulated
Rated voltage
200kV
Capacity
500MVA
Rated voltage
500kV/154kV/77kV
Connection
Y-Y-D
Insulation
SF6 gas insulated
Insulation
SF6 gas insulated
Insulation
SF6 gas insulated
DC switchgear
Step-down
transformer
154kV/87kV
Y-Y, Y-D
1H
Rated voltage/
Rated current
200kV/2250A
Rated voltage
154kV
Branch
configuration
5th,7th,11th,13th,HP
AC switchgear
(500kV)
AC switchgear
(154kV)
AC switchgear
(77kV)
※Note)Equivalent bipolar outage time:Interrupted capacity and outage time
are converted to equivalent outage time for bipolar capacity
(ex. Monopole 450MW×2days ⇒ Bipolar 900MW×1day)
8
©Tokyo Electric Power Co., Inc. Chubu Electric Power Co., Inc. All Rights Reserved