Data Sheet (English)

Compact Multiprotocol I/O Module for Ethernet
16 Digital PNP Inputs
TBEN-L4-16DIP
■ EtherNet/IP™, Modbus® TCP, or
PROFINET® slave
■ Integrated Ethernet switch
■ Supports 10 Mbps/100 Mbps
■ 2 x M12, 4-pin, D-coded, Ethernet fieldbus connection
■ Glass fiber reinforced housing
■ Shock and vibration tested
■ Fully potted module electronics
■ Protection classes IP65, IP67, IP69K
■ 7/8" connector for power supply, 4-pin
■ Input diagnostics per port
Type designation
Ident no.
Supply
Supply voltage
Admissible range
Voltage supply connection
Sensor/Actuator supply VAUX1
Edition • 2017-04-03T09:39:58+02:00
Electrical isolation
TBEN-L4-16DIP
6814009
24 VDC
18…30 VDC
Total current max. 9 A per voltage group
Total current V1 + V2 max. 11 A
4-pin male 7/8" connector
supply of ports C0-C7 from V1
short-circuit proof, 120 mA per port
galvanic isolation of the voltage groups V1 and V2,
voltages up to 500 VAC
System data
Fieldbus transmission rate
Fieldbus connection technology
Protocol detection
Web server
Service Interface
10 Mbps/100 Mbps
2 x M12, 4-pin, reverse-keyed
automatic
default: 192.168.1.254
Ethernet via P1 or P2
Field Logic Controller (FLC)
Supported from firmware version
Released from ARGEE version
3.2.9.0
2.0.24.0
Modbus TCP
Addressing
Supported function codes
Number of TCP connections
Input register start address
Output register start address
Static IP, BOOTP, DHCP
FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
8
0 (0x0000 hex)
2048 (0x0800 hex)
EtherNet/IP™
Addressing
Quick Connect (QC)
Device Level Ring (DLR)
Number of TCP connections
Number of CIP connections
Input Assembly Instance
Output Assembly Instance
Configuration Assembly Instance
acc. to EtherNet/IP™ specification
< 150 ms
supported
3
10
103
104
106
1/5
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Compact Multiprotocol I/O Module for Ethernet
16 Digital PNP Inputs
TBEN-L4-16DIP
PROFINET
Addressing
Conformance class
MinCycleTime
Fast Start-Up (FSU)
Diagnostics
Topology detection
Automatic addressing
Media Redundancy Protocol (MRP)
Digital inputs
Number of channels
Connectivity inputs
Input type
Type of input diagnostics
Switching threshold
Low level signal voltage
High level signal voltage
Low level signal current
High level signal current
Input delay
Potential separation
Standard/Directive conformity
Vibration test
Shock test
Drop and topple
Electro-magnetic compatibility
Approvals and certificates
UL conditions
General Information
Dimensions (W x L x H)
Operating temperature
Storage temperature
Altitude
Protection class
MTTF
Housing material
Housing color
Window material
Material screw
Material label
Halogen-free
Mounting
DCP
B (RT)
1 ms
< 150 ms
acc. to PROFINET alarm handling
supported
supported
supported
16
M12, 5-pin
PNP
group diagnostics
EN 61131-2 Typ 3, PNP
<5V
> 11 V
< 1.5 mA
> 2 mA
2.5 ms
galvanic isolation to P1/P2
, voltages up to 500 VDC
acceleration to 20 g
acc. to EN 60068-2-6
acc. to EN 60068-2-27
acc. to EN 60068-2-31/IEC 60068-2-32
acc. to EN 61131-2
CE
cULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
60.4 x 230.4 x 39mm
-40…+70 °C
-40…+85 °C
max.5000 m
IP65
IP67
IP69K
205 years
PA6-GF30
Black
Lexan
303 stainless steel
Polycarbonate
yes
2 mounting holes � 6.3 mm
Edition • 2017-04-03T09:39:58+02:00
Note the numbering of the IO range:
From firmware version 3.2.9.0 and higher ports C0
to C7 and channels CH0 to CH15 are counted. The
process data image is unchanged. For more details
on the corresponding change see manual.
2/5
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Compact Multiprotocol I/O Module for Ethernet
16 Digital PNP Inputs
TBEN-L4-16DIP
Note
M12 x 1 Ethernet
Ethernet cable (example):
RSSD-RSSD-441-2M/S2174
ID number 6914218
Note
M12 x 1 Input
Actuator and sensor cable/PUR cable (example):
RKC4.4T-2-RSC4.4T/TXL
ID number 6625608
Extension cable with Y piece for single assignment (example):
FSM4-2WAK3-1/1/P00
ID number 8009560
Note
7/8'' Power Supply
Power supply cable (example):
RKM43-1-RSM43
Edition • 2017-04-03T09:39:58+02:00
ID number 6914312
3/5
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Compact Multiprotocol I/O Module for Ethernet
16 Digital PNP Inputs
TBEN-L4-16DIP
Module LED Status
LED
Color
Status
Description
ETH1 / ETH2
Green
ON
Ethernet link (100 Mbps)
flashing
Ethernet communication (100 Mbps)
ON
Ethernet link (10 Mbps)
flashing
Ethernet communication (10 Mbps)
OFF
No Ethernet link
ON
Active connection to a master
flashing
Ready
ON
IP-address conflict or Restore Mode or Modbus timeout
flashing
Blink/Wink command active
Yellow
BUS
Green
Red
Green/Red alternating
ERR
PWR
Autonegotiation and/or waiting for DHCP/Boot-P addressing
OFF
Power off
Green
ON
Diagnostics disabled
Red
ON
Diagnostics enabled
Green
ON
Power supply V1 OK
OFF
V1 power off or below defined tolerance of 18 V
LED Status I/O
Color
Status
Description
Green
ON
Input active
Red
flashing
Power overload at the corresponding port. Both port LEDs are flashing.
OFF
Input inactive
Edition • 2017-04-03T09:39:58+02:00
LED
LED 0 … 15
4/5
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Compact Multiprotocol I/O Module for Ethernet
16 Digital PNP Inputs
TBEN-L4-16DIP
Process Data Mapping of the Single Protocols
For more details on the corresponding protocols see manual.
Modbus TCP Register Mapping
Reg
Inputs (RO)
Status (RO)
0x0000
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
DI15
DI14
DI13
DI12
DI11
DI10
DI9
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
C7P2
C7P4
C6P2
C6P4
C5P2
C5P4
C4P2
C4P4
C3P2
C3P4
C2P2
C2P4
C1P2
C1P4
C0P2
C0P4
-
FCE
-
-
CFG
COM
V1
-
V2
-
-
-
-
-
-
0x0001
Bit 0
Diag
Warn
Diag (RO)
0x0002
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I/O
Diag
I/O Diag (RO)
0xA000
SCS7
SCS6
SCS5
SCS4
SCS3
SCS2
SCS1
SCS0
Bit 0
EtherNet/IP™ data mapping with activated scheduled diagnostics, default settings
Word
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
V1
-
V2
-
-
-
-
-
-
Input data (Station -> Scanner)
GW Status
1
-
FCE
-
-
CFG
COM
Diag
Warn
Inputs
2
Diag 1
DI15
DI14
DI13
DI12
DI11
DI10
DI9
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
C7P2
C7P4
C6P2
C6P4
C5P2
C5P4
C4P2
C4P4
C3P2
C3P4
C2P2
C2P4
C1P2
C1P4
C0P2
C0P4
-
-
Sched
-
-
-
-
-
-
-
-
-
-
-
-
3
I/O
Diag
Diag 2
Diag
4
SCS7
SCS6
SCS5
SCS4
SCS3
SCS2
SCS1
SCS0
Bit 0
EtherNet/IP™ data mapping with activated summarized diagnostics
Word
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
V1
-
V2
-
-
-
-
-
-
Input data (Station -> Scanner)
GW Status
1
-
FCE
-
-
CFG
COM
Diag
Warn
Inputs
2
Diag 1
DI15
DI14
DI13
DI12
DI11
DI10
DI9
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
C7P2
C7P4
C6P2
C6P4
C5P2
C5P4
C4P2
C4P4
C3P2
C3P4
C2P2
C2P4
C1P2
C1P4
C0P2
C0P4
3
-
I/O
Diag
PROFINET Process Data
Byte
Inputs
0
1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
C3P2
C3P4
C2P2
C2P4
C1P2
C1P4
C0P2
C0P4
DI15
DI14
DI13
DI12
DI11
DI10
DI9
DI8
C7P2
C7P4
C6P2
C6P4
C5P2
C5P4
C4P2
C4P4
Key:
Digital input channel x
CFG
I/O Configuration error
DOx
Digital output channel x
FCE
I/O-ASSISTANT Force Mode active
Cx
Port x
I/ODiag
I/O diagnostics connected
Px
Pin x
SchedDiag
Manufacturer-specific diagnostics configured and active
DiagWarn
Diagnostic at least on 1 channel
SCSx
Short-circuit at port x
V1
Undervoltage V1
SCG1
Short-circuit supply ports C0-C3
V2
Undervoltage V2
SCG2
Short-circuit supply ports C4-C7
COM
Communication error on internal module bus
SCOx
Short-circuit output channel x
Edition • 2017-04-03T09:39:58+02:00
DIx
5/5
Bit 0
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com